PIN: 20153150010000
Property Address: 201 E 61ST ST
City - Zip: CHICAGO - 60637
2023 Property Class: 517
2023 Township: 70 - Hyde Park
2023 Neighborhood: 70010
2023 Tax District: 70127
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 39 Violations
Violation Inspector Comments Address Category Status View
PRV RECEIVER 450 PSIG FOR THE FOLLOWING ONE 3/8 TON REMOTE REFRIGERATION UNIT LOCATED ON TOP OF THE W.I.C. THAT SERVES THE W.I.C.. 201 E 61ST ST PERIODIC PASSED View
PRV HIGH SIDE FOR ONE COPELAND 1.5 HP. COMPRESSOR SERVING COOLER. COPRESSOR LOCATED IN BASMENT. 201 E 61ST ST PERIODIC FAILED View
CONNECT VENT LINE FOR ONE COPELAND 1.5 HP. COMPRESSOR LOCATED IN THE BASEMENT SERVING COOLER 201 E 61ST ST PERIODIC FAILED View
PRV HIGH SIDE FOR ONE COPELAND 1.5 HP. COMPRESSOR SERVING COOLER. COPRESSOR LOCATED IN BASMENT. 201 E 61ST ST PERIODIC CLOSED View
CONNECT VENT LINE FOR ONE COPELAND 1.5 HP. COMPRESSOR LOCATED IN THE BASEMENT SERVING COOLER 201 E 61ST ST PERIODIC CLOSED View
PROTECT SIDEWALK DURING CONST 201 - SOUTH WALL IS DEFLECTION OVER PUBLIC WALK WAY. SOUTHWEST CORNER HAS SHIFTING BRICKS. REQUIRES A CANOPY OVER PUBLIC WALK. 201 E 61ST ST COMPLAINT FAILED View
SUBMIT 2 COPY STRUCTURAL RPT 201 - SOUTH WALL AND SOUTHWEST CORNER WALLS WILL REQUIRE A STRUCTURAL ENGINEER'S REPORT. WEST PARAPET IS COVERED IN PLYWOOD, NEED REMOVED TO INSPECT. 201 E 61ST ST COMPLAINT FAILED View
SUBMIT STRUCT. ENG. RPT (INT.) 201 - FLOOR BEHIND BUTCHER AREA HAS DEFLECTION WHEN WALKED ON. FLOOR JOIST BELOW IN BASEMENT HAS ROTTED AND SPLIT JOIST. SCREW TYPE JACKS ARE USED FOR SHORING AND ARE SITTING ON UNKNOWN FOOTINGS. WILL REQUIRE A STRUCTURAL ENGINEER'S REPORT. 201 E 61ST ST COMPLAINT FAILED View
OBSTRUCTIONS IN EXIT WAY 201 - EAST REAR EXIT DOOR PADLOCKED AND SPRAY FOAMED SHUT. STEEL SECURITY GATE CHAINED AND LOCKED. 201 E 61ST ST COMPLAINT FAILED View
REPAIR FLOOR 201 - NUMEROUS BROKEN FLOOR TILES ON INTERIOR OF STORE. 201 E 61ST ST COMPLAINT FAILED View
CONNECT GAS APPLIANCE TO VENT 201 - FURNACE AND FURNACE FLUE PIPE HAVE EFFLORESCENCE CAUSED BY NO DRAFT. 201 E 61ST ST COMPLAINT FAILED View
REPAIR INTERIOR STAIR SYSTEM 201 - STAIRS FROM GRADE TO BASEMENT ARE LOOSE AND BECOMING UNATTACHED, STRINGER IS CRACKED, TREAD HEIGHTS VARY. 201 E 61ST ST COMPLAINT FAILED View
1-HR HEATING PLANT ENCLOSURE 201 - FURNACE ENCLOSURE HAS EXPOSED STUDS AND IS LACKING THE REQUIRED ONE HOUR FIRE RATING. 201 E 61ST ST COMPLAINT FAILED View
INTERIOR FINISH FIRERESISTANCE 201 - EAST AND WEST WALL HAVE WOOD PANELING AND IS REQUIRED TO HAVE THE APPROPRIATE FIRE RESISTANCE. (15-8-370, 15-12-340) 201 E 61ST ST COMPLAINT FAILED View
WORK NOT ALLOWED 201 - SOUTH STEEL PICKET FENCE OVER 5 FT. REDUCE HEIGHT, REMOVE OR OBTAIN PERMIT. 201 E 61ST ST COMPLAINT FAILED View
SOIL/WASTE,VENT PIPE MATRL 201 - REMOVE ALL PVC WASTE AND VENT PIPING AT THREE COMPARTMENT SINK 1ST FLOOR SOUTH ELEVATION AND BASEMENT SOUTH AND EAST ELEVATION. 201 E 61ST ST COMPLAINT FAILED View
PROPER MATRL WATER SUPPLY PIPE 201 - FLEXIBLE SUPPLY ON TOILET SOUTH ELEVATION. 201 E 61ST ST COMPLAINT FAILED View
PROVIDE AIR CHAMERS 201 - NO AIR CHAMBERS ON LAVATORY IN RESTROOM SOUTH ELEVATION. 201 E 61ST ST COMPLAINT FAILED View
PROVIDE 201 - PROVIDE FLOOR DRAIN FOR WATER HEATER WEST ELEVATION OF BASEMENT. (18-29-412.1) 201 E 61ST ST COMPLAINT FAILED View
OBTN PERMIT FOR PLUMBING WORK PERMIT FOR VIOLATIONS. 201 E 61ST ST COMPLAINT FAILED View
LICENSED BONDED PLMBG CONTRCTR OBTAIN A LICENSED PLUMBER TO DO PLUMBING WORK. 201 E 61ST ST COMPLAINT FAILED View
DEFECTIVE LIGHTING SERVICE 201 - REPLACE DEFECTIVE POWER SERVICE AND PROPERLY TERMINATE CIRCUIT BREAKERS. RELOCATE PANEL AWAY FROM STAIRCASE TO BASEMENT. 201 E 61ST ST COMPLAINT FAILED View
DEFECTIVE FIXTURES 201 - REPLACE DEFECTIVE LIGHT FIXTURES ON EXTERIOR AND INTERIOR. PROPERLY WIRE FLUORESCENTS INSIDE STORE. 201 E 61ST ST COMPLAINT FAILED View
EXPOSED WIRING 201 - REMOVE EXPOSED WIRING AT LIGHT FIXTURES, CONNECTIONS AT MEAT CASE AND IN BASEMENT - DANGEROUS AND HAZARDOUS. REMOVE ALL TILES TO COMPLETE RE-INSPECTION OF ELECTRICAL CONNECTIONS. 201 E 61ST ST COMPLAINT FAILED View
SYSTEM III 201 - INSTALL EMERGENCY LIGHTING SYSTEM III. REMOVE UNAPPROVED EXIT SIGNS AND INSTALL BATTERY PACKS THROUGHOUT STORE AND ADDITIONAL EXIT SIGNS. 201 E 61ST ST COMPLAINT FAILED View
201 - (18-27-110.12E) REMOVE ABANDONED ELECTRICAL EQUIPMENT IN CEILING AND BASEMENT. 201 E 61ST ST COMPLAINT FAILED View
DEFECTIVE OUTLETS 201 - REPLACE DEFECTIVE OUTLET AT REAR OF STORE MOUNTED ON WALK-IN COOLER. 201 E 61ST ST COMPLAINT FAILED View
INSTALL ILLUMINATION 201 - INSTALL ILLUMINATION TO BASEMENT AND FURNACE ROOM. 201 E 61ST ST COMPLAINT FAILED View
INSTALL COVERS 201 - INSTALL COVERS TO ALL OPEN BOXES IN CEILING AND BASEMENT. 201 E 61ST ST COMPLAINT FAILED View
UNAPPROVED CORDS 201 - REMOVE ALL ROMEX CONNECTIONS TO ELECTRICAL SYSTEM IN CEILING. 201 E 61ST ST COMPLAINT FAILED View
(13-12-360) PROVIDE PERMIT TO CORRECT VIOLATIONS. 201 E 61ST ST COMPLAINT FAILED View
SEE INSPECTOR COMMENTS 201 - (18-27-110.14) ELIMINATE LOOSE AND IMPROPER CONNECTIONS TO ELECTRICAL PANEL, MEAT CASE, AND LIGHT FIXTURES. 201 E 61ST ST COMPLAINT FAILED View
201 - (18-27-110.12) INSTALL CONDUITS AT COUNTER AREA IN WORKMANLIKE MANNER. 201 E 61ST ST COMPLAINT FAILED View
RECONNECT VENT LINE VENT LINE DISCONNECTED 201 E 61ST ST PERIODIC CLOSED View
NO BARBED WIRE ON FENCE < 8FT 201 - SOUTH STEEL PICKET FENCE HAS RAZOR WIRE. 201 E 61ST ST COMPLAINT FAILED View
201 - INSTALL GFCI'S TO MEAT CASE RECEPTACLES. (18-27-210.8) 201 E 61ST ST COMPLAINT FAILED View
PROVIDE 201 - FLOOR CONSTRUCTION OVER BASEMENT REQUIRES A FIRE RESISTANCE OF NOT LESS THAN ONE HOUR. 6(13-60-200) 201 E 61ST ST COMPLAINT FAILED View
UNAPPROVED CORDS 201 - REMOVE EXTENSION CORDS AND INSTALL ADDITIONAL OUTLETS TO AVOID USE OF CORDS. 201 E 61ST ST COMPLAINT FAILED View
PROVIDE 201 - NUMEROUS AISLES ARE REDUCED AS FOLLOWS 26 1/2", 25", 34", 30", 27", 31", 17", 28", 28 1/2" BEHIND EMPLOYEE COUNTER AREA. (15-4-880) 201 E 61ST ST COMPLAINT FAILED View