Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SEE INSPECTOR COMMENTS | OBTAIN PERMIT TO CORRECT VIOLATIONS AND FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES, WIRE, DEVICES AND EQUIPMENT. MISCELLANEOUS MODIFICATIONS VARIOUS. BASEMENT UNDER UNDERGOING FULL ELECTRICAL MODIFICATION. NO PERMITS. (14A-4-404.6) | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
PROVIDE ANY REQUIRED ROUGH INSPECTIONS FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES, WIRE, DEVICES AND EQUIPMENT. MISCELLANSOUS MODIFICATIONS VARIOUS. BASEMENT UNDERGOING FULL ELECRTICAL REMODEL. NO PERMITS. (14A-5-505.2) | 4948 W NORTH AVE | COMPLAINT | FAILED | View | |
SEE INSPECTOR COMMENTS | SEE NOTICE #11370 | 4948 W NORTH AVE | PERMIT | PASSED | View |
1HR FLR OVER BSMT, 1 OR 2 DU | TOTAL LACK OF FIRE SEPERATION AT BASEMENT CEILING. 1 HR REQUIRED. 5/8" TYPE X FIRECODE. D&H | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
PERMIT REQUIRED - CONTRACTOR | PERMIT REQUIRED FOR INSTALLATION OF DRYWALL AT BASEMENT CEILING | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
INSTALL SMOKE DETECTORS | MISSING THROUGH-OUT. D&H | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
DEBRIS, EXCESSIVE | ORGANIZE/ REMOVE EXCESSIVE STOCK IN BASMENT. FIRE HAZARD | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
CORD TO FIXTURE | UNAPPROVED CORD WIRED LIGHT FIXTURES. DAMAGED CORD WIRED LIGHT FIXTURES. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
CLASS B DOOR IN STAIRWELL | B- CLASS DOOR LEADING TO BASEMENT REQUIRED. D&H | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
PROVIDE | AISLES THROUGHT REDUCED DOWN TO 24 INCHES. 36" AISLES MINIMUM REQUIRED THROUGH-OUT. D&H | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
DEFECTIVE SERVICE | WOOD SERVICE MAST AND SUPPORTS DETERIORATED. MAIN DISCONNECT/PANEL MISSING FILLERS. ENSURE SERVICE IN APPROVED CONDITION. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
EXPOSED WIRING | OPEN WIRING VISIBLE AT EXTERIOR AND INTERIOR. REMOVE WHERE REQUIRED. DANGEROUS AND HAZARDOUS | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
ABANDONED EQUIPMENT | REMOVE ABANDONED REFRIGERATION EQUIPMENT WALK IN COOLER AND FREEZER AT FIRST FLOOR. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
ENGAG LIC & BOND PLMBNG CNTRC | 4948 W NORTH AVE | COMPLAINT | FAILED | View | |
WORKING SPACE | ELECTRICAL PANEL COMPLETELY INACCESSIBLE, PANEL BLOCKED BY STORAGE, DEBRIS AND CLUTTER. DANGEROUS AND HAZARDOUS | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
OBTAIN PERMIT FOR PLUMBING | 4948 W NORTH AVE | COMPLAINT | FAILED | View | |
RESTORE EXIT AND EM | UNABLE TO TEST EXISTING EMERGENCY LIGHTING SYSTEM. INSUFFICIENT BATTERY LIGHTS. DANGEROUS AND HAZARDOUS | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
PROPER SIZE GRD ELECTRODE COND | NO VISIBLE WATER GROUND. ENSURE SERVICE GROUNDED IN APPROVED MANNER. DANGEROUS AND HAZARDOUS | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | OPEN BOXES VARIOUS AREAS EXTERIOR AND INTERIOR. CLOSE WHERE WHERE REQUIRED. DANGEROUS AND HAZARDOUS | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
SUPPORT FIXTURES | LIGHT FIXTURES NOT SUPPORTED IN APPROVED MANNER EXTERIOR AND INTERIOR. SUPPORT IN APPROVED MANNER WHERE REQUIRED. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
LISTED FOR USE TEMP & LOCATION | ALL EXTERIOR LIGHT FIXTURES, BOXES, RACEWAYS MUST BE SUITABLE FOR WET LOCATION. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
INSTALL GFCI'S | INSTALL GFCI PROTECTION KITCHEN, BATH, BASEMENT, EXTERIOR, WET LOCATIONS. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | DAMAGED HANGING LIGHT FIXTURES, MISSING FIXTURE COVERS. REPLACE/REPAIR WHERE REQUIRED. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
ADD RECEPTACLES | ADD RECEPTACLES WHERE REQUIRED TO PREVENT EXCESSIVE USE OF CORDS. APPEARS EXCESSIVE CORDS REAR COUNTER/STOREAGE AREA. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
ARMORED CABLE | EXCESSIVE UNSUPPORTED ARMORED CABLE THROUGHOUT BASEMENT AREA. REMOVE AND/OR INSTALL IN APPROVED MANNER WHERE REQUIRED. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | MISSING THROUGH-OUT D&H | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
STOP/REMOVE NUISANCE | REMOVE TIRES, LAWN MOWERS, SNOW BLOWERS, ETC FROM BASEMENT AREA. FIRE HAZARD | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
REPAIR FLOOR | FLOOR BY REAR EGRESS MISSING TILE WITH DAMAGED SUBFLOOR CAUSING A TRIP HAZARD. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
REPAIR DOOR HARDWARE | REAR EGRESS- DOOR HARD TO UNLOCK AND OPEN. D&H | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | PLANS AND PERMITS REQUIRED. THIS SPACE WAS ORIGINALLY A RESTAURANT. PROVIDE PLANS AND PERMITS FOR CHANGE OF USE AND ANY ALTERATIONS MADE TO A NOW AUTO SUPPLY STORE | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
PROVIDE OPEN FRONT TOILET SEAT | UNAPPROVED CLOSED FRONT TOILET SEAT AT 1ST FLOOR BATHROOM. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
STOP ODORS RPR DFT SEWAGE SYS | OPEN SEWERS AT ABANDONED GREASE TRAP IN BASEMENT AND MISSING REMOVED LAVATORY IN BASEMENT. DANGEROUS AND HAZARDOUS. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE WATER PIPING | BROKEN SECTION OF SUSPENDED CAST IRON PIPING AT BASEMENT HAS BEEN REPAIRED USING DUCT TAPE. DANGEROUS AND HAZARDOUS. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | UNAPPROVED PVC DRAINAGE PIPING OBSERVED THROUGHOUT BASEMENT. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |
SUBMIT PLANS FOR PLUMBING PRMT | SPECIFICALLY ENTIRE PLUMBING SYSTEM HAS BEEN MODIFIED FROM ORIGINAL STATE WITHOUT PLANS PERMITS OR INSPECTIONS. | 4948 W NORTH AVE | COMPLAINT | FAILED | View |