Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR EXTERIOR STAIR | PROVIDE A HANDRAIL FOR THE STAIRS LEADING FROM THE FIRST FLOOR TO THE BASEMENT ON THE SOUTH EXTERIOR ELEVATION | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
STRUCTURAL MEMBER, PIER BLOCK | THE STEEL BEAM AND SCREW JACK COLUMN, WHICH ARE INSTALLED AT THE BOTTOM OF THE STAIRS TO THE BASEMENT, PENETRATE THROUGH THE STAIRS | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REMV OBSTR FROM DRAINAGE SYSTM | THE BAR SINK TRAP IS AN OPEN SITE; IT NEEDS TO BE RODDED BECAUSE IT IS OVERFLOWING | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
NO KEY TO USE EXIT DOOR | THE FRONT ENTRANCE DOOR IS EQUIPPED WITH A BUZZER SYSTEM THAT ONLY ALLOWS AN INDIVIDUAL TO EXIT IF BUZZED OUT | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | WEST ELEVATION/ ABOVE 2ND FLOOR WINDOW- SPALLING BRICKS AND WASHED OUT MORTAR | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
PROVIDE ROUGH INSPECTION FOR THE INSTALLATION OF ELECTRICAL CONDUIT BOXES, WIRING DEVICES, AND ELECTRICAL EQUIPMENT INSTALLED THROUGHOUT THE BASEMENT, FIRST FLOOR AND SECOND FLOOR AREAS, PURSUANT TO SECTION 13-12-380 OF THE CODE | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View | |
REPAIR/REBUILD GARAGE OR SHED | BRICK WALL WASHED OUT MORTAR AND SHIFTING BRICKS, OVERHEAD DOOR DENTED | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | THE HANDRAIL SYSTEM LEADING FROM THE FIRST FLOOR TO THE BASEMENT ON THE INTERIOR OF THE FIRST FLOOR IS MISSING, ON THE WRONG SIDE, AND THE WRONG HEIGHT | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
PROPER MATRL WATER SUPPLY PIPE | THE TOILETS AND LAVATORIES - REMOVE THE FLEX WATER SUPPLIES AND INSTALL COPPER TUBE SUPPLIES | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING/NO RESPONSE - UNVERIFIED DETECTORS AND OCCUPANCY UNABLE TO INSPECT REAR PORCH | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | PROVIDE A STRUCTURAL REPORT, DRAWINGS, AND THE REQUIRED PERMIT | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE WASTE PIPING | THE SECOND FLOOR TUB-WASTE RUNS IN PVC, REMOVE AND RE-PIPE WITH APPROVED MATERIALS | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | PROVIDE GFCI PROTECTION FOR ALL OF THE BAR COUNTER AREAS OF THE FIRST FLOOR UNIT PURSUANT TO SECTION 18-27-210.8 OF THE CODE | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
POST OWNER/MANAGERS NAME/# | POST OWNERSHIP/ OWNER'S MAILING ADDRESS IS MISSING | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR PORCH SYSTEM | FRACTURED THREADS OBSERVED, NO POST BASE BRACKET, NO FITTING OBSERVED, NO ANGLE BRACKETS, NO HANGERS, THE SPLICES ARE NOT BOLTED AND THE RAILS AND GUARD RAILS ARE THE WRONG HEIGHT | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | PROVIDE ENTRANCE TO THE SECOND FLOOR AND BASEMENT FOR A FULL INSPECTION | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | WEST ELEVATION/ABOVE 2ND FLOOR WINDOW - SPALLING BRICKS AND WASHED OUT MORTAR | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
PROVIDE OPEN FRONT TOILET SEAT | THE FIRST FLOOR MEN'S AND WOMAN'S BATHROOMS - REMOVE THE ROUND FRONT TOILETS AND INSTALL ELONGATED TOILETS WITH OPEN FRONT TOILET SEATS | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR STOOP | NORTH ELEVATION/ CONCRETE CRACKED WITH PEELING PAINT | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
PARAPET | NORTH ELEVATION PARAPET WASHED OUT MORTAR | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | PROVIDE THE PROPER TYPE OF COVERS FOR THE OPEN BOX WITH EXPOSED WIRING THROUGHOUT THE CEILING AREAS, A DANGEROUS AND HAZARDOUS CONDITION | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
OBTN PERMIT FOR PLUMBING WORK | PULL A PLUMBING PERMIT | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR DOOR HARDWARE | THE HINGES ON THE REAR NORTH ELEVATION OF THE BAR ARE LOOSE AND DO NOT HAVE A SELF-CLOSING DEVICE | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR STOOP | NORTH ELEVATION/CONCRETE-CRACKED WITH PEELING PAINT | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | THERE ARE NO CARBON MONOXIDE DETECTORS OBSERVED ON THE FIRST FLOOR, A DANGEROUS AND HAZARDOUS CONDITION | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE WASTE PIPING | THE KITCHEN SINK IN THE BAR - REMOVE THE PVC TRAP AND EXTENSION TUBING AND RE-PIPE WITH BRASS | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
MIXED OCCUPANCY SEPARATION | THE OPEN FLOOR JOIST SYSTEM OBSERVED ON THE FIRST FLOOR ABOVE THE DROPPED CEILING SYSTEM NEEDS ALL OF THE CEILING TILES TAKEN OUT, A DANGEROUS AND HAZARDOUS CONDITION | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | REMOVE THE PADLOCK FROM THE BASEMENT DOOR ON THE SOUTH ELEVATION AND ALSO THE LOCK ON THE SOUTHEAST GATE | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR WINDOW SILLS | NORTH ELEVATION/ WINDOW SILLS- WASHED OUT MORTAR | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
NO PERMIT WIRING | OBTAIN ELECTRICAL PERMIT AND A CONTRACTOR TO CORRECT VIOLATIONS AND FOR THE INSTALLATION OF ELECTRICAL CONDUIT BOXES, WIRING DEVICES, AND ELECTRICAL EQUIPMENT INSTALLED THROUGHOUT THE BASEMENT, FIRST FLOOR AND SECOND FLOOR AREAS | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING/ NO RESPONSE- UNVERIFIED DETECTORS AND OCCUPANCY UNABLE TO INSPECT REAR PORCH | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
ADD RECEPTACLES | ADD RECEPTACLES TO THE EASE EXTENSION CORD USE THROUGHOUT THE FIRST FLOOR CEILING AREAS, A DANGEROUS AND HAZARDOUS CONDITION | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
ENGAG LIC & BOND PLMBNG CNTRC | HIRE A LICENSED PLUMBING CONTRACTOR | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
CEILING WIRES AND CEILING GRIDS SHALL NOT BE USED FOR SUPPORT - PROPERLY SUPPORT ALL TRACK LIGHTS AND CEILING FANS THROUGHOUT THE FIRST FLOOR BAR AREAS PURSUANT TO SECTION 18-27-300.11 OF THE CODE | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View | |
REPAIR/REBUILD GARAGE OR SHED | GARAGE/ BRICK WALL WASHED OUT MORTAR AND SHIFTING BRICKS. OVERHEAD DOOR DENTED | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR WINDOW SILLS | NORTH ELEVATION/WINDOW SILLS - WASHED OUT MORTAR | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
INSTALL SMOKE DETECTORS | THERE ARE NO SMOKE DETECTORS OBSERVED ON THE FIRST FLOOR, DANGEROUS AND HAZARDOUS CONDITION | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | REPAIR OR REPLACE ALL THE DAMAGED CEILING TILES ON THE FIRST FLOOR | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
PROPER MATRL WATER SUPPLY PIPE | THE KITCHEN SINK - REMOVE THE FLEX WATER SUPPLIES AND REPLACE WITH COPPER TUBE SUPPLIES | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | THERE IS MISSING MORTAR AND SPALLING BRICK ON THE SOUTH ELEVATION | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
POST OWNER/MANAGERS NAME/# | POST OWNERSHIP/OWNER'S MAILING ADDRESS MISSING | 856 N FAIRFIELD AVE | COMPLAINT | FAILED | View |
SUBMIT PLANS FOR PLUMBING PRMT | 856 N FAIRFIELD AVE | PERMIT | FAILED | View |