The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): PROVIDE CAT1 & CAT5 TEST SHEET AND TAGS | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): LABLE DISCONNECT FEED LOCATION FOR TRANSFORMER, 110V, AND MAINLINE | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 4 & 5: LABEL ELEVATOR EQUIPMENT IN MACHINEROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): ETCH/FILL-IN CODE DATA TAG TO REFLECT TIME OF ALTERATION | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): PROPERLY GROUND EQUIPMENT TO PREVENT TRIPPING HAZZARD THAT RUNS FROM ONE MACHINE ROOM, ACROSS THE ROOF AND TO THE OTHER MACHINE ROOM. | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: PROVIDE ADEQUATE LIGHTING IN MACHINEROOM AND SECONDARY THAT IS CONTROLLED FROM A LIGHT SWITCH UPON ENTRANCE TO MACHINE ROOM OR SECONDARY | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): PROVIDE MAINTENANCE CONTROL PROGRAM RECORDS (MUST REMAIN ONSITE) | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: PROVIDE KICKPLATES AROUND OPENINGS IN MACHINEROOM FLOOR AND SECONDARY | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 4&5: PROVIDE COVER FOR CIRCUIT BREAKER BOX IN MACHINEROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: PROVIDE GFCIS IN MACHINEROOM AND PIT. IT MUST BE SEPARATE FROM SUMP PUMP FEED | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 1-5: PROVIDE MONTHLY FIRE TEST LOG | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS 1-5: PROVIDE MACHINEROOM DOOR SIGNAGE AND ANY DOORS LEADING TO MACHINEROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS 1-5: ROOFTOP MACHINEROOM DOOR MUST REMAIN LOCKED AND ACCESS TO MACHINEROOM MUST BE READILY AVAILABLE | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: PROVIDE ADEQUATE PIT AND CARTOP LIGHTING | 1755 E 55TH ST | PERIODIC | FAILED | View |
REMOVE DEBRIS FROM PIT | ELEVATORS 3-5: CLEAN CARTOPS AND PITS | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 4&5:- RESTRICTOR HAS BEEN DISABLED | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVARORS 4&5: PLACE CARTOP EQUIPMENT COVERS ON EXPOSED ELECTRICAL DEVICES | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 5: PROVIDE DOOR UNLOCKING DEVICE TO BE AVAILABLE TO AUTHORIZED PERSONNEL | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 4: PHASE II FIRE SERVICE UPDATE REQUIRED | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CORRECT ALL VIOLATIONS AND RESCHEDULE INSPECTION | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 1-3: PROVIDE SAFE MEANS TO ACCESS AND EGRESS MACHINE ROOM ON WEST SIDE OF BUILDING'S ROOFTOP | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 4&5: REPAIR WINDOW IN MACHINE ROOM TO PREVENT OUTSIDE ELEMENTS FROM ENTERING | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 1&2: PROVIDE PERMANENT MEANS TO ACCESS MACHINE ROOM VIA UNANCHORED STEPS | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: REMOVE NON ELEVATOR PARTS AND EQUIPMENT FROM MACHINE ROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: CUT ANCHORS IN MACHINE ROOM FLOOR TO PREVENT TRIP HAZARD | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: PROVIDE BARRICADE AROUND BACK WALL THAT POSES A FALL HAZARD | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): PROVIDE CAT1 TEST SHEET AND TAGS | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: TOP FLOOR HEIGHT POSES A TRIPPING HAZARD | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 4&5: REPAIR WINDOW IN MACHINE ROOM TO PREVENT OUTSIDE ELEMENTS FROM ENTERING | 1755 E 55TH ST | PERIODIC | FAILED | View |
TEST G & S ALL ELE | EV008125 | 1755 E 55TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: CLEAN MACHINEROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: FLOOR LEVELING IS NOT CORRECT. TOP FLOOR HEIGHT POSES A TRIPPING HAZARD | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: PROVIDE BARRICADE AROUND BACK WALL THAT POSES A FALL HAZARD IN MACHINE ROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 5 GOVERNOR SAFTY TEST AS PER CITY CODE ON CAR F3 FREIGHT. EV008125 | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE ACCES PANEL AT PIT FOR CAR #3 | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PATCH ALL HOISTWAY HOLES AND ADD MESH IN PIT | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE DRAIN COVER | 1755 E 55TH ST | PERMIT | FAILED | View |
PROVIDE | SMOKE DETECTOR AND COMMUNICATION SYSTEM INSTALLATION IS IN PROGRESS AT TIME OF INSPECTION. COMPLETE INSTALLATION OF ONE-WAY AND TWO-WAY COMMUNICATION SYSTEM THROUGHOUT THE BUILDING IS REQUIRED (SEC. 13-196-204). COMPLETE INSTALLATION OF WIRED SMOKE DETECTOR THROUGHOUT THE BUILDING IS REQUIRED (SEC. 13-196-210). | 1755 E 55TH ST | PERIODIC | PASSED | View |
SELF-CLOSE DOOR >4 STORY RES. | DOORS NOT PROPERLY CLOSING AND LATCHING: G1 (SERVICE), F4, F2, F1, E3-4 (SERVICE), D3-4 (SERVICE), C5-6 (SERVICE), C3, B2, B2 (SERVICE), A7, 1203, 1201 (SERVICE), 1101 (SERVICE), 1104 (SERVICE), 1003 (SERVICE), 1001(SERVICE), 904, 903 (SERVICE), 902, 802, 801(SERVICE), 704, 703 (NO CLOSER), 603 (SERVICE) LATCH BROKEN), 503 (SERVICE) UNABLE TO OPEN, 501, 405-6 (SERVICE) NO LATCH, 403-4 (SERVICE) NO LATCH AND CLOSER, 401, 402 (FRONT AND SERVICE) NO LATCH, 305, 304 (NO LATCH STRIP), 207 (SERVICE), 206 (SERVICE), 203 (SERVICE), 202 (SERVICE), 201 (SERVICE, ) DOORS), 102 (SERVICE) DOOR UNABLE TO OPEN. SEAL ALL MAILBOXES OPENINGS IN ALL UNIT DOORS WITH 1-HOUR FIRE RATED MATERIALS. | 1755 E 55TH ST | PERIODIC | PASSED | View |
OBSTRUCTIONS IN EXIT WAY | EGRESS OBSTRUCTIONS: L2, K2, K1, J1, C4, C3, 301 - FIRE ESCAPE DOORS BLOCKED WITH SHELVES, KITCHEN CABINET, MICROWAVE, LAUNDRY AND CLEANING MATERIALS.K1, J1, E1-2, 601-6, 501-6, 504-5, 305-6, 301-7, 201-7 (SHARED LOBBY) - SERVICE DOORS BLOCKED WITH STORAGE.C1-2 SERVICE DOOR LOCKED OUT, TENANTS UNABLE TO EXIT.WEST AND EAST SERVICE STAIRWELLS - TRASH CANS OBSTRUCTING EGRESS THROUGHOUT.904, 902, 704 - SERVICE DOOR BLOCKED WITH STORAGE, 407 SERVICE DOOR BLOCKED WITH KITCHEN SINK. 604 SERVICE DOOR PARTLY CLOSED OUT WITH DRYWALL. | 1755 E 55TH ST | PERIODIC | PASSED | View |
CLASS B DOOR IN STAIRWELL | STAIRWAY DOORS, INCLUDING E11AND E12 - PAINTED AND MISSING LABELS. | 1755 E 55TH ST | PERIODIC | PASSED | View |
SELF-CLOSE CLASS B FIRE DOOR | EAST AND WEST TOWERS: UNUSED TRASH CHUTES NOT PROPERLY SEALED WITH FIRE CAULK. 101 LOBBY DOOR TO COURTYARD (NO CLOSER). EAST PUMP ROOM DOOR TO LAUNDRY ROOM - DAMAGED AND MISSING LABEL. EAST BIKE ROOM LOBBY DOOR (NEAR SERVICE ELEVATOR) MISSING CLOSER AND LABEL. BIKE ROOM AND BIKE LOBBY ROOM DOORS AND FRAMES MISSING. EAST MAINTENACE ROOM AND WORKSHOP DOORS - MISSING CLOSER AND LABEL. FITTNESS AND HOSPITALITY ROOMS - MISSING LABEL. 12S, 1203 AND 803 (SERVICE DOORS INTO STAIRWAY) - MISSING LABELS. 3RD FLOOR (NEAR FIRE ESCAPE DOOR) ACCESS DOOR PANEL MISSING. LABEL. ELEVATOR MACHINE ROOM - HOLLOW WOOD DOOR. | 1755 E 55TH ST | PERIODIC | PASSED | View |
PIPE OPENING W/NONCOMBUST MATL | ELEVATOR MACHINE ROOMS, PUMP ROOMS, ALL ELECTRIC CLOSETS AND SINK CLOSETS THROUGHOUT - HOLES AND PIPE PENETRATIONS ON WALLS, CEILINGS AND FLOORS. SEAL MAILBOXES INTHE CORRIDOR WALLS ON ALL FLOORS WITH 1-HOUR FIRE RATED MATERIALS. SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS. | 1755 E 55TH ST | PERIODIC | PASSED | View |
ARRANGE PREMISE INSPECTION | NO ACCESS TO DOORS - 303, 304, 505 AND 1103 - UNABLE TO VERIFY FIRE RATING, CLOSING AND LATCHING CONDITIONS AT TIME OF INSPECTION. | 1755 E 55TH ST | PERIODIC | PASSED | View |
PROVIDE | ENTIRE BUILDING, INCLUDING PENTHOUSE ELEVATOR MACHINE ROOMS, MAINTENCE WORKSHOPS, AND BIKE / STORAGE ROOM - EMERGENCY LIGHTS MISSING. INSTALLATION IS IN PROCESS AT TIME OF INSPECTION (SEC. 13-160-690). | 1755 E 55TH ST | PERIODIC | PASSED | View |
INSTALL SMOKE DETECTORS | ELEVATOR MACHINE ROOMS, BIKE ROOMS, MAINTENACE WORKSHOP ROOMS, LAUNDRY ROOM AND PUMP ROOMS - SMOKE DETECTORS - MISSING. | 1755 E 55TH ST | PERIODIC | PASSED | View |
NO CLOSET/STORAGE UNDER STAIR | STORAGE CLOSET BUILT WITHIN STAIRWELL AT 9S, 11S AND 2ND FLOOR EAST STAIRWAY. | 1755 E 55TH ST | PERIODIC | PASSED | View |
CARB MONOX DETECT IN RESID | LAUNDRY ROOM - CARBON MONOXIDE DETECTOR - MISSING. | 1755 E 55TH ST | PERIODIC | PASSED | View |
COVER OUTLETS AND JBS | WEST PUMP ROOM - OPEN ELECTRIC BOX. | 1755 E 55TH ST | PERIODIC | PASSED | View |
EXPOSED WIRING | WEST PUMP ROOM - OPEN ELECTRIC BOX - EXPOSED WIRES. | 1755 E 55TH ST | PERIODIC | PASSED | View |
2HR SEP FOR STORAGE >100SF | BASEMENT AT VARIOUS LOCATIONS, INCLUDING BOILER ROOM, PUMP ROOM, ELECTRIC ROOM, GARBAGE DUMP AREA - RESIDENT STORAGE SPACES BUILT WITH COMBUSTIBLE WOOD MATERIALS WITHOUT PROPER ENCLOSURES - 2 HOUR SEPARATIONS REQUIRED. | 1755 E 55TH ST | PERIODIC | PASSED | View |
REMOVE | RESIDENTS SHARED SERVICE LOBBY USED AS STORAGE SPACES: DI-2, D5-6, 201 & 207, 305 & 306, 301 & 307, 504 & 505, 601 & 606 AND 902 & 904 - REMOVE OBSTRUCTIONS AND COMBUSTIBLE MATERIALS ON SAFETY CLEARANCE SPACES (SEC.15-4-890). | 1755 E 55TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR OR REPLACE EMERGENCY ALARM BELL ON PASSENGER ELEVATORS 1P, 2P | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL HANDS FREE EMERGENCY PHONE IN ELEVATORS 3F, 4P, 5F. | 1755 E 55TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE UPDATED CROSSHEAD DATA INFO(ENGRAVED) | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE COUNTERWEIGHT RUNBY SIGNAGE AND LABEL COUNTERWEIGHT HAZARD IN PIT | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST FAID'S | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | APPLY FOR VARIANCE FOR TOE GUARD ON CAR #3 | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATAGORY 1 SAFETY TEST ON ELEVATORS 1P, 2P, 3F, 4P, 5F. | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM COMPLETE INSPECTION ON CAR #2 | 1755 E 55TH ST | PERMIT | FAILED | View |
SEND EX. METAL LETTER | 1755 E 55TH ST | COMPLAINT | PASSED | View | |
REPAIR EXTERIOR DOOR HARDWARE | MOST FIRE ESCAPE DOORS THROUGH THE UNITS, INCLUDING: L2, H2, G2, F3, D4, B4, 1202, 1102, 1002, 701, 602, 601, 501, 401, 301, 202 AND 201 NOT PROPERLY CLOSING, LATCHING AND MISSING CLOSERS: | 1755 E 55TH ST | PERIODIC | PASSED | View |
REMOVE | TENANT STORAGE ROOMS BUILT INSIDE PUMP AND ELECTRICAL ROOMS. REMOVE COMBUSTIBLE STRUCTURES OR MATERIALS FROM FIRE IGINITION SOURCES (SEC.15-4-970). | 1755 E 55TH ST | PERIODIC | PASSED | View |
INSTALL EXIT SIGN | BIKE / STORAGE ROOM AND LAUNDRY ROOM - EXIT SIGN - MISSING. | 1755 E 55TH ST | PERIODIC | PASSED | View |
STOP/REMOVE NUISANCE | WEST TOWER: 2ND FLOOR SERVICE STAIRWAY - ENTANGLED COMCAST CABLES. | 1755 E 55TH ST | PERIODIC | PASSED | View |
PROVIDE | FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN. (13-196-206D) | 1755 E 55TH ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): LABLE DISCONNECT FEED LOCATION FOR TRANSFORMER, 110V, AND MAINLINE | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 4 & 5: LABEL ELEVATOR EQUIPMENT IN MACHINEROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): ETCH/FILL-IN CODE DATA TAG TO REFLECT TIME OF ALTERATION | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): PROPERLY GROUND EQUIPMENT TO PREVENT TRIPPING HAZZARD THAT RUNS FROM ONE MACHINE ROOM, ACROSS THE ROOF AND TO THE OTHER MACHINE ROOM. | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: CLEAN MACHINEROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: PROVIDE ADEQUATE LIGHTING IN MACHINEROOM AND SECONDARY THAT IS CONTROLLED FROM A LIGHT SWITCH UPON ENTRANCE TO MACHINE ROOM OR SECONDARY | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): PROVIDE MAINTENANCE CONTROL PROGRAM RECORDS (MUST REMAIN ONSITE) | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: PROVIDE KICKPLATES AROUND OPENINGS IN MACHINEROOM FLOOR AND SECONDARY | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 4&5: PROVIDE COVER FOR CIRCUIT BREAKER BOX IN MACHINEROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: PROVIDE GFCIS IN MACHINEROOM AND PIT. IT MUST BE SEPARATE FROM SUMP PUMP FEED | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 1-5: PROVIDE MONTHLY FIRE TEST LOG | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS 1-5: PROVIDE MACHINEROOM DOOR SIGNAGE AND ANY DOORS LEADING TO MACHINEROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS 1-5: ROOFTOP MACHINEROOM DOOR MUST REMAIN LOCKED AND ACCESS TO MACHINEROOM MUST BE READILY AVAILABLE | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: PROVIDE ADEQUATE PIT AND CARTOP LIGHTING | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3-5: CLEAN CARTOPS AND PITS | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 4&5:- RESTRICTOR HAS BEEN DISABLED | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVARORS 4&5: PLACE CARTOP EQUIPMENT COVERS ON EXPOSED ELECTRICAL DEVICES | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 5: PROVIDE DOOR UNLOCKING DEVICE TO BE AVAILABLE TO AUTHORIZED PERSONNEL | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 4: PHASE II FIRE SERVICE UPDATE REQUIRED | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CORRECT ALL VIOLATIONS AND RESCHEDULE INSPECTION | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 1&2: PROVIDE PERMANENT MEANS TO ACCESS MACHINE ROOM VIA UNANCHORED STEPS | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: REMOVE NON ELEVATOR PARTS AND EQUIPMENT FROM MACHINE ROOM | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: PROVIDE BARRICADE AROUND BACK WALL THAT POSES A FALL HAZARD | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: CUT ANCHORS IN MACHINE ROOM FLOOR TO PREVENT TRIP HAZARD | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 1-3: PROVIDE SAFE MEANS TO ACCESS AND EGRESS MACHINE ROOM ON WEST SIDE OF BUILDING'S ROOFTOP | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 3: TOP FLOOR HEIGHT POSES A TRIPPING HAZARD | 1755 E 55TH ST | PERIODIC | FAILED | View |
FINAL OPEN PERMIT | CLOSE OPEN PERMIT (100264806) FOR MODERNIZATION OF ELEVATORS #1 AND #2 | 1755 E 55TH ST | PERIODIC | FAILED | View |
OBTAIN PERMIT FOR DEVICE | ALL ELEVATORS: OBTAIN PERMIT TO TIE IN SMOKE DETECTORS FOR AUTO RECALL PER CITY OF CHICAGO CODE | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS (1-5): PROVIDE CAT1 & CAT5 TEST SHEET AND TAGS | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 1 TEST ON ALL ELEVATORS | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 5 TEST ON ELEVATORS 1P- 2P | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CLEAN MACHINE ROOMS | 1755 E 55TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ADEQUATE CLIMATE CONTROL IN BOTH MACHINE ROOMS | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CAR TOP RAILING AND LABEL COUNTERWEIGHT HAZARD | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ANTI-ROTATION DEVICE FOR CABLE SHACKLES | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE VISION PANEL FOR CAR #4 PIT ACCESS DOOR | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE COUNTERWEIGHT RUNBY SIGNAGE AND LABEL COUNTERWEIGHT HAZARD IN PIT FOR ALL CARS | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE UPDATED CROSSHEAD DATA INFO(ENGRAVED)ALL CARS | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CODE COMPLIANT PIT LADDER FOR ALL CARS AS NEEDED | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE DOOR STOPPERS FROM BASEMENT AND 11TH FLOOR HOISTWAY DOORS | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERMANENTLY WIRE IN SOURCE VOLTAGE ON CAR #5 | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST FAID'S ALL CARS | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE PUSH/PULL PIT STOP SWITCHES ON ALL CARS | 1755 E 55TH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE BRAILLE TAGS AT ALL LANDINGS FOR ALL ELEVATORS | 1755 E 55TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE FIRE SERVICE KEY BOX IN LOBBY OF P3 ELEVATOR | 1755 E 55TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE PICTOGRAPHS AT ALL LANDINGS | 1755 E 55TH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | APPLY FOR VARIANCE FOR TOE GUARD ON CAR #3 AND CAR #5 | 1755 E 55TH ST | PERMIT | PASSED | View |