Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
PARAPET | WEST ELEVATION-PARAPET WALL LEANING IN OUT, REAR AT ALCOVE DETERIORATING BRICKS AT PARAPET | 957 N HAMLIN AVE | COMPLAINT | FAILED | View |
RMV PLBFIX INSTALLD W/0 PERMIT | PLUMBER ON PERMIT DID NOT DO ANY WORK. (13-168-030 THRU 060) (11-8-070) (18-29-106-2)(13-29-106-1) 1(4-332-010-100) | 957 N HAMLIN AVE | COMPLAINT | PASSED | View |
ARRANGE PREMISE INSPECTION | CALL FOR INSPECTION TO WITNESS PLUMBING REMOVED (13-12-11) (18-29-601 2&3) INTERIOR | 957 N HAMLIN AVE | COMPLAINT | PASSED | View |
PROPER MATERIAL FOR HSE DRAIN | REMOVE PVC BELOW GRADE INCLUDING DOWN SPOUT METERIAL (18-29-702) (13-168-480) (13-168-490) | 957 N HAMLIN AVE | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | ELIMINATE MINI BREAKERS IN GARDEN UNIT PANEL 18-240.85 | 957 N HAMLIN AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | INSTALL COLD WATER GROUNDING ELECTRODE CONDUCTOR IN SEPARATE RACEWAY 18-27-250.64 | 957 N HAMLIN AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | ELIMINATE DOUBLE TERMINATIONS AT SERVICE GROUND 18-27-110.14(A) | 957 N HAMLIN AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | NEED PANEL SCHEDULES FOR ALL PANELS 18-27-110.22 | 957 N HAMLIN AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | FIX BONDING OF FEEDERS AT SERVICE WITH BROKEN CONCENTRIC KNOCKOUTS 18-27-300.12 | 957 N HAMLIN AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | FIX BROKEN FITTING AT REAR EXTERIOR LIGHTING JUNCTION BAX AND SUPPORT RACEWAY 18-27-300.121 AND 18-27-300.13 | 957 N HAMLIN AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | ALL CONDUCTORS OF A MULTIWIRE CIRCUIT TO BE IN SAME RACEWAY *UNIT 2S HAS (4) NEUTRALS AND (2) HOTS IN PIPE, UNIT 1N HAS (3) HOTS AND NO NEUTRALS IN PIPE 18-27-300.20 AND 18-27-110.12 | 957 N HAMLIN AVE | PERMIT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 957 N HAMLIN AVE | PERMIT | PASSED | View | |
ARRANGE COMPLETED PERMIT INSP. | 957 N HAMLIN AVE | PERMIT | PASSED | View | |
SEE INSPECTOR COMMENTS | EMERGENCY BATTERY UNITS TO BE METAL 18-27-7000.66(C)(3) | 957 N HAMLIN AVE | PERMIT | PASSED | View |