Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SEE INSPECTOR COMMENTS | 7240 W DEVON AVE | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR MALFUNCTIONING DOOR RESTRICTOR.(PREVIOUSLY CITED) | 7240 W DEVON AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ACCESS TO ELEVATOR MACHINE ROOM REQUIRED TO COMPLETE THIS INSPECTION.(PREVIOUSLY CITED) | 7240 W DEVON AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TEST. TAG AND DOCUMENT AS REQUIRED.(PREVIOUSLY CITED) | 7240 W DEVON AVE | PERIODIC | PASSED | View |
ARRANGE FOR INSPECTION | INSPECTION | 7240 W DEVON AVE | PERMIT | PASSED | View |
ACCESS TO ROOF | INSPECTION | 7240 W DEVON AVE | PERMIT | PASSED | View |
INSTALL VENT/AS SHOWN ON PLANS | 7240 W DEVON AVE | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR ELEVATOR AS NECESSARY TO COMPLETE ACCEPTANCE TEST: 1) REPLACE CONTAMINATED OIL 2)REPLACE DEFECTIVE VALVE RE-SCHEDULE ACCEPTANCE INSPECTION WITH THE CITY OF CHICAGO ELEVATOR BUREAU | 7240 W DEVON AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | FINISH CAB FLOOR | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL FIREMAN'S KEY BOX | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL FAID SYSTEM FOR FIRE RECALL 2001 CODE | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE GROUND ON LINE SIDES FEEDS OF DISCONNECTS. | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE METAL SUMP HOLE COVER | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE GFEI OUTLET, LIGHT SWITCH IN PIT | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE PIT LADDER | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE IN CASE OF FIRE PICTOGRAPHS AT ALL HALL STATIONS | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE METAL CODA DATA PLATE ON CONTROLLER | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE GFCI OUTLET IN MACHINE ROOM | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROPERLY PIPE PHONE LINE IN MACHINE DOOR | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE EMERGENCY PHONE IN ELEVATOR | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE TOP OF CAR RAILING | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | HOISTWAY MUST MAINTAIN 2HR FIRE RATING | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SCHEDULE REINSPECTION WITH FIRE SERVICE RECALL TEST UPON COMPLETION OF ABOVE VIOLATION. | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | DO NOT USE ELEVATOR UNTIL REINSPECTION | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PRESSURE, FULL LOAD AND RELIEF TEST. | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PATCH HOLES AND PIPE CHASES IN HOISTWAY | 7240 W DEVON AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING TWO WAY COMMUNICATION (PHONE) REQUIRED IN ELEVATOR CAB. | 7240 W DEVON AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TEST. TAG AND DOCUMENT AS REQUIRED. | 7240 W DEVON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR MALFUNCTIONING DOOR RESTRICTOR. | 7240 W DEVON AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TEST. TAG AND DOCUMENT AS REQUIRED. | 7240 W DEVON AVE | PERIODIC | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 7240 W DEVON AVE | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | ACCESS TO ELEVATOR MACHINE ROOM REQUIRED TO COMPLETE THIS INSPECTION. | 7240 W DEVON AVE | PERIODIC | FAILED | View |