The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ARRANGE COMPLETED PERMIT INSP. | 1000 W NORTH AVE | COMPLAINT | CLOSED | View | |
MAINTAIN MECH. VENT SYSTEM | 1000 W NORTH AVE | COMPLAINT | CLOSED | View | |
14 GAUGE HOOD/STACK ABOVE ROOF | 1000 W NORTH AVE | COMPLAINT | CLOSED | View | |
FIREMAN'S DUMP SIGN | FOR REFRIGERATION RACKS A & B VALVES ARE LOCATED IN REAR EMERGENCY EXIT HALLWAY AND DOCK EXIT HALLWAY. | 1000 W NORTH AVE | PERIODIC | FAILED | View |
VENT LINE TERMINATION | OFF DISCHARGE FROM FIREMAN'S DUMP VALVE'S LOCATED ON. | 1000 W NORTH AVE | PERIODIC | FAILED | View |
REPAIR OR REPLACE | PROTECTIVE ENCLOSURE FOR FIREMANS DUMP VALVE OF REFRIGERATION RACK "B" LOCATED IN DOCK EXIT HALLWAY. (13-20-790,13-192-760) | 1000 W NORTH AVE | PERIODIC | FAILED | View |
REPAIR OR REPLACE | PROTECTIVE ENCLOSURE FOR FIREMANS DUMP VALVE OF REFRIGERATION RACK "B" LOCATED IN DOCK EXIT HALLWAY. (13-20-790,13-192-760) | 1000 W NORTH AVE | PERIODIC | PASSED | View |
FIREMAN'S DUMP SIGN | FOR REFRIGERATION RACKS A & B VALVES ARE LOCATED IN REAR EMERGENCY EXIT HALLWAY AND DOCK EXIT HALLWAY. | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROPERLY REPAIR PASSENGER ELEVATOR AND RETURN TO SERVICE | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFROM A CATEGORY 1 TEST ON PASSENGER ELEVATOR | 1000 W NORTH AVE | PERIODIC | PASSED | View |
OBTAIN REFRIGERATION PERMIT | RE: FOR ONE 15 TON CARRIER ROOF TOP UNIT. | 1000 W NORTH AVE | PERIODIC | PASSED | View |
ARRANGE FOR RE-INSPECTION | CONTACT INSPECTOR STEPHEN MCGANN #971 @ (312)743-3562 ON TUESDAYS BETWEEN 8-9AM. | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINT VERT RECIP CONVEYOR | PROPERLY ENCLOSE TOP OF HOISTWAY | 1000 W NORTH AVE | PERIODIC | FAILED | View |
MAINT VERT RECIP CONVEYOR | REPAIR DAMAGED HOISTWAY ENCLOSURE | 1000 W NORTH AVE | PERIODIC | FAILED | View |
MAINT VERT RECIP CONVEYOR | INSTALL ALL HOISTWAY COVERS | 1000 W NORTH AVE | PERIODIC | FAILED | View |
MAINT VERT RECIP CONVEYOR | ADJUST STOPPING - BOTH DIRECTIONS | 1000 W NORTH AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 5 TESTING.BOTH CARS | 1000 W NORTH AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CODE DATA PLATE ON CONTROLLER. | 1000 W NORTH AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SCHEDULE FINAL INSPECTION FOR PERMIT #100314296. | 1000 W NORTH AVE | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TESTS. | 1000 W NORTH AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE MONTHLY FIRE SERVICE TEST LOG ON SITE. | 1000 W NORTH AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SCHEDULE FINAL INSPECTION TO INCLUDE FIRE SERVICE FOR PERMIT #100009539. | 1000 W NORTH AVE | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE FIRE SIGNS ON ALL LANDINGS | 1000 W NORTH AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL EMERGENCY PHONE 24 HRS SERVICE INSIDE ELEVATOR | 1000 W NORTH AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR DOOR RESTRICTOR | 1000 W NORTH AVE | PERIODIC | FAILED | View |
MAINT VERT RECIP CONVEYOR | INSTALL ALL HOISTWAY COVERS (PREVIOUSLY CITED) | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINT VERT RECIP CONVEYOR | ADJUST STOPPING - BOTH DIRECTIONS (PREVIOUSLY CITED) | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE MONTHLY FIREMAN'S RECALL TEST AND MAINTAIN LOG ON SITE | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CATEGORY 1 TESTING AND MAINTAIN LOG ON SITE | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CARTIFICATE FRAME INSIDE PASSENGER ELEVATOR | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINT VERT RECIP CONVEYOR | PROVIDE CERTIFICATE FRAME | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINT VERT RECIP CONVEYOR | REPAIR DAMAGED HOISTWAY GAGE | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINT VERT RECIP CONVEYOR | REPAIR WIRES AND GREENFIELD ON GATE CONTACTS | 1000 W NORTH AVE | PERIODIC | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 1000 W NORTH AVE | PERMIT | PASSED | View | |
MAINTAIN EXIT SIGN ILLUMINATED | REPAIR EXIT SIGNS NOT ILLUMINATED. | 1000 W NORTH AVE | COMPLAINT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 18-28-106.1 INSPECTION REQUIRED ARRANGE FOR COMPLETE PERMIT INSPECTIONS AND OBTAIN PERMIT FOR VENT SYSTEMS WHEN WORK IS COMPLETE! | 1000 W NORTH AVE | PERIODIC | FAILED | View |
MAINTAIN MECH. VENT SYSTEM | APPLICABILITY MAINTAIN MECHANICAL VENTILATION EQUIPMENT IN GOOD REPAIR & OPERATE TO PROVIDE ADEQUATE VENT DURING WORKING HOURS | 1000 W NORTH AVE | PERIODIC | FAILED | View |
REPAIR OR REPLACE | REPAIR OR REPLCE EXHAUST SYSTEM | 1000 W NORTH AVE | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | REMOVE STORAGE AND SHELVING OBSTRUCTING REAR EXIT CORRIDOR. | 1000 W NORTH AVE | COMPLAINT | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | REPAIR ALL EXIT SIGNS NOT ILLUMINATED. | 1000 W NORTH AVE | COMPLAINT | FAILED | View |
RULES & REGS | 1000 W NORTH AVE | COMPLAINT | FAILED | View | |
RULES & REGS | 1000 W NORTH AVE | PERMIT | FAILED | View | |
VENT LINE TERMINATION | OFF DISCHARGE FROM FIREMAN'S DUMP VALVE'S LOCATED ON. | 1000 W NORTH AVE | PERIODIC | PASSED | View |
MAINT VERT RECIP CONVEYOR | PROVIDE CROSS-HEAD DATA PLATE ON VRC. | 1000 W NORTH AVE | PERMIT | FAILED | View |
MAINT VERT RECIP CONVEYOR | PROPERLY ENCLOSE TOP OF HOISTWAY (PREVIOUSLY CITED) | 1000 W NORTH AVE | PERIODIC | PASSED | View |
REPAIR INTERIOR STAIR SYSTEM | INSTALL HANDRAIL RETURNS AT STAIRS | 1000 W NORTH AVE | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | MAINTAIN ALL EXIT SIGNS AND EMERGENCY LIGHTS INCLUDING BATTERIES IN ALL AREA'S | 1000 W NORTH AVE | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | RETAG ALL FIRE EXTINGUISHERS AND ANSOL SYSTEM OPEN VIOLATION | 1000 W NORTH AVE | PERIODIC | FAILED | View |