Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ARRANGE PREMISE INSPECTION | NO ENTRY | 5050 S EAST END AVE | PERIODIC | FAILED | View |
TEST G & S ALL ELE | EV001786. | 5050 S EAST END AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL OR MAKE EMERGENCY PHONE IN ELEVATORS APARTMENT TO 24/7 OPERATE WITH DEDIGATES LINGS | 5050 S EAST END AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 1 TEST | 5050 S EAST END AVE | PERIODIC | PASSED | View |
POST OWNER/MANAGERS NAME/# | INCOMPLETE INFORMATION POSTED. | 5050 S EAST END AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ACCESS TO DOOR: 6B, 10B, 14C SERVICE AND 14D SERVICE - UNABLE TO VERIFY FIRE RATING, CLOSING AND LATCHING CONDITIONS. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
FILE BLDG REGISTRATION | BUILDING IS NOT REGISTERED FOR 1990 TO 2011. | 5050 S EAST END AVE | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 5050 S EAST END AVE | PERIODIC | CLOSED | View | |
NO ENTRY | 5050 S EAST END AVE | PERIODIC | CLOSED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | TEST FIRE SERVICE UPON COMPLETION OF WORK | 5050 S EAST END AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL A FIRE RATED SELF CLOSING/LOCKING MACHINE ROOM DOOR | 5050 S EAST END AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FILL CONCRETE OPINING TOP OF SHAFT INSIDE HOISTWAY | 5050 S EAST END AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL DIVIDER NETTING SIGNIFY SEPARATION FOR MULTIPLE HOISTWAY | 5050 S EAST END AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COVER "OLD" ESCUTCHIONS ON HOISTWAY DOOR | 5050 S EAST END AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RETEST GRIPPER | 5050 S EAST END AVE | PERMIT | PASSED | View |
PROVIDE GUARD RAIL 42 IN HIGH | WEST BASEMENT STAIRWAY - GUARDRAIL SECTIONS ARE OF "LADDER" TYPE, WITH HORIZONTAL TIES SPACED 21 INCHES APART. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
PROVIDE | SMOKE DETECTORS AND VOICE COMMUNICATION SYSTEM INSTALLATION IS IN PROCESS. COMPLETE INSTALLATION OF ONE WAY-TWO WAY COMMUNICATION SYSTEM THROUGHOUT BUILDING PER SECTION CODE 13-196-204. COMPLETE INSTALLATION OF WIRED SMOKE DETECTORS THROUGHOUT BUILDING PER SECTION CODE 13-196-210. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
SELF-CLOSE DOOR >4 STORY RES. | 7F - SERVICE DOOR NOT LATCHING - RUBBING ON FRAME. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
SELF-CLOSE CLASS B FIRE DOOR | PENTHOUSE: STAIRWELL ACCESS PANEL DOOR - FIRE RATING HOUR MISSING FROM THE LABEL, WITH MISSING CLOSER. 14TH FLOOR / ELEVATOR LOBBY CEILING HATCH OPENING - CLASS B ACCESS PANEL DOOR, WITH STAIRCASE REQUIRED. BASEMENT: WORKSHOP ROOM - DOOR MISSING LABEL. BIKE / STORAGE ROOM - NO DOOR LABEL. BOILER ROOM - FIRE RATING HOUR MISSING FROM THE LABEL. 1ST FLOOR: REAR LOBBY ACCESS PANEL WOOD DOOR - MISSING LABEL. BIKE ROOM - DOOR LABEL MISSING. ALL FLOORS: ELEVATOR LOBBY DOORS - MISSING LABEL. 4D SERVICE DOOR - NOT CLOSING, RUBBING ON FLOOR. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
CLASS B DOOR IN STAIRWELL | ALL FLOOR: STAIRWELL DOORS - NO FIRE RATING HOURS ON LABELS. 4N STAIRWAY - DOOR HITTING THE WALL. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
REPAIR EXTERIOR DOOR HARDWARE | PENTHOUSE: ROOF ACCESS EXTERIOR DOOR - CLOSER BROKEN. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
OBSTRUCTIONS IN EXIT WAY | EXIT OBSTRUCTIONS: SERVICE DOORS BLOCKED WITH REFRIGERATOR - 2C, 3A, 3C, 4C, 4D, 5B, 5C, 6C, 7C, 7D, 8A, 8C, 8D, 9B, 9D, 10C, 10D, 11A, 11C, 11D, 12C, 12D, 13B, 13C, 13D, AND 14C.SERVICE DOORS BLOCKED BY KITCHEN STOVE, SHELVES AND COUNTER: 1F, 2C, 3A, 3B, 4A, 6A, 6B, 7A, 9A, 11B, 12A AND 14D. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
CLASS A FIRE DOOR, NO GLASS | GROUND FLOOR STORAGE ROOM, NEAR WEST EXIT DOOR - CURRENTLY USED AS STORAGE FOR LAWN MOWERS, WEED WACKER AND OTHER LAWN EQUIPMENTS AND MATERIALS - EXTEND 3-HOUR CMU BLOCK WALL TO THE CONCRETE CEILING, AND INSTALL 3-HOUR RATED CLASS A DOOR. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
RELOCATE SMOKE DETECTOR | STAIRWELL AT TOP AND PENTHOUSE MECHANICAL ROOM - SMOKE DETECTOR LOCATED 4 FEET BELOW THE CEILINGS. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
PROVIDE | PENTHOUSE MECHANICAL ROOM, TENANT STORAGE ROOMS AND BIKE ROOMS, - EMERGENCY LIGHTS MISSING (SEC.13-160-690). | 5050 S EAST END AVE | PERIODIC | PASSED | View |
INSTALL EXIT SIGN | BIKE / STORAGE ROOM AND BOILER ROOM - EXIT SIGNS - MISSING. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
INSTALL SMOKE DETECTORS | BIKE / STORAGE ROOMS - SMOKE DETECTORS - MISSING. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
CARB MONOX DETECT IN RESID | BIKE / STORAGE ROOMS - CARBON MONOXIDE DETECTORS - MISSING. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
DOOR SWING IN DIR. OF TRAVEL | BASEMENT BIKE / STORAGE ROOM AND 1ST FLOOR BIKE ROOM - DOORS SWING IN OPPOSITE DIRECTION OF EXIT TRAVEL. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
I-A I-B I-C AND II FIRE RESIST | BASEMENT: TENANT STORAGE CAGES BUILT WITH WOOD AND CHAIN-LINK. BOILER ROOM ENTRY PLATFORM BUILT WITH WOOD BOARDS. REMOVE AND REPLACE WITH NON-COMBUSTIBLE MATERIALS. | 5050 S EAST END AVE | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | BOTH STAIRWAYS: RAILING AND GUARDRAIL SECTIONS ARE OF "LADDER" TYPE, WITH HORIZONTAL TIES SPACED 18 INCHES APART. GUARDRAIL HEIGHT ARE ONLY 36 INCHES. PERMIT REQUIRED FOR REPAIRS. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
PROVIDE | FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN. (13-196-206D) | 5050 S EAST END AVE | COMPLAINT | PASSED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY | 5050 S EAST END AVE | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | BUILDING IS NOT REGISTERED FOR 1990 TO 2011. | 5050 S EAST END AVE | PERIODIC | FAILED | View |
PROVIDE | BOTH STAIRWAYS - STAIRWELL IDENTIFICATION AND GEOGRAPHICAL LOCATIONS MISSING AT EACH FLOOR CORRIDORS (SEC.13-76-075). | 5050 S EAST END AVE | PERIODIC | PASSED | View |
COVER OUTLETS AND JBS | 1ST FLOOR BIKE ROOM - JUNCTION BOX OPEN AND MISSING COVER. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
EXPOSED WIRING | 1ST FLOOR BIKE ROOM - EXPOSED WIRES FROM OPEN JUNCTION BOX. | 5050 S EAST END AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | 1. EMERGENCY PHONES. 2.27.1.1.2 2.27.1-1.3. 2. DOOR RESTRICTOR 2.12.5. 18-30-010, 13-20-120. EV001786 | 5050 S EAST END AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR ALARM BELLS AND EMERGENCY PHONES IN BOTH ELEVATORS | 5050 S EAST END AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM ALL CATEGORY TESTING AS NEEDED ON BOTH ELEVATORS | 5050 S EAST END AVE | PERIODIC | PASSED | View |