Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
INSTALL SMOKE DETECTORS | 2ND FLOOR NO SMOKE DETECTOR INTERIOR STAIR | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | 2ND FLOOR NO CARBON MONOXIDE DETECTOR | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
INSTALL SMOKE DETECTORS | ENCLOSE PORCH, 2ND FLOOR NO SMOKE DETECTOR. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | 2ND FLOOR NO CARBON MONOXIDE DETECTOR. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 2ND FLOOR BATHROOM WALL AND CEILING WATER DAMAGE. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQUIRED | 2ND FLOOR ALTER TO APARTMENT. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
BASEMENT, DISCONTINUE | BASEMENT ALTER. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
EGRESS -BASEMENT | BASEMENT ONE MEANS OF EGRESS. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
SEPARATION OF DWELLING ADEQUAT | BASEMENT CEILING, OPEN CEILING JOIST AND CEILING TILES. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
PARTITIONS, N/L/B - BASEMENT | BASEMENT PARTITION WALL WOOD PANELING AND OPEN STUDS. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
CEILING HEIGHT - 7' - BASEMENT | BASEMENT CEILING HEIGHT 6'2". | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | BASEMENT DECONVERT. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
WORK NOT ALLOWED | BASEMENT REMOVE. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
RMV PLBFIX INSTALLD W/0 PERMIT | BASEMENT REMOVE PLUMBING AND CAP PARTITION BEHIND WALL. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REMOVE GAS LINE AND JET | BASEMENT REMOVE GAS LINE AND CAP BEHIND WALL. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
HEAT UNIT ADEQUATELY | 2ND FLOOR NO HEAT (GAS CO DISCONNECTED SPACE HEATER ABD STOVE AND TAG ITEMS | 13306 S MACKINAW AVE | COMPLAINT | PASSED | View |
INSTALL SMOKE DETECTORS | 2ND FLOOR NO SMOKE DETECTOR | 13306 S MACKINAW AVE | COMPLAINT | PASSED | View |
CARB MONOX DETECT IN RESID | 2ND FLOOR NO CARBON MONOXIDE DETECTOR | 13306 S MACKINAW AVE | COMPLAINT | PASSED | View |
HEAT UNIT ADEQUATELY | 2ND FLOOR NO HEAT | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
PROPER SIZE GRD ELECTRODE COND | NO GROUND | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
REPAIR EXTERIOR WALL | NORTH ELEVATION SIDING MISSING. | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
MAINTAIN WINDOW | EAST ELEVATION ATTIC WINDOW FRAME ROTTED. | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
REPAIR/REBUILD GARAGE OR SHED | GARAGE SERVICE DOOR OFF HINGES, PARTIALLY OPEN, ROOF SAGGING, SIDING BUCKLING. | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
REPAIR PORCH SYSTEM | SCRAPE AND PAINT RUSTED METAL HAND AND GUARD RAILS FRONT ONE STORY CONCRETE PORCH. | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
DEFECTIVE METER EQUIPMENT | REPLACE RUSTED METER BOX. | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
SECURE RACEWAY | PROPERLY SUPPORT SERVICE RISER AND METER BOX. | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
SEE INSPECTOR COMMENTS | PROVIDE INTERIOR INSPECTION TO VERIFY LOCATION AND CONDITION OF ELECTRICAL PANEL. (18-27-110.3) | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
PROVIDE WEATHER PROOF BOXES, LIGHTS, FITTINGS AND APPROVED RACEWAY FOR EXTERIOR LIGHTS AT GARAGE ENTRANCE DOOR AREA. (18-27-110.11) | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View | |
OBTAIN ELECTRICAL PERMIT AND CONTRACTOR TO CORRECT VIOLATIONS. (13-12-360) | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View | |
PLANS & PERMITS REQ - CONTRCTR | SUBMIT PLANS AND OBTAIN PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO ATTIC OR RESTORE THE BUILDING TO THE ORIGINAL STATE | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
REPLACE DEFECTIVE TRAP | TRAP FOR KITCHEN SINK LEAKING ON 1ST FLOOR | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
OBTN PERMIT FOR PLUMBING WORK | OBTAIN PERMIT FOR PLUMBING WORK BEFORE UNDERTAKING WORK | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
LICENSED BONDED PLMBG CONTRCTR | EMPLOY LICENSED AND BONDED PLUMBER TO PERFORM PLUMBING WORK | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
RMV PLBFIX INSTALLD W/0 PERMIT | INSTALLED BATHTUB AND KITCHEN SINK, 2ND FLOOR | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
DEFECTIVE FEEDER | SERVICE FEEDER FROM METER TO PANEL- LACKS LOCKNUT AND BUSING, CONTINUITY ISSUE | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
DEFECTIVE DISTRIBUTION | PANEL HAS ILLEGAL SPLICES (18-27-373.5, 18-27-110.14) | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
BOND AROUND FITTINGS | BOND NEUTRAL SERVICE DISCONNECT (18-27-250.28) | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
CONTINUITY OF RACEWAY | LOOSE FITTING AT PANEL | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
DEFECTIVE OUTLETS | 1ST FLOOR LIVING ROOM | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
DEFECTIVE FIXTURES | NON-WORKING AND MISSING GLOBES, 1ST AND 2ND FLOORS | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
SEE INSPECTOR COMMENTS | PROVIDE GFCI PROTECTION FOR KITCHEN COUNTERS AND BATHROOMS (18-27-570.8) | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
PROVIDE ALL REQUIRED SMOKE AND CARBON MONOXIDE DETECTORS (18-27-570.10) | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View | |
REPLCE WINDOW PANES, PLEXGLAS | NORTHEAST AT 1ST - WINDOW - BROKEN PANE. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REPAIR GUTTER | NORTH GUTTER - SAGGING AND BENT. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | NORTHWEST AT 1ST - LOOSE AND FALLING SIDING. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
UNSANITARY CONDITIONS-ANIMALS | WEST YARD - DOG FOULING. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
STOP/REMOVE NUISANCE | EAST AT 1ST - EXTENSION CORD RUN OUT 1ST FLOOR WINDOW INTO BUSHES. WEST YARD - SEVERAL LARGE 6'' TO 12'' WIDE BY 4'' TO 8'' DEEP HOLES IN YARD. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | BUILDING INTERIOR - NO RESPONSE - UNVERIFIED DETECTORS AND CONDITIONS. UNABLE TO INSPECT INTERIOR STAIRWAYS. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REPAIR/REBUILD GARAGE OR SHED | GARAGE - SIDING - LOOSE AND BUCKLED. NORTH DOWNSPOUT MISSING SECTION. NORTH GUTTER - LOOSE AND TIPPED. SOUTH ROOF SECTION - SAGGING. SERVICE DOOR OUT OF PLUMB WITH LARGE 2'' TO 3'' GAP AT BOTTOM SILL. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | BOYFRIEND OF TENANT HOME ALONE; DID NOT WANT TO PERMIT ACCESS. UNABLE TO INSPECT INTERIOR, STAIRWELLS, APARTMENTS, ATTIC, BASEMENT, AND ENCLOSED REAR PORCH. UNVERIFIED DETECTORS AND OCCUPANCY. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL - LOOSE, HANGING SIDING | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
UNSANITARY CONDITIONS-ANIMALS | DOG FECES IN REAR YARD | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
STOP/REMOVE NUISANCE | (NORTH) LADDER, HOSES, COOLERS, A/C CONDENSERS CLUTTERING SERVICEWALK; BOAT ON SIDE OF GARAGE; (EAST) GRILL ON FRONT LANDING | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | LADDER, HOSES, COOLERS, A/C CONDENSER CLUTTERING SERVICEWALK AND OBSTRUCTING PASSAGEWAY | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
DEBRIS, EXCESSIVE | TRASH, DEBRIS ON FRONT LANDNG AND IN FRONT YARD | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REPAIR/REBUILD GARAGE OR SHED | GARAGE - FOUNDATION HAS BUCKLED, STRUCTURE IS SAGGING AT CENTER; WINDOW MISSING AT EAVE. PLANS AND PERMIT REQUIRED TO REPAIR GARAGE. | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REPAIR FENCE | WOODEN FENCE - LEANING; UNSECURED | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | (NORTH) 1ST FLOOR -WINDOW - CRACKED PANE; BASEMENT - WINDOW PANE MISSING; (SOUTH) BASEMENT - WINDOW - CRACKED PANE | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
NO POSTED ADDRESS | POST ADDRESS. | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
WORK NOT ALLOWED | REMOVE ALL PARTITIONS AND FIXTURES (INCLUDING PLUMBING AND ELECTRICAL) INSTALLED IN ATTIC WITHOUT PERMITS | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
PROV WC LAV TUB TO FAMILY UNIT | ON 2ND FLOOR BATHTUB LOCATED IN SEPARATE ROOM FROM TOILET AND SINK | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
PROPER MATRL WATER SUPPLY PIPE | REMOVE PVC FLEX WATER LINES TO FIXTURES THROUGHOUT BUILDING | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
NO PERMIT WIRING | FOR ALTERATION OF BUILDING ELECTRICAL SYSTEM- NEW ELECTRICAL PANEL INSTALLED, BUILDOUT OF 2ND FLOOR FOR ADDED DWELLING UNIT | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
CIRCUIT ONE UNIT ONLY | TWO DWELLING UNITS FED FROM SINGLE METER AND PANEL | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
PROPER SIZE OCP | REMOVE 30 AMP BRANCH CIRCUIT WITH #12 WIRE ATTACHED | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
INSTALL COVERS | ABOVE KITCHEN SINK AND IN BASEMENT, OPEN SWITCH BOX 2ND FLOOR | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
ACCESS TO JBS | BASEMENT CEILING BY COLUMN | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
UNAPPROVED HEATING DEVICE | 2ND FLOOR TENANT USING ELECTRICAL HEATER | 13306 S MACKINAW AVE | COMPLAINT | PASSED | View |
SAFE WORKING CONDITIONS | 2ND FLOOR SPACE HEATER BROKEN AND DISCONNECTED | 13306 S MACKINAW AVE | COMPLAINT | PASSED | View |
CUT OR REMOVE HIGH WEEDS | WEST, NORTH ELEVATIONS - WEEDS, TALL BUSHES THRU-OUT | 13306 S MACKINAW AVE | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE FAUCET | TUB FAUCET ON 2ND FLOOR LEAKING | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
EXPOSED WIRING | ON REAR STAIRS TO BASEMENT FROM SWITCH TO LIGHT | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
PRV DISCHARGE PIPE FROM PRV | PROVIDE DISCHARGE PIPE FROM WATER HEATER AND HOT WATER STORAGE TANK RELIEF VALVE | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |
ARMORED CABLE | USED AS PRIMARY WIRING METHOD IN BASEMENT CEILINGS AND WALLS | 13306 S MACKINAW AVE | COMPLAINT | CLOSED | View |