Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OWNER OR LICENSED CONTRACTOR | 1605 E 50TH ST | PERIODIC | PASSED | View | |
HEAT UNIT ADEQUATELY | 1ST FLOOR-1C-ROOM TEMPERATURE IS 64 10:47 AM; HEATING SYSTEM IS NOT ON AT TIME OF INSPECTION. | 1605 E 50TH ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR REQ, RESDNTL | BASEMENT-EAST STAIRWELL-FIRE EXTINGUISHER IS MISSING. | 1605 E 50TH ST | PERIODIC | FAILED | View |
POST OWNER/MANAGERS NAME/# | NORTH ELEVATION OWNER'S I.D. SIGN NOT POSTED. | 1605 E 50TH ST | PERIODIC | FAILED | View |
REPAIR OR REPLACE | NORTH ELEVATION DOORBELL SYSTEM IS FROZEN-OUT OF ORDER(SEC.7-28-060). | 1605 E 50TH ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | WEST STAIRWELL-1ST FLOOR EXIT SIGN NOT ILLUMINATED. | 1605 E 50TH ST | PERIODIC | FAILED | View |
REMOVE LEAD MATERIALS F/COVER | 2ND, 4TH, 5TH FLOOR-ELECTRICAL ROOM-LOCKS WILL NOT ENGAGE-DOOR WILL NOT REMAIN CLOSED. | 1605 E 50TH ST | PERIODIC | FAILED | View |
ILLUMINATE PUBLIC STAIR/HALL | 5A FLOOR-CORRIDOR-BULBS ARE OUT-VERY LOW ILLUMINATION DIM CORRIDOR. | 1605 E 50TH ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 11TH FLOOR-ELECTRICAL ROOM-DOOR RUBS FLOOR-DIFFICULT TO OPEN. | 1605 E 50TH ST | PERIODIC | FAILED | View |
CARB MONOX DETECT IN RESID | 3RD-14 FLOOR ALL APARTMENTS, LAUNDRY ROOM-CARBON MONOXIDE DETECTOR IS MISSING. | 1605 E 50TH ST | PERIODIC | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | EAST STAIRWELL-13TH FLOOR CLOSER INSTALLED BUT DOOR DOES NOT CLOSE COMPLETELY. | 1605 E 50TH ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINQUISHERS MISSING LABELS STAIRWAYS | 1605 E 50TH ST | PERIODIC | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | DOOR CLOSER NOT WORKING STAIRWAY 13A, 8A, 5A | 1605 E 50TH ST | PERIODIC | FAILED | View |
RESTORE EXIT AND EM | EMERGENCY III LIGHTING OUT IN STAIRWAY 7A, 2A | 1605 E 50TH ST | PERIODIC | FAILED | View |
INSTALL SMOKE DETECTORS | NO SMOKE DETECTOR IN LAUNDRY ROOM IN BASEMENT. | 1605 E 50TH ST | PERIODIC | FAILED | View |
CARB MONOX DETECT IN RESID | NO CARBON MONOXIDE IN LAUNDRY ROOM IN BASEMENT. | 1605 E 50TH ST | PERIODIC | FAILED | View |
POST OWNER/MANAGERS NAME/# | NORTH ELEVATION OWNER'S I.D. SIGN NOT POSTED. | 1605 E 50TH ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | WEST STAIRWELL-1ST FLOOR EXIT SIGN NOT ILLUMINATED. | 1605 E 50TH ST | PERIODIC | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | EAST STAIRWELL-13TH FLOOR CLOSER INSTALLED BUT DOOR DOES NOT CLOSE COMPLETELY. | 1605 E 50TH ST | PERIODIC | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | DOOR CLOSER NOT WORKING STAIRWAY 13A, 8A, 5A | 1605 E 50TH ST | PERIODIC | FAILED | View |
RESTORE EXIT AND EM | EMERGENCY III LIGHTING OUT IN STAIRWAY 7A, 2A | 1605 E 50TH ST | PERIODIC | FAILED | View |
INSTALL SMOKE DETECTORS | NO SMOKE DETECTOR IN LAUNDRY ROOM IN BASEMENT. | 1605 E 50TH ST | PERIODIC | FAILED | View |
CARB MONOX DETECT IN RESID | NO CARBON MONOXIDE IN LAUNDRY ROOM IN BASEMENT. | 1605 E 50TH ST | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | NOT REGISTERED 2012 | 1605 E 50TH ST | PERIODIC | FAILED | View |
RESTORE EXIT AND EM | 14TH FLOOR (EAST & WEST STAIRWELLS); BASEMENT (EAST STAIRWELL) - EMERGENCY LIGHTS - NOT WORKING AT TIME OF INSPECTION | 1605 E 50TH ST | PERIODIC | FAILED | View |
CLASS B DOOR IN STAIRWELL | VARIOUS LOCATIONS, BOTH STAIRWELLS - FIRE DOORS - FIRE-RATING TAGS MISSING | 1605 E 50TH ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | 14TH FLOOR (EAST STAIRWELL) - FIRE EXTINGUISHER EXPIRED; TAGGED 2010 | 1605 E 50TH ST | PERIODIC | FAILED | View |
REPAIR DOOR, INT. | SUB-BASEMENT - BOILER ROOM - ENTRY DOOR - HITTING JAMB; LOOSE AT HINGES | 1605 E 50TH ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ACCESS TO UNIT 8A DOOR - UNABLE TO VERIFY FIRE RATING, CLOSING AND LATCHING CONDITIONS. | 1605 E 50TH ST | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | BLDG. - NOT REGISTERED FROM 2012 THRU 2014. | 1605 E 50TH ST | PERIODIC | FAILED | View |
CLASS B DOOR IN STAIRWELL | 3E STAIRWAY DOOR - NOT LATCHING. | 1605 E 50TH ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | UNABLE TO INSPECT MOST APARTMENTS. UNVERIFIED DETECTORS AND OCCUPANCY. | 1605 E 50TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | NO CAT 1 OR CAT 5 SAFETY TEST TAGS ON GOVERNOR PASSENGER AND FREIGHT | 1605 E 50TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL CODE DATA PLATES ON CONTROLLER PASSENGER AND FREIGHT ELEVATORS | 1605 E 50TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY1 TEST AND CATEGORY5 TEST ALL ELEVATORS | 1605 E 50TH ST | PERIODIC | PASSED | View |
SELF-CLOSE CLASS B FIRE DOOR | SUB-BASEMENT BOILER ROOM: ENTRY DOOR HITTING JAMB AND LOOSE AT HINGES - NEW CLASS B DOOR ASSEMBLY REQUIRED; DOOR ACCESS THROUGH STORAGE ROOM - LOOSE HINGES, NOT LATCHING AND MISSING LABEL; REAR EXTERIOR DOOR TO BE EQUIPED WITH PANIC BAR RELEASE PER ARCHITECT'S RECOMMENDATION. BASEMENT LAUNDRY ROOM DOOR ONLY 3/4 HOUR FIRE RATING. 14TH FLOOR, BUILT-IN HATCH ACCESS PANEL DOOR, WITH STAIRCASE TO PENTHOUSE MISSING FIRE RATED LABEL. 6TH, 7TH, 11TH AND 12TH FLOOR TRASH ROOM DOORS - NOT LATCHING, WITH 11TH FLOOR DOOR RUBBING ON FLOOR. | 1605 E 50TH ST | PERIODIC | FAILED | View |
SELF-CLOSE DOOR >4 STORY RES. | DOORS NOT PROPERLY CLOSING AND LATCHING: 3E, 9C AND 10B, WITH 3E DOOR RUBBING ON FLOOR MAT. | 1605 E 50TH ST | PERIODIC | FAILED | View |
PIPE OPENING W/NONCOMBUST MATL | PENTHOUSE - LARGE GAP AROUND DUCT PENETRATION. 5E, 6E AND 9E EAST STAIRWELL - HOLES ON WEST WALL. TENANT STORAGE - PIPE PENETRATIONS SEALED WITH SPRAY FOAM. BOILER ROOM - PIPE PENETRATION HOLES; BREACHED WALLS FILLED CONCRETE DEBRIS. SEAL ALL OPENINGS WITH PROPER FIRE-STOPPING MATERIALS SUCH AS FIRE-RATED CAULK, FILLED WITH MINERAL WOOL BACK-UP. EXPANDABLE SPRAY FOAM DRAFT-STOPPING CANNOT BE USED FOR FIRE-STOPPING PENETRATIONS. SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY STANDARDS. | 1605 E 50TH ST | PERIODIC | FAILED | View |
PROVIDE | SMOKE DETECTORS AND VOICE COMMUNICATION SYSTEM INSTALLATION IS IN PROCESS. COMPLETE INSTALLATION OF ONE-TWO WAY COMMUNICATION SYSTEM THROUGHOUT THE BUILDING PER SECTION CODE 13-196-204. COMPLETE INSTALLATION OF WIRED SMOKE DETECTORS THROUGHOUT THE BUILDING PER SECTION CODE 13-196-210. | 1605 E 50TH ST | PERIODIC | FAILED | View |
PROVIDE | BOTH INTERIOR STAIR SYSTEMS - MISSING GEOGRAPHICAL LOCATIONS ON CORRIDOR WALLS AND INSIDE STAIRWELLS (SEC.13-76-075). | 1605 E 50TH ST | PERIODIC | FAILED | View |
PROVIDE | SUB-BASEMENT BOILER ROOM: ACCESS THROUGH THE STORAGE ROOM - 2' DEEP DROP WITHOUT STAIR SYSTEM. PROVIDE NON-COMBUSTIBLE STAIRCASE, WITH RAILINGS FROM SUB-BASEMENT TO BASEMENT STORAGE SPACE. | 1605 E 50TH ST | PERIODIC | FAILED | View |
POST OWNER/MANAGERS NAME/# | BUILDING - INCOMPLETE MANAGEMENT INFORMATION SIGN POSTED - MAILING ADDRESS AND CONTACT PHONE MISSING. | 1605 E 50TH ST | PERIODIC | FAILED | View |
PROVIDE CLASS A FIRE DOOR | BASEMENT: ELECTRIC "MAIN" SERVICE DISCONECT ROOM - DOUBLE SWING CLASS A DOOR - DRAFTY, WITH EDGE OVERLAP COVER MISSING. EMERGENCY II SYSTEM (ELECTRIC TRANSFER SWITCH) ROOM BUILT WITHOUT A PERMIT - ENTRY DOOR MISSING. BOOSTER PUMP WITH DISCONNECT ROOM BUILT WITHOUT A PERMIT. FOUR-HOUR RATED ENCLOSURE WITH CLASS A DOOR REQUIRED. SUBMIT PLANS AND OBTAIN PERMIT FOR RENOVATION. | 1605 E 50TH ST | PERIODIC | FAILED | View |
INSTALL SMOKE DETECTORS | LAUNDRY ROOM - SMOKE DETECTOR - MISSING. | 1605 E 50TH ST | PERIODIC | FAILED | View |
CARB MONOX DETECT IN RESID | LAUNDRY ROOM - CARBON MONOXIDE DETECTOR - MISSING. | 1605 E 50TH ST | PERIODIC | FAILED | View |
INSTALL EXIT SIGN | BASEMENT: LAUNDRY ROOM AND TENANT STORAGE / BIKE ROOM - EXIT AND DIRECTIONAL SIGNS - MISSING. | 1605 E 50TH ST | PERIODIC | FAILED | View |
REMOVE | 14TH FLOOR CEILING: HATCH ACCESS PANEL DOOR WITH STAIRCASE TO PENTHOUSE MOUNTED ON WOODEN BOARD - REMOVE AND REPLACE WITH NON-COMBUSTIBLE MATERIALS (SEC.15-12-030). | 1605 E 50TH ST | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | EAST AND WEST INTERIOR STAIRWAYS - RAILING AND GUARDRAIL SECTIONS ARE OF "LADDER" TYPE, WITH HORIZONTAL TIES SPACED 18 INCHES APART. GUARDRAIL HEIGHT ARE ONLY 36 INCHES HIGH. PERMIT REQUIRED TO REPAIR BOTH STAIRWAYS. | 1605 E 50TH ST | PERIODIC | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | EXTERIOR BASEMENT TO GRADE STAIRWAY - GUARDRAIL SECTIONS ARE OF "LADDER" TYPE, WITH HORIZONTAL TIES SPACED 18 INCHES APART, AND ONLY 36 INCHES HIGH. | 1605 E 50TH ST | PERIODIC | FAILED | View |
EXPOSED WIRING | SUB-BASEMENT: BOILER ROOM - EXPOSED WIRES IN OPEN JUNCTION BOX. | 1605 E 50TH ST | PERIODIC | FAILED | View |
PROVIDE | SUB-BASEMENT: PROVIDE TWO-HOUR ENCLOSURE FOR THE TRASH CHUTE DISCHARGED SPACE PER SECTION CODE 15-8-170 (A). | 1605 E 50TH ST | PERIODIC | FAILED | View |
PROVIDE | FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN. (13-196-206D) | 1605 E 50TH ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SCHEDULE "FINAL" INSPECTION WITH CITY OF CHICAGO ELEVATOR BUREAU & URBAN ELEVATOR FOR ELEVATOR MODERNIZATION PERMIT# 100117141 | 1605 E 50TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATAGORY 1 SAFETY TEST. | 1605 E 50TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 1 TEST | 1605 E 50TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR EMERGENCY LIGHT/ ALARM BELL | 1605 E 50TH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | UPDATE FIRE SERVICE/MAINTENANCE LOGS | 1605 E 50TH ST | PERIODIC | PASSED | View |
UNAPPROVED HEATING DEVICE | APT 6D USING ELECT HEAT AND STOVE FOR HEAT | 1605 E 50TH ST | COMPLAINT | FAILED | View |
WINDOW REPAIR FOR AIR SEEPAGE | APT 6D LIVING ROOM WINDOW AIR SEEPAGE. | 1605 E 50TH ST | COMPLAINT | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 1605 E 50TH ST | PERIODIC | CLOSED | View | |
REPAIR | BOTTOM REAR BLOW DOWN VALVE #1 FITZ. | 1605 E 50TH ST | PERIODIC | CLOSED | View |
INSTALL | CARBON MONOXIDE DETECTOR IN BOILER ROOM. | 1605 E 50TH ST | PERIODIC | PASSED | View |
COVER OUTLETS AND JBS | 14TH FLOOR CORRIDOR-COVER ON MISSING THERMOSTAT. | 1605 E 50TH ST | PERIODIC | FAILED | View |
PROVIDE | 5TH FLOOR-EAST STAIRWELL-GLASS PANEL MISSING AT FIRE HOSE CABINET DOOR .(SEC.7-28-060). | 1605 E 50TH ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | BASEMENT: TENANT STORAGE / BIKE ROOM - FIRE EXTINGUISHER'S TAG MISSING. | 1605 E 50TH ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CODE DATA PLATE ALL ELEVATORS | 1605 E 50TH ST | PERIODIC | PASSED | View |
COVER OUTLETS AND JBS | SUB-BASEMENT: BOILER ROOM - OPEN JUNCTION BOX. | 1605 E 50TH ST | PERIODIC | FAILED | View |