Chicago Building Violations Data: 36 Violations
Violation Inspector Comments Address Category Status View
TEST G & S ALL ELE EV008098 1617 E 50TH PL PERIODIC PASSED View
TEST G & S ALL ELE 5 YEAR SAFETY TEST. 1617 E 50TH PL PERIODIC CLOSED View
FILE BLDG REGISTRATION BLDG. - NOT REGISTERED FROM 2009 THRU 2014. 1617 E 50TH PL PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA NO CODE DATA PLATE ON CONTROLLERS 1617 E 50TH PL PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CAT1 ANNUAL SAFETY TEST ON ELEVATORS #1-2 1617 E 50TH PL PERIODIC FAILED View
INSTALL SMOKE DETECTORS BASEMENT - LAUNDRY ROOM - MISSING SMOKE DETECTOR. 1617 E 50TH PL PERIODIC FAILED View
PROVIDE BOTH STAIRWAYS - STAIR IDENTIFICATIONS AND GEOGRAPICAL LOCATIONS MISSING AT EACH FLOOR ON INTERIOR SIDE OF STAIRWELL AND CORRIDOR WALL (SEC. 13-76-075). 1617 E 50TH PL PERIODIC FAILED View
INSTALL EXIT SIGN BASEMENT: TENANT STORAGE / BIKE ROOM - EXIT AND DIRECTIONAL EXIT SIGNS MISSING. 1617 E 50TH PL PERIODIC FAILED View
SELF-CLOSE CLASS B FIRE DOOR BOILER ROOM / REAR DOOR INTO BIKE ROOM - MISSING LABEL. TRASH CHUTES AT 1ST, 3RD AND 6TH FLOOR - NOT CLOSING. BOILER ROOM INTERIOR DOOR - BROKEN AND MISSING LABEL (NEW CLASS B DOOR REQUIRED). BASEMENT LAUNDRY ROOM - DOOR ONLY 3/4 HOUR. EMERGENCY II SYSTEM CLOSET - REVERSE CLOSER TO ALLOW DOOR TO SELF-CLOSE. 14TH FLOOR CEILING: BUILT-IN ACCESS HATCH PANEL DOOR, WITH STAIRCASE - MISSING FIRE RATED LABEL. BOILER ROOM REAR EXTERIOR DOOR TO BE EQUIPED WITH PANIC BAR RELEASE PER ARCHITECT'S RECOMMENDATION. 1617 E 50TH PL PERIODIC FAILED View
PROVIDE BOILER / GARBAGE CHUTE ROOM: PROVIDE NON COMBUSTIBLE STAIRWAY SYSTEM FROM SUB-BASEMENT TO BASEMENT LEVEL AT DOORS OPENING INTO STORAGE / BIKE ROOM (SEC. 13-196-570). 1617 E 50TH PL PERIODIC FAILED View
2HR SEP FOR STORAGE >100SF SEPARATE STORAGE ROOMS INSIDE BOILER ROOM AND BIKE ROOM WITH 2-HOUR ENCLOSURE AND CLASS B DOOR ASSEMBLY. PLANS AND PERMIT REQUIRED . 1617 E 50TH PL PERIODIC FAILED View
PROVIDE CLASS A FIRE DOOR ELECTRIC "MAIN" SERVICE DISCONNECT ROOM - DOUBLE SWING CLASS A DOOR HAS LARGE GAP AT BOTTOM, AND MISSING EDGE OVERLAP COVER. 1617 E 50TH PL PERIODIC FAILED View
POST OWNER/MANAGERS NAME/# BLDG. - INCOMPLETE MANAGEMENT INFORMATION SIGN POSTED - MISSING MAILING ADDRESS AND CONTACT PHONE NUMBERS. 1617 E 50TH PL PERIODIC FAILED View
PIPE OPENING W/NONCOMBUST MATL PENTHOUSE - PIPE PENETRATIONS SEALED WITH SPRAY FOAM. 14TH FLOOR / TRASH ROOM, AND BASEMENT / LAUNDRY ROOM - UNUSED OPEN PIPE TO BE CAPPED OR REMOVED AND SEAL WITH FIRE CAULK. SPRAY FOAM DRAFT-STOPPING CANNOT BE USED FOR FIRE-STOPPING PENETRATIONS. PROPER FIRE STOPPING MATERIALS SUCH AS FIRE CAULK WITH MINERAL WOOL BACK-UP IS RECOMMENDED. SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS. 1617 E 50TH PL PERIODIC FAILED View
1HR ENCL FLR TO FLR SHAFT/DUCT PENTHOUSE AND ELEVATOR MACHINE ROOM - TRASH CHUTE PIPE SHAFT WITH LARGE CAVITY ON FLOORS. 3RD FLOOR / ELECTRIC CLOSET - HOLE AROUND THE SHAFT. STAIRWELLS - OPENING AROUND THE PIPE PENETRATIONS. CLOSE AND SEAL ALL PENETRATION HOLES WITH PROPER FIRE STOPPING MATERIALS. SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY 1617 E 50TH PL PERIODIC FAILED View
PROVIDE GUARD RAIL 42 IN HIGH EXTERIOR BASEMENT TO GRADE STAIRWAY - GUARDRAIL SECTIONS ARE OF "LADDER" TYPE, WITH HORIZONTAL TIES SPACED 18 INCHES APART AND ONLY 36 INCHES HIGH. 1617 E 50TH PL PERIODIC FAILED View
CLASS B DOOR IN STAIRWELL EAST AND WEST STAIRWAYS - CLASS B DOORS WITH ONLY SPRING LOADED HINGE CLOSERS THROUGHOUT. PROVIDE BOTH STAIRWAY CLASS B DOORS WITH HEAVY DUTY 1-1/2 HOUR UL APPROVED DOOR SELF-CLOSING DEVICE. 1617 E 50TH PL PERIODIC FAILED View
REMOVE 14TH FLOOR CEILING: ACCESS PANEL HATCH DOOR, WITH STAIRCASE TO PENTHOUSE MOUNTED ON WOODEN BOARDS - REMOVE AND REPACE WITH NON-COMBUSTIBLE MATERIALS (SEC 15-12-030). 1617 E 50TH PL PERIODIC FAILED View
PROVIDE PROVIDE 2-HOUR ENCLOSURE FOR TRASH CHUTE DISCHARGE SPACE, WITHIN THE BOILER ROOM PER SECTION 15-8-170(A). 1617 E 50TH PL PERIODIC FAILED View
PROVIDE FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN. (13-196-206D) 1617 E 50TH PL COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CATAGORY 1 SAFETY TESTS ON CARS #1&2 1617 E 50TH PL PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA SCHEDULE "FINAL" INSPECTION WITH CITY OF CHICAGO ELEVATOR BUREAU & URBAN ELEVATOR FOR ELEVATOR MODERNIZATION. PERMIT# 100117140 1617 E 50TH PL PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CATAGORY 1 SAFETY TESTS ON CARS #1&2 1617 E 50TH PL PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR 2ND FLOOR DOWN HALL CALL FOR PASSENGER ELEVATOR 1617 E 50TH PL PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR EMERGENCY LIGHT & ALARM BELL 1617 E 50TH PL PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA UPDATE FIRE SERVICE LOG/ MAINTENANCE LOGS 1617 E 50TH PL PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CATEGORY 1 TEST ON ELEVATORS 1617 E 50TH PL PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE ANTI-ROTATION DEVICE FOR SHACKLES ON BOTH ELEVATORS 1617 E 50TH PL PERIODIC PASSED View
INSTALL PROPER SIZE DISCHARGE PIPE SAFETY RELIEF #2 FITZ SM. 1617 E 50TH PL PERIODIC CLOSED View
REMOVE DISCHARGE PIPE FROM SAFETY RELIEF, WRONG SIZE, DISCHARGE PIPE CANNOT BE REDUCED. 1617 E 50TH PL PERIODIC CLOSED View
REPAIR LEAKING FITTINGS #7 BRADFORD 12 HWT. 1617 E 50TH PL PERIODIC CLOSED View
OWNER OR LICENSED CONTRACTOR 1617 E 50TH PL PERIODIC CLOSED View
FILE BLDG REGISTRATION NOT REGISTERED 2009-2011 1617 E 50TH PL PERIODIC FAILED View
OBSTRUCTIONS IN EXIT WAY UNIT 3E - SHOE RACK OBSTRUCTING EGRESS. UNIT 2E - CARPET OBSTRUCTING FULL DOOR SWING, MAKING IT DIFFICULT TO OPEN AND CLOSE. 1617 E 50TH PL PERIODIC FAILED View
REPAIR INTERIOR STAIR SYSTEM EAST AND WEST INTERIOR STAIRWAYS - RAILING AND GUARDRAIL SECTIONS ARE OF "LADDER" TYPE, WITH HORIZONTAL TIES SPACED 18 INCHES APART. GUARDRAIL HEIGHT ONLY 36 INCHES. PERMIT REQUIRED TO REPAIR BOTH STAIRWAYS. 1617 E 50TH PL PERIODIC FAILED View
ARRANGE PREMISE INSPECTION WRONG ADDRESS PROVIDED. UNABLE TO INSPECT INTERIOR, STAIRWELLS, APARTMENTS (?), AND BASEMENT. UNVERIFIED DETECTORS AND CONDITIONS. 1617 E 50TH PL PERIODIC FAILED View