Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ACCESS TO JBS | PROVIDE ACCESS TO JUNCTION BOXES AT BASEMENT WALLS AND CEILINGS LOCATED BEHIND NEW STUDS PROVIDE ACCESS TO JUNCTION BOX AT REAR EXTERIOR ELEVATION FOR EXTERIOR LIGHTING AT 1ST FLOOR LEVEL | 536 W 47TH ST | COMPLAINT | PASSED | View |
SECURE RACEWAY | PROPERLY SUPPORT CONDUITS AT BASEMENT CEILING AND WALLS | 536 W 47TH ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE PANEL SCHEDULE FOR NEW 100 AMP PANEL 18-27-384.13 | 536 W 47TH ST | COMPLAINT | PASSED | View |
NO PERMIT WIRING | PROVIDE PLANS AND PERMITS FOR WORK PERFORMED IN ATTIC AND BASEMENT WITHOUT | 536 W 47TH ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | REMOVE DOUBLE TERMINATIONS AT SERVICE PANEL IN BASEMENT 18-27-110.14 | 536 W 47TH ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | REMOVE ALL MINI BREAKERS USED IN SERVICE PANEL 18-27-240.85 | 536 W 47TH ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | MOVE MAIN WATER GROUND CONNECTION TO WITHIN 5 FEET OF WHERE WATER SERVICE ENTERS THE BUILDING 18-27-250.50 | 536 W 47TH ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | REMOVE ALL CONDUITS AT BASEMENT WALLS AND CEILINGS RUN IN UNWORKMAN LIKE MANNER 18-27-110.14 | 536 W 47TH ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE BONDING BUSHINGS AT NEW 100 AMP SERVICE PANEL 18-27-250.92 AND 94 | 536 W 47TH ST | COMPLAINT | PASSED | View |