The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
FILE BLDG REGISTRATION | BUILING NOT REGISTERED 1990-2006 | 3458 W LAKE ST | PERIODIC | FAILED | View |
POST OWNER/MANAGERS NAME/# | BUILDING POST MANAGEMENT SIGN | 3458 W LAKE ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | 1ST (STORE) RECHARGE AND TAG FIRE EXTINGUSHIERS | 3458 W LAKE ST | PERIODIC | FAILED | View |
CONTINUITY OF RACEWAYS | PROVIDE GROUND CONTINUITY FOR LIGHT FIXTURE THROUGHOUT CEILING AREA, FIXTURE BY WALK-IN COOLER AREA AND INSIDE OF WALK-IN COOLER AREA WITH BARE WIRES. (DANGEROUS AND HAZARDOUS CONDITION) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | BROKEN WINDOWS 2ND FLOOR. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
BLOCKED FIRE DOOR | REAR EXTERIOR AT REAR EXIT EXCESSIVE JUNK AND DEBRIS. ALSO BLOCKING REAR EXIT. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
SUPPLEMENTAL GROUND | PROVIDE SUPPLEMENTAL GROUND FOR METER BANK AREA. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
ABANDONED EQUIPMENT | REMOVE ALL ABANDONED EXTERIOR LIGHTS AND JUNCTION BOXES AND IN INTERIOR CEILING AREA REMOVE ALL ABANDONED JUNCTION BOXES AND CONDUIT RUNS. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
OPEN | NO FLOOR DRAIN AT EMPLOYEE BATHROOM. (18-29-412.4.3) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
SECURE RACEWAY | PROPERLY SUPPORT ALL JUNCTION BOXES AND LIGHTS AT EXTERIOR AREA OF BUILDING. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. ALL CONDUIT, JUNCTION BOXES, DEVICES THROUGHOUT THE STORE AREA. (14E-1-110.12) | 3458 W LAKE ST | COMPLAINT | FAILED | View | |
REPAIR EXTERIOR WALL | EXTERIOR WALL BAY WINDOW LOOSE AND HANGING, RUSTED METAL SECTIONS. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINGUISHERS ALL MISSING AND OR OUTDATED TAGS. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
TENANT ACCESS TO SERVICE | TENANTS SHALL HAVE ACCESS TO THEIR PANELS AT ALL TIMES. PANELS FOR UNITS LOCATED IN STORE REAR AREA. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
PLASTIC TYPE EM LIGHTS AND EXIT SIGNS NOT APPROVED FOR USE. ONLY METAL TYPE EXIT SIGN AND EMERGENCY LIGHTS ARE APPROVED FOR USE. (14E-7-700.66C3) DANGEROUS AND HAZARDOUS CONDITION DUE TO NON-WORKING DEVICES. | 3458 W LAKE ST | COMPLAINT | FAILED | View | |
STAIRWELL ENCLOSURE - BASEMENT | INTERIOR EVIDENCE AT 1ST FLOOR CEILING UNDERSIDE OF STAIRS EXPOSED WOOD MISSING FIRE PROTECTION. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
INT WALL/CEILING CHIP PLASTER | 1ST FLOOR CEILING WATER DAMAGED. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE OPEN FRONT TOILET SEAT | ROUND TOILET WITH CLOSED FRONT SEAT AT EMPLOYEE BATHROOM. (18-29-420.3) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
FIRE EXTNGSHR REQ, RESDNTL | FIRE EXTINGUISHERS NOT INSTALLED, SITTING ON FLOOR IN CORNER. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
LISTED FOR USE TEMP & LOCATION | PROVIDE WEATHERPROOF BOXES, LIGHTS, FITTINGS AND APPROVED RACEWAY IN WALK-IN COOLER AREAS. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE A WATER MAIN GROUND CONDUIT, CONDUCTOR TO WITHIN 5 FT. OF WATER METER OR VALVE. (14E-2-250.68C1) | 3458 W LAKE ST | COMPLAINT | FAILED | View | |
PROVIDE | 1ST FLOOR CEILING EXPOSED JOIST MISSING SECTIONS OF PLASTER. COMPROMISED FIRE SEPARATION. (13-56-28) (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
ADD RECEPTACLES | ADD RECEPTACLES TO EASE EXTENSION CORD USE THROUGHOUT THE CEILING AREA AND STORE AREAS. (DANGEROUS AND HAZARDOUS CONDITION) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE | INTERIOR PLATFORM AT CASHIER UNKNOWN FIRE RATING. (15-8-570) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
THE LIGHT FIXTURES HAVE BEEN ALTERED WITH UNKNOWN PARTS AND WITHOUT PERMITS. (14E-1-110.3) | 3458 W LAKE ST | COMPLAINT | FAILED | View | |
SUBMIT PLANS FOR PLUMBING PRMT | SPECIFICALLY BATHROOM, KITCHEN AND MECHANICAL ROOM WASTE, DRAINAGE, VENT AND WATER PIPING WERE ALL CONSTRUCTED WITHOUT PLANS OR PERMITS. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | SUBMIT PLANS AND OBTAIN PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO 1ST FLOOR OR RESTORE THE BUILDING TO THE ORIGINAL STATE. INCLUDE ALL STRUCTURAL REPAIR IN PLANS AND PERMIT. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
CEILING SUPPORT WIRES AND CEILING GRIDS SHALL NOT BE USED FOR SUPPORT. THERE ARE CONDUIT, JUNCTION BOXES THROUGHOUT THE ABOVE DROP CEILING AREAS AND THROUGHOUT STORE AREA THAT ARE NOT PROPERLY SUPPORTED. THERE ARE LIGHT FIXTURES THROUGHOUT THE STORE AREA NOT PROPERLY SUPPORTED. (DANGEROUS AND HAZARDOUS CONDITION) (14E-3-300.11) | 3458 W LAKE ST | COMPLAINT | FAILED | View | |
OBSTRUCTIONS IN EXIT WAY | REAR EXIT OBSTRUCTED BLOCKED AND DOOR UNABLE TO OPEN DOOR. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
WORKING SPACE | PROVIDE PROPER CLEARANCES FOR ELECTRICAL PANEL AND DISCONNECTS OBSTRUCTED BY WALL AND DEBRIS. DANGEROUS AND HAZARDOUS CONDITION DUE TO NOT READILY ACCESSIBLE. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | MISSING WORKING CARBON MONOXIDE DETECTORS. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE THE REQUIRED DIAGRAM AND LOAD CALCULATIONS FOR FEEDERS, SERVICES AND REQUIRED EQUIPMENT. (14E-2-215.5, 14E-2-220.5) | 3458 W LAKE ST | COMPLAINT | FAILED | View | |
SUBMIT STRUCT. ENG. RPT (INT.) | STRUCTURE INTERIOR 1ST FLOOR CEILING JOIST OVER NOTCHED AND SECTION OF WALL REMOVED AND HANGING FROM CEILING. PROVIDE PLANS AND PERMIT FOR REPAIR WITH STRUCTURAL ENGINEER'S REPORT. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
INSTALL SMOKE DETECTORS | MISSING SMOKE DETECTORS. (DANGEROUS AND HAZARDOUS) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE VALVE,PIPING | 4" CAST IRON SANITARY PIPE AT EAST WALL NEXT TO MEAT COUNTER IS MISSING SUPPORT ON VERTICAL AND HORIZONTAL RUNS. PIPE IS LEANING AND AT RISK OF FALLING. (DANGEROUS AND HAZARDOUS) (18-29-102.3) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
OBTAIN ELECTRICAL PERMIT AND CONTRACTOR TO CORRECT VIOLATIONS. (13-12-360) | 3458 W LAKE ST | COMPLAINT | FAILED | View | |
PROPER MATRL WATER SUPPLY PIPE | UNAPPROVED FLEXIBLE WATER SUPPLIES TO ALL PLUMBING FIXTURES. (18-29-605) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
WORK NOT ALLOWED | EVIDENCE OF ALTERATIONS AT 1ST FLOOR STORE - WALLS REMOVED AND INSTALLED, ELEVATED PLATFORM INSTALLED, ELEVATED OFFICE INSTALLED, EXITS COMPROMISED. REMOVE ALL PARTITIONS AND FIXTURES INCLUDING PLUMBING AND ELECTRIC INSTALLED ON THE 1ST FLOOR WITHOUT A PERMIT. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
INSTALL COVERS | PROVIDE PROPER TYPE COVERS FOR OPEN WIRING AT LIGHT FIXTURES. (DANGEROUS AND HAZARDOUS CONDITION) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
ENGAG LIC & BOND PLMBNG CNTRC | ENGAGE LICENSED AND BONDED PLUMBING CONTRACTOR TO INSTALL PLUMBING. | 3458 W LAKE ST | COMPLAINT | FAILED | View |
PROVIDE | AISLES RESTRICTIONS THROUGHOUT: 26", 30", 33". ALL BELOW 36". (DANGEROUS AND HAZARDOUS) (15-4-880, 15-4-900) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
SPLICE IN CORD | REMOVE UNAPPROVED CORD SPLICE TO APPLIANCES IN KITCHEN AREA, AND COOLER AREAS. (DANGEROUS AND HAZARDOUS CONDITION) | 3458 W LAKE ST | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | 2ND 3RD AND REAR PORCH NO ENTRY | 3458 W LAKE ST | PERIODIC | FAILED | View |