Chicago Building Violations Data: 41 Violations
Violation Inspector Comments Address Category Status View
FILE BLDG REGISTRATION SR0702143800/REGISTER BUILDING FOR 2007 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REMV OBSTR FROM DRAINAGE SYSTM REMOVE OBSTRUCTION FROM PLUMBING SYSTEM CAUSING FREEZES BACK-UP OF SEWAGE INTO GROUND FLOOR FAMILY UNIT 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
CARPETING REPAIR /REPLACE WATER DAMAGED CARPETS IN UNIT 1A 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REPAIR/REPLACE SMOKE DETECTORS SMOKE DETECTOR IN UNIT 1A W/O BATTERY 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
DEFECTIVE FIXTURES REPAIR LIGHT FIXTURE IN KITCHEN OF UNIT 1A 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REPAIR PORCH SYSTEM REAR PORCH SYSTEM IS STRUCTURALLY UNSOUND SYSTEM SWAYS LATERALLY LEDGER BOARD SPANS OR 14 FEET WITH 5/8" DIAM BOLTS SPACED 21" OC INSIDE 4"X4" COLUMNS ARE SPLICED BUT NOT BOLTED OUTSIDE 6"X6" COLUMNS ARE BOTH SPLICED AND NOTCHED. COLUMNS ARE NOT CENTERED ON PLINTH BLOCKS PROVIDE PLAN AND OBTAIN PERMIT 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
FILE BLDG REGISTRATION SR-0702143800/ REGISTER BUILDING FOR 2007 4351 S CHAMPLAIN AVE COMPLAINT PASSED View
REMV OBSTR FROM DRAINAGE SYSTM REMOVE OBSTRUCTION FROM PLUMBING SYSTEM CAUSING FREEZES BACK-UP OF SEWAGE INTO GROUND FLOOR FAMILY UNIT 4351 S CHAMPLAIN AVE COMPLAINT PASSED View
CARPETING REPAIR/REPLACE WATER DAMAGED CARPETS IN UNIT 1A 4351 S CHAMPLAIN AVE COMPLAINT PASSED View
REPAIR/REPLACE SMOKE DETECTORS SMOKE DETECTOR IN UNIT 1A W/O BATTERY 4351 S CHAMPLAIN AVE COMPLAINT PASSED View
DEFECTIVE FIXTURES REPAIR LIGHT FIXTURE IN KITCHEN OF UNIT 1A 4351 S CHAMPLAIN AVE COMPLAINT PASSED View
REPAIR PORCH SYSTEM REAR PORCH SYSTEM IS STRUCTURALLY UNSOUND SYSTEM SWAYS LATERALLY LEDGER BOARD SPANS OR 14 FEET WITH 5/8" DIAM BOLTS SPACE 21" OC INSIDE 4"X 4" COLUMNS ARE SPLICED BUT NOT BOLTED OUTSIDE 6"X6" COLUMNS ARE BOTH SPLICED AND NOTCHED COLUMNS ARE NOT CENTERED ON PLINTH BLOCKS. PROVIDE PLAN AND OBTAIN PERMIT 4351 S CHAMPLAIN AVE COMPLAINT PASSED View
OBTN PERMIT FOR PLUMBING WORK PERMIT 18-29-106 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
LICENSED BONDED PLMBG CONTRCTR LISCNESED PLUMBER 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
STOP ODORS RPR DFT SEWAGE SYS CORRECT FLOODING CONDITION ON FIRST FLOOR UNITS AND PROVIDED PROPER MAIN CLEANOUT FOR GUTTER 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
SOIL/WASTE,VENT PIPE MATRL REMOVE PVC BELOW GROUND AND NEW CLEANOUT BELOW KITCHEN SINK AND FIRST FLOOR NORTH UNIT 18-29-702 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
EXPOSE FOR INSPECT APPROVAL FIRST FLR. KITCHEN FLOOR PVC UNDERGROUND INSTALLED WITHOUT PERMITS OR INSPECTIONS. 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
PROVIDE HOT WATER TO FIXTURES COMPLETE PREMISES 18-29-608 SIP DU BUILDING 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REPLACE DEFECTIVE WATER PIPING PROVIDE PROPER PRINCIPAL SNUGGLY PROPERLY AFTER WATER METER FOR ALL FIXTURES. 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
PRV WATER AT PLUMBING FIXTURE PROVIDED APPROVED BOOSTER PUMP SYSTEM AFTER WATER METER TO SUPPLY ALL FIXTURES AND EQUIPMENT 18-29-604 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REPAIR DEFECTIVE DOWNSPOUT NORTH SIDE OF BUILDING STANDING WATER 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
KEEP FIXTUR CLEAN AND SANITARY COMPLETE PREMISES 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REPLACE DEFECTIVE VALVE,PIPING PROVIDE EXPANSION TANKS @ ALL WATER HEATER 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REPLACE DEFECTIVE WASTE PIPING FIRST FLR. KITCHEN BELOW FLOOR REPLACE PVC WITH APPROVED MATERIALS CAST IRON. 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
INDIRECT CONN.FOR WATER SUPPLY REMOVE DOUBLE CHECK AND ISTALL RPZ ASSEMBLY ON LAWN SPRINKLERS 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REMV OBSTR FROM DRAINAGE SYSTM SR-0701835435 UNIT 1A (SOUTH UNIT) CONTINUE TO BACK SEWAGE INTO THIS APARTMENT (18-29-301.3)(18-29-102.3) 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
OBTAIN PERMIT FOR PLUMBING FOR INSTALLING FOUR INCH P.V.C. CLEAN OUT UNDER KITCHEN SINK. (18-29-106.1&2) 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
EXPOSE FOR INSPECT APPROVAL (18-29-312.1 THRU 8) EXPOSE JOINT UNDER KITCHEN SINK CLEAN OUT WHERE P.V.C. AND BELOW GRADE CONNECTION WAS APPLIED. (18-29-102.3) 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
ARRANGE PREMISE INSPECTION UNIT 1 SOUTH (1A) 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
TEST WATER DISTRIB SYSTEM TEST 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REPAIR INTERIOR WALLS/CEILING 1ST FLOOR MIDDLE BATHROOMS MOLD ON WALLS 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
STOP ODORS RPR DFT SEWAGE SYS 1ST FLOOR RAW SEWAGE BACKING UP FROM FLOOR DRAINS TOILET AND CLEAN OUT IN BATHROOM 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
POST OWNER/MANAGERS NAME/# POST ID 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
FILE BLDG REGISTRATION REGISTER BUILDING 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REPAIR PORCH SYSTEM REAR PORCH GRADE TO 3RD COLUMNS OVER NOTCHED NOT PROPERLY SPLICED AND BOLTED LEDGER BOLTED NOT PROPERLY BOLTED STRINGERS NOT PROPERLY ATTACHED FRONT RAILS DEFLECT UNDER LOAD RAILS NOT PROPERLY ANCHORED TO BUILDING STAIR SYSTEM SWAYS SIDE TO SIDE COLUMNS NOT SITTING PROPERLY ON FOOTING 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
PLANS & PERMITS REQ - CONTRCTR OBTAIN PLANS AND PERMIT FOR REPAIRS TO REAR PORCH 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
ARRANGE FOR REINSPECTION REGAR REINSPECTION 13-12-100 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REPAIR OR REPLACE 1ST FLOOR MIDDLE BEDROOMS HALLWAY CARPET MOLD GROWING RAW SEWAGE BACKED UP FROM FLOOR DRAINS ONTO CARPET 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
PRV CLEANOUT AT BASE OF STACK FIRST FLOOR UNIT NORTH FULL SIZED FLUSH CLEANOUT OF PROPER MATERIALS. 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
REMV OBSTR FROM DRAINAGE SYSTM ABATE REOCCURING FLOODS AND PERMISES 4351 S CHAMPLAIN AVE COMPLAINT FAILED View
TEST ALTERED SYSTEM TEST 4351 S CHAMPLAIN AVE COMPLAINT FAILED View