Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR EXTERIOR WALL | ROTTED SIDING FRONT-2ND LEVEL-BOTTOM, AT NORTH ELEVATION. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY TO CHECK SMOKE DETECTORS/COMPLAINT. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
RELOCATE SMOKE DETECTOR | FRONT & REAR STAIRWELL: NO SMOKE DETECTOR | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
PERMIT REQUIRED - CONTRACTOR | OBTAIN PERMIT TO REMOVE ATTIC UNIT | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | NO PLANS ON FILE FOR ATTIC UNIT | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | REAR AT GRADE, INTERIOR STAIRWELL: WALL MOLD | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE PLBG FIXTURE | 1ST, TUB: PEELING PAINT | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE TRAP | 1ST, KITCHEN SINK: TRAP LEAKING | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
SERVICE WALK, PASSAGE, AREAWAY | SERVICE WALK - FRACTURED UP HEAVED. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
REPAIR SCREENS | FRONT AND REAR, 1ST: TORN SCREEN | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
SERVICE WALK, PASSAGE, AREAWAY | NORTH WALK: BROKEN | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
INSTALL SMOKE DETECTORS | 1ST AND ATTIC: NO SMOKE DETECTOR | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
SUBMIT 2 COPY STRUCTURAL RPT | 1ST FLOOR DECK STRUCTURE / 1ST FLOOR DECK APPEARS TO BE WEAK AND IS SAGGING UP TO 4 INCHES OUT OF LEVEL. WOOD POST AND BEAM HAS BEEN PROPPED UP WITH NEWER 6X6 POSTS THAT HAS CONCRETE FOOTING WHICH IS POURED ON TOP OF EXISTING CONCRETE SLAB. 1 SUCH POST HAS BEEN NOTCHED OUT AROUND EXISTING PLUMBING PIPES. DECK JOIST HAS A LARGE CRACK. EAST ELEVATION / ENCLOSED PORCH / SOUTHEAST 6X6 COLUMN - ROTTING AND DETERIORATED. DECKING ON INTERIOR IS WEAK AND UNSTABLE AT THIS LOCATION. DECK APPEARS TO BE UP, TO 5 INCHES OUT OF LEVEL. UNDERSIDE OF ENCLOSED PORCH IS ENCLOSED WITH LATTICE AND WOOD, UNABLE TO VERIFY DEPTH OF FOOTINGS AT COLUMN LOCATIONS. CITY OF CHICAGO REQUIRES A DETAILED AND COMPREHENSIVE STRUCTURAL REPORT THAT ADDRESSES THE PROBLEM, ITS CAUSE AND POTENTIAL SOLUTIONS.SUBMIT ENGINEERING REPORT ON THE STABILITY OF 1ST FLOOR DECK STRUCTURE AND REAR ENCLOSED PORCH. | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
INSTALL SMOKE DETECTORS | FRONT INTERIOR STAIRWAY AND REAR ENCLOSED PORCH / SMOKE DETECTORS - MISSING. | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | BASEMENT / CARBON MNOXIDE DETECTOR - MISSING. | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | BASEMENT / CARBON MNOXIDE DETECTOR - MISSING. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
INSTALL SMOKE DETECTORS | FRONT INTERIOR STAIRWAY AND REAR ENCLOSED PORCH / SMOKE DETECTORS - MISSING. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
SUBMIT 2 COPY STRUCTURAL RPT | 1ST FLOOR DECK STRUCTURE / 1ST FLOOR DECK APPEARS TO BE WEAK AND IS SAGGING UP TO 4 INCHES OUT OF LEVEL. WOOD POST AND BEAM HAS BEEN PROPPED UP WITH NEWER 6X6 POSTS THAT HAS CONCRETE FOOTING WHICH IS POURED ON TOP OF EXISTING CONCRETE SLAB. 1 SUCH POST HAS BEEN NOTCHED OUT AROUND EXISTING PLUMBING PIPES. DECK JOIST HAS A LARGE CRACK. EAST ELEVATION / ENCLOSED PORCH / SOUTHEAST 6X6 COLUMN - ROTTING AND DETERIORATED. DECKING ON INTERIOR IS WEAK AND UNSTABLE AT THIS LOCATION. DECK APPEARS TO BE UP, TO 5 INCHES OUT OF LEVEL. UNDERSIDE OF ENCLOSED PORCH IS ENCLOSED WITH LATTICE AND WOOD, UNABLE TO VERIFY DEPTH OF FOOTINGS AT COLUMN LOCATIONS. CITY OF CHICAGO REQUIRES A DETAILED AND COMPREHENSIVE STRUCTURAL REPORT THAT ADDRESSES THE PROBLEM, ITS CAUSE AND POTENTIAL SOLUTIONS.SUBMIT ENGINEERING REPORT ON THE STABILITY OF 1ST FLOOR DECK STRUCTURE AND REAR ENCLOSED PORCH. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
REPAIR DOWNSPOUT | SOUTHEAST DOWNSPOUT - MISSING BOTTOM 5 FOOT SECTION. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
REPAIR PORCH SYSTEM | EAST ELEVATION / ENCLOSED PORCH / SOUTHEAST 6X6 COLUMN - ROTTING AND DETERIORATED. DECKING ON INTERIOR IS WEAK AND UNSTABLE AT THIS LOCATION. DECK APPEARS TO BE UP, TO 5 INCHES OUT OF LEVEL. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
REPAIR OR REPLACE | PER SECTION CODE : PROVIDE CAST IRON COVER FOR CATCH BASIN. (18-29-1003), (18-29-1003.4.1) REAR YARD / CATCH BASIN COVER - MISSING. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
REPAIR OR REPLACE | RUSTED GUTTER - FULL OF DEBRIS-NORTH-REAR (18.29.1101.2.1) | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | LOCK GATES - NORTH | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR | FRONT DOOR - BROKEN WINDOW LIGHT. | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
USE SANITARY REFUSE CONTAINERS | GARAGE - NOT IN CONTAINERS - REAR GARAGE AREA. | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
REPAIR / REBUILD SHED | GARAGE: BROKEN OVERHEAD DOOR, OPEN MORTAR JOINTS, MISSING PANES, PEELING PAINT | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
CUT OR REMOVE HIGH WEEDS | REAR: HIGH WEEDS | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
RATS | GARAGE: RAT HARBORING | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR | FRONT DOOR - BROKEN WINDOW LIGHT. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
USE SANITARY REFUSE CONTAINERS | GARAGE - NOT IN CONTAINERS - REAR GARAGE AREA. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
REPAIR OR REPLACE | RUSTED GUTTER - FULL OF DEBRIS-NORTH-REAR (18.29.1101.2.1) | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
RATS | RAT HARBORING REAR GARAGE | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
OBSTRUCTIONS IN EXIT WAY | LOCK GATES - NORTH | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
DEBRIS, EXCESSIVE | EXCESSIVE GARBAGE - GARAGE. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
REPAIR/REBUILD GARAGE OR SHED | GARAGE - BROKEN WINDOWS - OVERHEAD DOOR - OVERHEAD DOOR - COLLAPSED - OPEN JOINTS SERVICE DOOR BROKEN. | 8307 S MORGAN ST | COMPLAINT | CLOSED | View |
REPAIR DOWNSPOUT | SOUTHEAST DOWNSPOUT - MISSING BOTTOM 5 FOOT SECTION. | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
REPAIR PORCH SYSTEM | EAST ELEVATION / ENCLOSED PORCH / SOUTHEAST 6X6 COLUMN - ROTTING AND DETERIORATED. DECKING ON INTERIOR IS WEAK AND UNSTABLE AT THIS LOCATION. DECK APPEARS TO BE UP, TO 5 INCHES OUT OF LEVEL. | 8307 S MORGAN ST | COMPLAINT | FAILED | View |
REPAIR OR REPLACE | PER SECTION CODE : PROVIDE CAST IRON COVER FOR CATCH BASIN. (18-29-1003), (18-29-1003.4.1) REAR YARD / CATCH BASIN COVER - MISSING. | 8307 S MORGAN ST | COMPLAINT | FAILED | View |