Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
CLOSE BOX OPENINGS | CLOSE UNUSED OPENING IN ELECTRICAL BOX OR CABINET | 1713 E 75TH ST | COMPLAINT | FAILED | View |
SERVICE DROP OUT OF REACH | RELOCATE SERVICE DROPS OUT OF NORMAL REACH AT REAR OF BUILDING | 1713 E 75TH ST | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | REPLACE DEFECTIVE LIGHT FIXTURE IN WALKIN COOLER | 1713 E 75TH ST | COMPLAINT | FAILED | View |
DEFECTIVE LIGHTING SERVICE | ILLEGAL USE OF EMT IN SERVICE RUN, AND DISCONNECT NOT LOCATED WITHIN FIVE FEET OF ENTRY | 1713 E 75TH ST | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | PVC WASTE AND VENT BEHIND 3 COMPARTMENT SINK ON SOUTH WALL OF KITCHEN | 1713 E 75TH ST | COMPLAINT | FAILED | View |
REPAIR FLOOR | HOLE IN FLOOR FROM BEHIND COUNTER TO KITCHEN AREA | 1713 E 75TH ST | COMPLAINT | FAILED | View |
MULTIPLE CONDUCTOR TERM | IN PANEL TWO CONDUCTORS TERMINATED UNDER SINGLE BREAKER - 3X | 1713 E 75TH ST | COMPLAINT | FAILED | View |
INSTALL HOOD/DUCT FOR RANGE | HOOD FOR STOVE NOT FUNCTIONING PROPERLY BUSINESS FULL OF SMOKE | 1713 E 75TH ST | COMPLAINT | FAILED | View |
PROVIDE | NO FLOOR DRAIN FOR CONDENSATE WATER AT ICE MAKER FLOOR DRAIN MUST BE WITHIN 5 INCHES OF ICE MAKER 18-29-412.4 | 1713 E 75TH ST | COMPLAINT | FAILED | View |
LICENSED BONDED PLMBG CONTRCTR | LICENSED PLUMBER | 1713 E 75TH ST | COMPLAINT | FAILED | View |
CONTINUITY OF RACEWAY | LOOSE FITTINGS, MISSING FITTING AT SERVICE PANEL | 1713 E 75TH ST | COMPLAINT | FAILED | View |
INSTALL COVERS | INSTALL COVER TO OPEN PANEL | 1713 E 75TH ST | COMPLAINT | FAILED | View |
PROPER MATRL WATER SUPPLY PIPE | PLASTIC SUPPLY TO TOILET LAV MEN AND WOMEN RESTROOM. LAUNDRY TUB AND HAND SINK IN KITCHEN AREA AND BEHIND SERVICE COUNTER | 1713 E 75TH ST | COMPLAINT | FAILED | View |
REMOVE EXPOSED CABLE | ALL LIGHTS INSTALLED ABOVE DROP CEILING - ROMEX | 1713 E 75TH ST | COMPLAINT | FAILED | View |
ARMORED CABLE | EXPOSED RUNS AND RUN TERMINATED IN PANEL LACKS CONNECTOR | 1713 E 75TH ST | COMPLAINT | FAILED | View |
INTERIOR FINISH FIRERESISTANCE | PANELING ON WALLS AT FRONT AREA. | 1713 E 75TH ST | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | REPLACE ALL DEFECTIVE LIGHT FIXTURES ON INTERIOR OF STOREFRONTS AND EXTERIOR LIGHTS UNDER CANOPIES. ALL EXTERIOR FIXTURES MUST BE WEATHERPROOF | 1713 E 75TH ST | COMPLAINT | FAILED | View |
OBTN PERMIT FOR PLUMBING WORK | PERMITS FOR VIOLATION | 1713 E 75TH ST | COMPLAINT | FAILED | View |
PROVIDE OPEN FRONT TOILET SEAT | NO OPEN FRONT TOILET SEATS MEN AND WOMEN'S RESTROOM | 1713 E 75TH ST | COMPLAINT | FAILED | View |
STOP/REMOVE NUISANCE | PROPANE TANKS STORED NEAR TO GAS OPERATED COOK STOVE TO OPERATE OUTDOOR GRILL INSIDE | 1713 E 75TH ST | COMPLAINT | FAILED | View |
REPAIR BATTERY LIGHT | BATTERY EMERGENCY LIGHTING IS NOT WORKING | 1713 E 75TH ST | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | THROUGHOUT STORE | 1713 E 75TH ST | COMPLAINT | FAILED | View |
UNAPPROVED CORDS | REMOVE ALL UNAPPROVED CORDS THROUGH OUT SPACE | 1713 E 75TH ST | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | 2 SOUTH EXIT DOORS MORTAR WITH SIGNS, ONE GATED AND PADLOCKED OTHER SEALED SHUT | 1713 E 75TH ST | COMPLAINT | FAILED | View |
SYSTEM III | INSTALL EMERGENCY LIGHTING SYSTEM III. ALL EXITS AND BATTERY PACKS MUST BE CHICAGO APPROVED | 1713 E 75TH ST | COMPLAINT | FAILED | View |
CHIMNEY | LOOSE BRICKS AT SOUTH CHIMNEY | 1713 E 75TH ST | COMPLAINT | FAILED | View |
SERVICE DROP OUT OF REACH | REMOVE ROMEX FROM LIGHT FIXTURE ON EXTERIOR AT ENTRANCE DOOR AT FRONT OF BUILDING | 1713 E 75TH ST | COMPLAINT | FAILED | View |
RESTORE EXIT AND EM | EXIT SIGNS ARE NOT ILLUMINATED AND LACK BATTERY BACK-UP | 1713 E 75TH ST | COMPLAINT | FAILED | View |
PRV VALVE ON CW INLET TO HWHTR | NO CONTROL VALVE ON COLD WATER IN LET AT WATER HEATER | 1713 E 75TH ST | COMPLAINT | FAILED | View |
PROVIDE | LAV IN MEN'S ROOM TO CLOSE TO FRONT OF TOILET 18-29-405.3.1 | 1713 E 75TH ST | COMPLAINT | FAILED | View |
PROVIDE GUTTER & DOWNSPOUT | GUTTERS LEAK CAUSING MASONRY DAMAGE SOUTH WALL | 1713 E 75TH ST | COMPLAINT | FAILED | View |
SEC FEEDER/BRANCH | TERMINATED IN PANEL | 1713 E 75TH ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | OPEN MORTAR JOINTS NEAR TO GRADE WEST AND SOUTH. OPEN MORTAR JOINTS NEAR TO ROOF LINE SOUTH | 1713 E 75TH ST | COMPLAINT | FAILED | View |
18-22-210.8 INSTALL GFCI'S IN WET LOCATIONS | 1713 E 75TH ST | COMPLAINT | FAILED | View | |
DEFECTIVE METER EQUIPMENT | REPLACE VANDALIZED AND DEFECTIVE METER SOCKET AT REAR OF BUILDING | 1713 E 75TH ST | COMPLAINT | FAILED | View |
UNAPPROVED CORDS | SPLICE EXTERSION CORDS AND CORD WIRING ABOVE DROP CEILING | 1713 E 75TH ST | COMPLAINT | FAILED | View |