Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ARRANGE FOR INSPECTION | CONTACT INSPECTOR #655 AT 312-446-5316. | 819 S WESTERN AVE | PERIODIC | FAILED | View |
ACCESS TO ROOF | 819 S WESTERN AVE | PERIODIC | FAILED | View | |
RMV PLBFIX INSTALLD W/0 PERMIT | REMOVE PLUMBING FIXTURES INSTALLED WITHOUT PLANS AND PERMITS THROUGHOUT LOCATION | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | 14E-2-210.70 A1 | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
PROVIDE | HOT WATER TANK SAFE PAN PIED INTO FLOOR DRAIN LOCATED IN MECHANICAL ROOM | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
RESTORE EXIT AND EM | 819 S WESTERN AVE | COMPLAINT | FAILED | View | |
LICENSED BONDED PLMBG CONTRCTR | 819 S WESTERN AVE | COMPLAINT | FAILED | View | |
SUBMIT PLANS FOR PLUMBING PRMT | PLANS AND PERMITS FOR ALL PLUMBING INSTALLED IN COMMERICAL LOCATION | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
ADD RECEPTACLES | 819 S WESTERN AVE | COMPLAINT | FAILED | View | |
PROVIDE OPEN FRONT TOILET SEAT | NO OPEN FRONT TOILET SEAT INSTALLED IN MENS COMMERICAL BATHROOM | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
REMOVE | ABOVE GROUND DRAINAGE PIT WITH PUMP INSIDE MECHANICAL ROOM | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
NEED ELECTRICAL PERMIT TO CORRECT VIOLATIONS.14A-4-404.6 | 819 S WESTERN AVE | COMPLAINT | FAILED | View | |
INSTALL ILLUMINATION | LIGHT AND SWITCH JUST FOR SINK. | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE PLBG FIXTURE | HOT WATER TANK IN MECANICAL ROOM IS LEAKING AND RUSTED AT BOTTOM | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
INSTALL GFCI'S | 819 S WESTERN AVE | COMPLAINT | FAILED | View | |
PROVIDE | TEMPERATURE CONTROL VALVES FOR PLUBLIC LAVATORIES THROUGHOUT | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
PROVIDE A WATER MAIN GROUND CONDUCTOR IN CONDUIT WITHIN 5FT OF WATER MAIN. 14E-2-250.68 C1 | 819 S WESTERN AVE | COMPLAINT | FAILED | View | |
SEE INSPECTOR COMMENTS | NO BREAKER TIES 14E-2-240.15 B1 | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
CORD TO FIXTURE | 819 S WESTERN AVE | COMPLAINT | FAILED | View | |
OBTN PERMIT FOR PLUMBING WORK | 819 S WESTERN AVE | COMPLAINT | FAILED | View | |
REPAIR DOOR, INT. | ALL INTERIOR DOORS SHALL BE B LABEL DOORS, INCLUDING DOORS LEADING UNDER STAIRS. | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | EXPIRED FIRE EXTINGUISHER THROUGHOUT PROPERTY. | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
INTERIOR FINISH FIRERESISTANCE | INTERIOR FINISH UNDER STAIRS REQUIRED 1HOUR FIRE RESISTANT MATERIAL CURRENTLY 1/2" MATERIAL USED. | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
CLASS B DOOR IN STAIRWELL | CLASS B DOORS FOR STAIRWELLS. | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | SELF CLOSING DEVICES FOR ALL B LABEL DOORS. | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
HEATING PLANT SEPARATION | 1HR FIRE SEPERATION REQUIRED FOR HEATING PLANT/ MECHANICAL ROOM CURRENTLY MECHANICAL ROOM NOT FULLY FINISHED WITH 1HR FIRE RESISTANT MATERIAL . | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | MISSING SMOKE DETECTORS THROUGHOUT PROPERTY. | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN ASSEMBLY | MISSING CARBON MONOXIDE DETECTORS THROUGHOUT PROPERTY. | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
BLOWER SYSTEM DIRECTLY OUTSIDE | INSTALL PROPER VENTILATION FLUE PIPE FOR DRYER SYSTEM LOCATED WITHIN KITCHEN AREA. | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | PVC USED AT LAVATORY WASTE IN MENS BATHROOM | 819 S WESTERN AVE | COMPLAINT | FAILED | View |
INSTALL ILLUMINATION | 819 S WESTERN AVE | COMPLAINT | FAILED | View |