PIN: 20322220050000
Property Address: 8115 S GREEN ST
City - Zip: CHICAGO - 60620
2023 Property Class: 211
2023 Township: 72 - Lake
2023 Neighborhood: 72222
2023 Tax District: 72001
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 20 Violations
Violation Inspector Comments Address Category Status View
SEE INSPECTOR COMMENTS SEE NOTICE # 11593 8115 S GREEN ST PERMIT FAILED View
CONTINUITY OF RACEWAY PROPERLY SEAT ALL FITTING AND CONNECTORS IN ELECTRICAL PANELS, MISSING LOCKNUTS 8115 S GREEN ST COMPLAINT PASSED View
HEAT UNIT ADEQUATELY ROOM TEMP 65 DEGRESS AT TIME OF INSPECTION, HEATING SYSTEM ON AT TIME OF INSPECTION, INSUFFICIENT HEAT. 8115 S GREEN ST COMPLAINT FAILED View
SAFE WORKING CONDITIONS ONE OF FIVE RADIATORS OPERABLE THROUGH-OUT SECOND FLOOR APARTMENT. 8115 S GREEN ST COMPLAINT FAILED View
INSTALL SMOKE DETECTORS INTERIOR FRONT STAIRWAY MISSING SMOKE DETECTOR. 8115 S GREEN ST COMPLAINT FAILED View
DEFECTIVE LIGHTING SERVICE NO SPLICES ALLOWED ON SERVICE CONDUCTORS REMOVE JUNCTION BOX IN SERVICE RUN 8115 S GREEN ST COMPLAINT PASSED View
CIRCUIT ONE UNIT ONLY 8115 S GREEN ST COMPLAINT PASSED View
NO PERMIT WIRING NEW PANELS AND ASSOCIATED WIRING NO PERMITS 8115 S GREEN ST COMPLAINT PASSED View
DEFECTIVE FEEDER PANELS USED AS RACEWAY 8115 S GREEN ST COMPLAINT PASSED View
DEFECTIVE DISTRIBUTION BOND & GROUND ALL SERVICE DISCONNECTS 8115 S GREEN ST COMPLAINT PASSED View
PROPER SIZE OCP #14 WIRE ON 20 AMP BREAKER 8115 S GREEN ST COMPLAINT PASSED View
DEFECTIVE OUTLETS 2ND FLOOR MULTIPLE LOCATIONS, OPEN GROUND, HOT & NEUT REVERSED 8115 S GREEN ST COMPLAINT PASSED View
EXPOSED WIRING FIXTURES 2ND FLOOR CEILING FAN 8115 S GREEN ST COMPLAINT PASSED View
MULTIPLE CONDUCTOR TERM 2 CONDUCTORS TERMINATED UNDER SINGLE BREAKER 8115 S GREEN ST COMPLAINT PASSED View
SEE INSPECTOR COMMENTS PROVIDE GFCI PROTECTION KITCHENS, BATHS & UNFINISHED BASEMENT 18-27-570.8 8115 S GREEN ST COMPLAINT PASSED View
REMOVE************** REMOVE ALL ABANDONED ELECTRICAL PIPE, WIRE & APPARATUS 18-27-110.12 8115 S GREEN ST COMPLAINT PASSED View
EXPOSED WIRING REAR STAIRS & BASEMENT 8115 S GREEN ST COMPLAINT PASSED View
ARMORED CABLE REAR STAIRS & BASEMENT 8115 S GREEN ST COMPLAINT PASSED View
PROPER SIZE GRD ELECTRODE COND LOCATION AT WATER ENTRY 8115 S GREEN ST COMPLAINT PASSED View
PROVIDE ALL REQUIRED SMOKE & CO 2 DETECTORS 18-27-570.10 8115 S GREEN ST COMPLAINT PASSED View