Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SEE INSPECTOR COMMENTS | SEE NOTICE # 11593 | 8115 S GREEN ST | PERMIT | FAILED | View |
CONTINUITY OF RACEWAY | PROPERLY SEAT ALL FITTING AND CONNECTORS IN ELECTRICAL PANELS, MISSING LOCKNUTS | 8115 S GREEN ST | COMPLAINT | PASSED | View |
HEAT UNIT ADEQUATELY | ROOM TEMP 65 DEGRESS AT TIME OF INSPECTION, HEATING SYSTEM ON AT TIME OF INSPECTION, INSUFFICIENT HEAT. | 8115 S GREEN ST | COMPLAINT | FAILED | View |
SAFE WORKING CONDITIONS | ONE OF FIVE RADIATORS OPERABLE THROUGH-OUT SECOND FLOOR APARTMENT. | 8115 S GREEN ST | COMPLAINT | FAILED | View |
INSTALL SMOKE DETECTORS | INTERIOR FRONT STAIRWAY MISSING SMOKE DETECTOR. | 8115 S GREEN ST | COMPLAINT | FAILED | View |
DEFECTIVE LIGHTING SERVICE | NO SPLICES ALLOWED ON SERVICE CONDUCTORS REMOVE JUNCTION BOX IN SERVICE RUN | 8115 S GREEN ST | COMPLAINT | PASSED | View |
CIRCUIT ONE UNIT ONLY | 8115 S GREEN ST | COMPLAINT | PASSED | View | |
NO PERMIT WIRING | NEW PANELS AND ASSOCIATED WIRING NO PERMITS | 8115 S GREEN ST | COMPLAINT | PASSED | View |
DEFECTIVE FEEDER | PANELS USED AS RACEWAY | 8115 S GREEN ST | COMPLAINT | PASSED | View |
DEFECTIVE DISTRIBUTION | BOND & GROUND ALL SERVICE DISCONNECTS | 8115 S GREEN ST | COMPLAINT | PASSED | View |
PROPER SIZE OCP | #14 WIRE ON 20 AMP BREAKER | 8115 S GREEN ST | COMPLAINT | PASSED | View |
DEFECTIVE OUTLETS | 2ND FLOOR MULTIPLE LOCATIONS, OPEN GROUND, HOT & NEUT REVERSED | 8115 S GREEN ST | COMPLAINT | PASSED | View |
EXPOSED WIRING FIXTURES | 2ND FLOOR CEILING FAN | 8115 S GREEN ST | COMPLAINT | PASSED | View |
MULTIPLE CONDUCTOR TERM | 2 CONDUCTORS TERMINATED UNDER SINGLE BREAKER | 8115 S GREEN ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE GFCI PROTECTION KITCHENS, BATHS & UNFINISHED BASEMENT 18-27-570.8 | 8115 S GREEN ST | COMPLAINT | PASSED | View |
REMOVE************** | REMOVE ALL ABANDONED ELECTRICAL PIPE, WIRE & APPARATUS 18-27-110.12 | 8115 S GREEN ST | COMPLAINT | PASSED | View |
EXPOSED WIRING | REAR STAIRS & BASEMENT | 8115 S GREEN ST | COMPLAINT | PASSED | View |
ARMORED CABLE | REAR STAIRS & BASEMENT | 8115 S GREEN ST | COMPLAINT | PASSED | View |
PROPER SIZE GRD ELECTRODE COND | LOCATION AT WATER ENTRY | 8115 S GREEN ST | COMPLAINT | PASSED | View |
PROVIDE ALL REQUIRED SMOKE & CO 2 DETECTORS 18-27-570.10 | 8115 S GREEN ST | COMPLAINT | PASSED | View |