Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ARRANGE COMPLETED PERMIT INSP. | 1924 N DRAKE AVE | PERMIT | PASSED | View | |
SEE INSPECTOR COMMENTS | BOND GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO GROUNDED SERVICE CONDUCTOR.18-27-250.24 | 1924 N DRAKE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | GROUNDING ELECTRODE CONDUCTOR MUST BE SECURELY FASTENED TO THE COLD WATER PIPE AT SOURCE.18-27-250.64(B) | 1924 N DRAKE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | GROUNDING ELECTRODE MUST BE CONTINUOUS TO BOTH SIDES OF THE WATER METER AND SIZED PER 18-27-250.66.18-27-250.64(C) | 1924 N DRAKE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | INSTALL PROPER SIZE CIRCUIT BREAKER FOR #14 WIRE.18-27-110.10 | 1924 N DRAKE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | MAIN BONDING JUMPER SHALL BE MADE TIGHT.18-27-250.28 | 1924 N DRAKE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | INSTALL HARDWIRED SMOKE/CARBON DIOXIDE DETECTOR FOR PENTHOUSE.18-27-560.3 | 1924 N DRAKE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | INSTALL TWO 20 AMP DEDICATED COUNTERTOP CIRCUITS.18-27-210.11 | 1924 N DRAKE AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | ELECTRICAL CONTRACTOR MUST BE PRESENT FOR INSPECTION.13-12-170 | 1924 N DRAKE AVE | PERMIT | PASSED | View |