Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
PRV RECEIVER | 450#PSIG FOR THE FOLLOWING ONE 1 1/2 TON AND ONE 1 TON REMOTE REFRIGERATION UNITS THAT SERVES THE R.I.C./R.I.F.. THE UNITS ARE LOCATED ON THE SIDE OF THE BLDG. | 3700 W ADDISON ST | PERIODIC | FAILED | View |
SEE INSPECTOR COMMENTS | OBTAIN PERMIT BEFORE CAUSING OR COMMENCING THE ERECTION,INSTALLATION,ALTERATION,REPAIR,ENLARGEMENT OR RE-HANGING OF ANY SIGN,SIGN BOARD OR ATTACHMENT THERETO,PROJECTING APPROXIMATE 5 X 2' READS ELECTRONIC MESSAGE BOARD | 3700 W ADDISON ST | COMPLAINT | FAILED | View |
SERVICE BONDING BUSHINGS | NO MAIN BONDING JUMPER AS PER 18-27-250.92 &18-27-250.94 | 3700 W ADDISON ST | PERMIT | PASSED | View |
WATER METER BONDING JUMPERS | PROVIDE MAIN BONDING JUMPER AS PER 250.104 | 3700 W ADDISON ST | PERMIT | PASSED | View |
IMPROPER CONNECTIONS | REPLACE ALL DAMAGED WIRE TERMINATION ON ALL PANELS AS PER 18-27-110.14 | 3700 W ADDISON ST | PERMIT | PASSED | View |
COLOR CODE BRANCH CIRCUITS | PROVIDE PROPER COLOR CODE AT ALL PANELS AS PER 18-27-210.5 | 3700 W ADDISON ST | PERMIT | PASSED | View |
NONFERROUS METAL TAG | PROVIDE NON FERROUS MAETAL ATAG AS PER 18-27-25064 | 3700 W ADDISON ST | PERMIT | PASSED | View |
EQUIPMENT SHALL BE APPROVED | 2 POLE BREAKERS IN PANEL #4 LISTINGS HAVE BEEN VOIDED BY REMOVING BOLT ON BOLT ON FOOT AND NEUTRALS TIED TO 1 OF THE 2 POLES ON MULTIPLE BREAKERSEXTREMELY DANGEROUS AND HAZARDOUS | 3700 W ADDISON ST | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | REMOVE NEUTRALS FROM BREAKER PANEL #4 AS PER 18-27-110.32 AND 18-27-110.12(B) DANGEROUS AND HAZARDOUS | 3700 W ADDISON ST | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE ACCURATE AND DETAILED PANEL SCHEDULES AS PER 18-27-384.13 | 3700 W ADDISON ST | PERMIT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 3700 W ADDISON ST | PERMIT | PASSED | View | |
ARRANGE COMPLETED PERMIT INSP. | 3700 W ADDISON ST | PERMIT | PASSED | View | |
OBTAIN REFRIGERATION PERMIT | TWO AMERICAN STANDARD 12.5 TON RTU'S WITH 2 COMPRESORS EACH R410A | 3700 W ADDISON ST | PERIODIC | FAILED | View |
BOXES COVERED AND ACCESSIBLE | LB CONDUIT BODY NOT ACCESSIBLE AS PER 18-27-370.29 | 3700 W ADDISON ST | PERMIT | PASSED | View |
UNIT BATTERY RULES | PROVIDE REQUIRED UNIT BATTERIES AS PER 18-27-700.43 AND 18-27-700.66 | 3700 W ADDISON ST | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | EMT IS NOT ALLOWED FOR SUPPORT FOR CAMERAS AS PER 18-27-348.5(5) | 3700 W ADDISON ST | PERMIT | PASSED | View |
SIZE GEC | IMPROPER SIZED GEC AS PER 18-250.66 | 3700 W ADDISON ST | PERMIT | PASSED | View |