Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
CHIMNEY | REAR ELEVATION CHIMNEY FRACTURES ,WASHED OUT MORTAR ,LOOSE AND SPAULING BRICKS. | 3607 W FULLERTON AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY TO INTERIOR TO VERIFY DETECTORS AND 3 C APARTMENT TO ANSWERE THE COMPLAINT. | 3607 W FULLERTON AVE | COMPLAINT | FAILED | View |
ARRANGE ANNUAL INSP. | 3607 W FULLERTON AVE | COMPLAINT | FAILED | View | |
MAINTAIN MECH. VENT SYSTEM | 3607 W FULLERTON AVE | COMPLAINT | FAILED | View | |
OPEN TYPE VIOLATION | PROVIDE ADEQUATE HEAT | 3607 W FULLERTON AVE | COMPLAINT | FAILED | View |
PROVIDE | RE: A REFRIGERANT DETECTOR FOR THE MACHINERY ROOM, LOCATED ON THE SECOND FLOOR.(18-28-1105.5)RE: PROPER SIGNAGE FOR MACHINERY ROOM, AND THE HAND OPERATED EMERGENCY VALVE.(18-28-1101.5)RE: PROPER OPENING PROTECTIVES FOR MACHINERY ROOM. OPENING PROTECTION BETWEEN THE MACHINERY ROOM AND OTHER OCCUPIED SPACES SHALL BE APPROVED, SELF-CLOSING, TIGHT FITTING FIRE DOORS WITH A MINIMUM FIRE-RESISTANCE RATING OF 3/4 HOUR.(18-28-1106.4)RE: FOR MACHINERY ROOM. A CLEARLY IDENTIFIED SWITCH OF THE BREAK-GLASS-TYPE, THAT WILL PROVIDE ON-ONLY CONTROL OF THE MACHINERY ROOM VENTILATION FANS.(18-28-1106.10.2) | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
REPAIR OR REPLACE | RE: COPPER TUBING USED IN REFRIGERATING SYSTEMS SHALL BE BRAZED. SOLDER JOINTS AND MECHANICAL JOINTS SHALL NOT BE USED.(18-28-1107.4.4) | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
REMOVE | RE: ONE DOMESTIC HOT WATER HEATER, WITH OPEN FLAME. OPEN FLAMES THAT USE COMBUSTION AIR FROM THE MACHINERY ROOM SHALL NOT BE INSTALLED IN A MACHINERY ROOM.(18-28-1105.7) | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
CLUTTER AND DEBRI | RE: FOR MACHINERY ROOM LOCATED ON THE SECOND FLOOR, AND THE HAND OPERATED EMERGENCY VALVE LOCATED OUTSIDE OF THE MACHIERY ROOM. THE HAND OPERATED EMERGENCY VALVE SHALL BE READILY AVAILABLE FOR FIRE DEPARTMENT USE.(18-28-1106.12) | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
ARRANGE FOR RE-INSPECTION | RE: CONTACT INSPECTOR STEPHEN MCGANN #971 AT (312)446-5390 OR (312)743-3562. | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
PROVIDE | RE: A REFRIGERANT DETECTOR FOR THE MACHINERY ROOM, LOCATED ON THE SECOND FLOOR.(18-28-1105.5)RE: PROPER SIGNAGE FOR MACHINERY ROOM, AND THE HAND OPERATED EMERGENCY VALVE.(18-28-1101.5)RE: PROPER OPENING PROTECTIVES FOR MACHINERY ROOM. OPENING PROTECTION BETWEEN THE MACHINERY ROOM AND OTHER OCCUPIED SPACES SHALL BE APPROVED, SELF-CLOSING, TIGHT FITTING FIRE DOORS WITH A MINIMUM FIRE-RESISTANCE RATING OF 3/4 HOUR.(18-28-1106.4)RE: FOR MACHINERY ROOM. A CLEARLY IDENTIFIED SWITCH OF THE BREAK-GLASS-TYPE, THAT WILL PROVIDE ON-ONLY CONTROL OF THE MACHINERY ROOM VENTILATION FANS.(18-28-1106.10.2)ALSO PROVIDE PROPER SIGNAGE FOR ALL DOORS OF THE "MACHINERY ROOM". | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
REMOVE | RE: ONE DOMESTIC HOT WATER HEATER, WITH OPEN FLAME. OPEN FLAMES THAT USE COMBUSTION AIR FROM THE MACHINERY ROOM SHALL NOT BE INSTALLED IN A MACHINERY ROOM.(18-28-1105.7) | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
CLUTTER AND DEBRI | RE: FOR MACHINERY ROOM LOCATED ON THE SECOND FLOOR, AND THE HAND OPERATED EMERGENCY VALVE LOCATED OUTSIDE OF THE MACHIERY ROOM. THE HAND OPERATED EMERGENCY VALVE SHALL BE READILY AVAILABLE FOR FIRE DEPARTMENT USE.(18-28-1106.12) | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
ARRANGE FOR RE-INSPECTION | RE: CONTACT INSPECTOR STEPHEN MCGANN #971 AT (312)446-5390 OR (312)743-3562. | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
ARRANGE ANNUAL INSP. | ARRANGE FOR ANNUAL VENTILATION INSPECTION | 3607 W FULLERTON AVE | PERIODIC | PASSED | View |
MAINTAIN MECH. VENT SYSTEM | MAINTAIN EQUIPMENT ALL FRESH AIR (OA) DAMPERS SCREWED CLOSED ON RTU'S EXHAUST FANS NOT RUNNING | 3607 W FULLERTON AVE | PERIODIC | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | ARRANGE INSPECTION 18-28-106.1 | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
MAINTAIN MECH. VENT SYSTEM | MAINAIN EQUIPMENT 2 RTU'S NOT WORKING | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | (VT 8011) HEAT REQUIRED 68 DEGREE'S TEMP | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |
REPAIR OR REPLACE | RE: COPPER TUBING USED IN REFRIGERATING SYSTEMS SHALL BE BRAZED. SOLDER JOINTS AND MECHANICAL JOINTS SHALL NOT BE USED.(18-28-1107.4.4) | 3607 W FULLERTON AVE | PERIODIC | FAILED | View |