The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
FIRE EXTNGSHR REQ, RESDNTL | MISSING FIRE EXTINGUISHER THRU-OUT. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | ALL BATHROOM WALLS / CEILING WATER DAMAGED | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
REPAIR SKYLIGHT | SKYLIGHT CRACKED | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR FRAME | NORTHEAST EXTERIOR DOOR ROTTED FRAME | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
INT WALL/CEILING CHIP PLASTER | BODY SHOP AREA CEILING BROKEN PLASTER | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
DEFECTIVE BREAKER | BODY SHOP BREAKER BOX NO BLANKS COVER | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | ALL ELEVATION BROKEN & CRACK WINDOW PANES | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
RATS | RAT PROBLEMS | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
EXPOSED WIRING | BASEMENT OFFICE CEILING OPEN WIRES | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
SUPPLY HOT WTR MIN TEMP 120DEG | NO HOT WATER | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | THERE WAS ONLY 1 EXIT SIGN OBSERVED AT THIS ILLEGAL PPA VENUE AND IT WAS A PLASTIC SIGN (NOT MEATAL AS CODE REQUIRES). THERE IS NO DIRECTIONAL SIGNAGE AS WELL. DANGEROUS AND HAZARDOUS. SECTION 14X-5-505.6.2. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
REPAIR LINTELS | AT THE SOUTH ELEVATION THERE EXISTS A 10' WIDE STRUCTURAL LINTEL AT AN OVERHEAD GARAGE DOOR. THIS METAL LINTEL IS RUSTED, WARPED AND SAGGING. REPLACE WITH NEW. PLANS AND PERMIT REQUIRED. SECTION 14X-3-303.4. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
FIRE EXTNGSHR REQ, NONRESDNTL | THERE ARE NO FIRE EXTINGUISHERS IN THIS ILLEGAL EVENT SPACE WITH A DWELLING UNIT. SECTION 14X-5-504.5. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
FINES AND PENALTIES | THERE HAS BEEN EXTENSIVE WORK PERFORMED AT THIS PROPERTY WITHOUT PLANS OR PERMITS BY UNLICENSED PERSONELL. THIS WORK APPEARS TO BE UNFINISHED AND A STOP WORK ORDER HAS BEEN ISSUED. (13-12-050). | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | ALL OF THE PATHWAYS TO THE EXIT DOORS IN THIS ILLEGAL EVENT SPACE HAS EITHER FURNITURE OR STORED ITEMS OBSTRUCTING EGRESS. THERE IS A DOUBLE SET OF EXIT DOORS AT THE WEST WALL THE ARE INOPERABLE AN DO NOT OPEN. THERE IS AN EXIT DOOR ON THE EAST SIDE THAT LEADS TO AN ENCLOSED COURTYARD WITH NO ACCESS TO THE PUBLIC WAY. TO ACCESS THE REAR DOOR ONE HAS TO NAVIGATE A LARGE GARAGE SPACE FILLED WITH JUNK / DEBRIS / STORED ITEMS. ACCORDING TO THE CITY CODE, THIS ILLEGAL EVENT SPACE THAT HOSTS LARGE PPA TYPE PARTIES HAS ONLY 1 SEMI-VIABLE EXIT (WITH NO EXIT SIGN) AT THE FRONT (SOUTH) WALL. EXTREMELY DANGEROUS AND HAZARDOUS. SECTION 14X-5-505.1.2. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
INSTALL SMOKE DETECTORS | THERE ARE NO SMOKE DETECTORS IN THIS ILLEGAL EVENT SPACE WITH A DWELLING UNIT. DANGEROUS AND HAZARDOUS. SECTION 14X-5-504.5. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
WORKING ON STOP WORK ORDER | THERE HAS BEEN EXTENSIVE WORK PERFORMED AT THIS BUILDING WITHOUT ANY PLANS OR PERMITS. IT APPEARS AS THOUGH THERE IS UNFINISHED WORK WITH THE INTENT OF FINISHING THIS WORK. NO LICENSED PERSONELL PERFORMED ANY OF THIS WORK SO FAR, AS IS REQUIRED BY LAW. SHOW PROOF OF LICENSED CONTRACTORS AND STOP ALL WORK IMMEDIATELY UNTIL PLANS ARE SUBMITTED TO THIS DEPARTMENT AND A PERMIT(S) IS/ARE ISSUED. (13-12-129 AND 13-32-290). | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | THE FRONT (SOUTH) UPPER WALL OF THIS 1 STORY BRICK BUILDING IS SEVERELY DEGRADED IN THAT THE CENTER PORTION (20' WIDE X 12' HIGH) OF THIS EXTERIOR BRICK WALL IS BOWED BACK, POUT OF PLUMB, OVER THE ROOF AREA. THE EXTREME STRESS CAUSED BY THIS UNCENTERED, OUT OF PLUMB, LARGE WEIGHT HAS CAUSED MULTIPLE STRESS FRACTURES IN THE BRICK WORK. THESE STRESS CRACKS ARE VISABLE IN THE BRICK COLUMNS DESIGNED TO SUPPORT THIS AREA OF THIS WALL. THIS DEGRADED WALL IS OVER THE PUBLIC WAY. THIS WAREHOUSE BUILDING IS ON A BLOCK OF RESIDENTIAL HOMES. PLANS AND A PERMIT ARE REQUIRED TO REBUILD THIS SECTION OF EXTERIOR WALL. DANGEROUS AND HAZARDOUS. SECTION 14X-3-303.1. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | THIS BUILDING IS AN INDUSTRIAL MANUFACTURING FACILITY / WAREHOUSE AND IS ZONED AS SUCH (M-1). THE ONGOING MISUSAGE OF THIS BUILDING INVOLVES LARGE RAVE PARTIES WITH EITHER CASH COVER CHARGE OR ONLINE TICKET SALES. THERE IS A FULLY STOCKED BAR HERE SERVING ALCOHOL TO ATTENDEES. THERE WERE APPROXIMATELY 100 PAID ATTENDEES AT THE TIME OF THIS INSPECTION. ALSO, THIS WAREHOUSE IS BEING USED AS AN OCCUPIED DWELLING UNIT. THERE ARE 2 BEDROOMS AND A FULL KITCHEN WITH A BATHROOM. THERE HAS BEEN A CONSIDERABLE AMOUNT OF WORK PERFORMED HERE WITHOUT PLANS OR PERMITS THAT INCLUDES ADDING PARTITION WALLS FORMING ROOMS AS WELL AS PLUMBING AND ELECTRICAL PIPING / FIXTURE INSTALLATION. A LARGE LOFTED AREA HAS BEEN CONSTRUCTED AS WELL WITHOUT PLANS / PERMITS.THERE ARE NO RECORDS, PLANS OR PERMITS ON FILE FOR THE PPA ACTIVITY NOR ARE THERE ANY APPLICATIONS ON FILE FOR ANY TYPE OF BUSINESS LISENCES. A CLOSURE HAS BEEN ISSUED BY THE DEPARTMENT OF BUILDINGS AND BACP.SECTION 14A-4-401.1. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
RESTORE ROOF LIVE LOADTO ORIG | THIS IS A TRUSS ROOF BUILDING. THERE ARE 2 HEAVY GAS FIRED HEATERS FASTENED TO THE BOTTOM CORD OF THE STRUCTURAL ROOF TRUSSES. THIS IS NOT ALLOWED. THESE TRUSSES SERVE ONE PURPOSE: TO SUPPORT THE TOTAL LOAD OF THE ROOF. ANY ADDITIONAL LOADS IS NOT IN THE DESIGN OF THESE CRITICAL STRUCTURAL MEMBERS AND MUST BE REMOVED. DANGEROUS AND HAZARDOUS. SECTION 14A-8-803.3. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN ASSEMBLY | THERE ARE NO CARBON MONOXIDE DETECTORS IN THIS ILLEGAL EVENT SPACE WITH DWELLING UNIT. DANGEROUS AND HAZARDOUS. SECTION 14X-5-504.9. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
III-B AND IV-A FIRE RESISTANCE | IF ZONING APPROVAL IS OBTAINED AND THE PROPER PERMITS ARE ISSUED, THEN THE EXISTING (PLYWOOD) PARTITION WALLS ARE TO BE UPGRADED WITH THE APPROPRIATE FIRE RESISTIVE MATERIAL. THE EXISTING PLYWOOD PARTITION WALLS ARE TO BE CONSIDERED DANGEROUS AND HAZARDOUS. (15-8-260 C). | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
ILLUMINATE PUBLIC STAIR/HALL | THIS IS AN INDUSTRIAL BUILDING BEING MISUSED AS A PPA EVENT SPACE AND A DWELLING UNIT. THERE IS NO DEDICATED EXIT ILLUMUNATION ANYWHERE AT THIS PROPERTY. THERE ARE AREAS WHERE IT IS SO POORLY ILLUMINATED THAT FINDING AN EXIT DOOR IS EXTREMELY DIFFICULT. DANGEROUS AND HAZARDOUS. SECTION 14X-5-506.6.1. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
REGISTRATION FOR BLDG WORK | THERE HAS BEEN EXTENSIVE WORK PERFORMED AT THIS BUILDING WITHOUT ANY PLANS OR PERMITS. NO LICENSED PERSONELL PERFORMED ANY OF THIS WORK AS IS REQUIRED BY LAW. SHOW PROOF OF LICENSED CONTRACTORS. (13-28-010). | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
SUBMIT 2 COPY STRUCTURAL RPT | THIS REPORT IS TO EXAMINE THE ENTIRE SOUTH ELEVATION BRICK WALL.SECTION 14X-1-104.1. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
WORK NOT ALLOWED | IF A ZONING VARIANCE IS NOT OBTAINED TO ALLOW FOR A DWELLING UNIT WITH 2 (LOFTED) BEDROOMS, A KITCHEN AND A BATHROOM AS WELL AS THE OPERATION OF A PPA EVENT SPACE, THEN ALL WORK PERFORMED WITHOUT PERMITS IS TO BE COMPLETELY REMOVED AND THIS BUILDING IS TO BE RESTORED TO THE ORIGINAL CONDITION PRIOR TO THIS EXTENSIVE, UN-PERMITTED WORK. SECTION 14A-4-401. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
EXPOSED WIRING | THIS INDUSTRIAL WAREHOUSE HAS BEEN ALTERED INTO AN ONGOING ILLEGAL PPA EVENT SPACE WITH AN APARTMENT INSTALLED. ALL OF THE ELECTRICAL WORK IS ONGOING AND HAS BEEN PERFORMED, WITHOUT PERMIT, BY NON-LICENSED INDIVIDUALS. AS A RESULT OF THIS UNPROFESSIONAL WORKMANSHIP, THERE IS EXPOSED (LIVE) ELECTRICAL WIRING THROUGHOUT THIS BUILDING. THIS IS TO BE CONSIDERATE EXTREMELY DANGEROUS AND HAZARDOUS. SECTION 14X-7-703/705. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |
INSTALL EXIT SIGN | THERE IS NO EMERGENCY LIGHTING SYSTEM IN PLACE AT THIS ILLEGALLY OPERATED EVENT SPACE. DANGEROUS AND HAZARDOUS. SECTION 17X-5-505.6.2. | 4516 W THOMAS ST | COMPLAINT | FAILED | View |