Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
MAINTAIN OR REPAIR ELECT ELEVA | WORKING DOOR RESTRICTOR REQUIRED. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WORKING ACCESS AND INSPECTION REQUIRED. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CLEAR DEBRIS BLOCKING ACCESS TO BASEMENT LANDING. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
RMV WATER,SOIL,WASTE,VENT | 1, CONTRACTOR OF RECORD DID NOT INSTALL PLUMBING IN COMMERICAL AREA BATHROOMS ON SECOND FLOOR | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
ENGAG LIC & BOND PLMBNG CNTRC | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View | |
ARRANGE FOR REINSPECTION REGAR | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View | |
SEE INSPECTOR COMMENTS | SEE NOTICE # 11489 | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | 6411 N ROCKWELL ST | PERMIT | PASSED | View | |
OPEN | 6411 N ROCKWELL ST | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | KEY TO UNLOCK LANDING DOORS REQUIRED IN FIREMANS KEY BOX. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | WORKING CARTOP INSPECTION REQUIRED. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE TEST WEIGHTS FROM CARTOP. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WORKING TWO WAY COMMUNICATION REQUIRED WITH ONLY 1 PHONE BUTTON-NOT 2. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ABC RATED FIRE EXTINGUISHER REQUIRED IN MACHINE ROOM. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CERTIFICATE FRAME REQUIRED IN ELEVATOR CAB. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE CAR CALLS FOR NON EXISTANT LANDINGS. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CLEAN CARTOP AND MACHINE ROOM. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIRE SERVICE MUST MEET CURRENT CODE (CHECK DOOR OPERATION, CALL CANCEL) | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | DOOR UNLOCKING DEVICE MUST WORK AT ALL LANDINGS. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WORKING TOP EMERGENCY EXIT REQUIRED (NO LESS THAN 16" ON EACH SIDE) | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CALL CANCEL BUTTON REQUIRED. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CARTOP HAND RAILS REQUIRED. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE STANDING WATER IN PIT AND REPAIR SUMP PUMP. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
ARRANGE FOR INSPECTION | CALL 312-743-3562 ASK FOR INSPECTOR #653 RICH HASTINGS ,WEDNESDAYS BETWEEN 8:00 AND 9:00 AM. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
ACCESS TO ROOF | ROOF AND ALL CONDENSING UNITS. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIRE CAULK ALL HOISTWAY PENETRATIONS. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COMPLETE CAB INTERIORS (FINISHED FLOORS REQ'D) | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COMPLETE 1ST FLOOR ENTRANCE. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | KEEP ELEVATOR PITS CLEAN AND DRY. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ACCESS TO ELEVATOR MACHINE ROOM REQUIRED TO COMPLETE THIS INSPECTION. CALL 312.743.3594 TO SCHEDULE. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | "IN CASE OF FIRE" PICTOGRAPHS REQUIRED AT ALL LANDINGS. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR OR REPLACE DAMAGED SMOKE DETECTOR AT BASEMENT LANDING. TEST SAME. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CORRECT MALFUNCTIONING FIRE SERVICE I.E. ELEVATOR 3 LANDS AT BASEMENT LANDING INSTEAD OF DESIGNATED FLOOR. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PREPERLY SECURE CANOPY ACCESS PANEL (ESCAPE HATCH). | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATORS #3 AND #4: SCHEDULE FINAL INSPECTION WITH BUILDING DEPARTMENT AND SCHINDLER ELEVATOR TO FINAL INSTALLATION PERMIT # 100648314.(PREVIOUSLY CITED) | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR AND MAINTAIN ELEVATOR #2. ELEVATOR IS OUT OF SERVICE AT TIME OF INSPECTION AND NO WORK IS BEING PERFORMED. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ALL ELEVATORS: IDENTIFY ELEVATORS AT ALL LANDING DOOR FRAMES. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ALL ELEVATORS: MACHINE ROOM ACCESS IS REQUIRED TO COMPLETE THIS INSPECTION. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATOR #3: REPAIR TWO WAY COMMUNICATION (PHONE). | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATOR 4: CERTIFICATE FRAME REQUIRED IN ELEVATOR CAB. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST AUTOMATIC FIRE RECALL. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CORRECT PROBLEM OF STANDING WATER IN ELEVATOR PIT. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIRE SERVICE KEY SWITCHES MUST BE IDENTIFIED AS SUCH. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIRE SERVICE JEWEL MUST BE ILLUMINATED. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CORRECT FLASHING HAT FEATURE AND RETEST AUTO FIRE RECALL. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATOR #2: A)REPAIR MALFUNCTIONING FIRE SERVICE. B)REPAIR MALFUNCTIONING TWO WAY COMMUNICATION(PHONE). C)REPAIR OR REPLACE EXPOSED CAB INTERIOR LIGHTING AND BROKEN FIXTURES. D)REPLACE MISSING THIRD FLOOR HALL CALL FIXTURE. E)CLEAN ELEVATOR PI | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CLEAN ELEVATOR MACHINE ROOM. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST FIRE SERVICE RECALL CARS #3 & 4 | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
RESTORE EXIT AND EM | THROUGHOUT 6TH FLR AND STAIRWELLS, SPECIFICALLY | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PRINTS AND PERMIT REQUIRED ON JOBSITE. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BRAILL TAGS AND ELEVATOR IDENTIFICATION REQUIRED AT ALL LANDINGS. | 6411 N ROCKWELL ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR CAB INTERIOR LIGHTING. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE MORE MACHINE ROOM LIGHTING. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY INTERIOR. UNABLE TO VERIFY DETECTORS AND INTERIOR CONDITIONS. UNABLE TO INVESTIGATE COMPLAINTS OF WATER PRESSURE AND WATER INFILTRATION FROM BALCONIES. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ILLUMINATION REQUIRED AT ALL LANDINGS(NO LIGHTS IN HALLWAYS). | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATOR #1: OBTAIN REQUIRED PERMIT FROM A LICENSED ELEVATOR CONTRACTOR TO COMPLETE INSTALLATION OF THIS DEVICE.ELEVATOR IS CURRENTLY OUT OF SERVICE IN A DANGEROUS AND HAZARDOUS CONDITION. ALL WORK TO MEET APPLICABLE CHICAGO BUILDING CODES. (A17.1-02007). | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATOR #2: A)REPAIR MALFUNCTIONING FIRE SERVICE. B)REPAIR MALFUNCTIONING TWO WAY COMMUNICATION(PHONE). C)REPAIR OR REPLACE EXPOSED CAB INTERIOR LIGHTING AND BROKEN FIXTURES. D)REPLACE MISSING THIRD FLOOR HALL CALL FIXTURE. E)CLEAN ELEVATOR PIT. F)PROVIDE DOOR UNLOCKING TOOL ON JOBSITE IN FIREMANS SERVICE KEY BOX. G)MACHINE ROOM ACCESS REQUIRED TO COMPLETE THIS INSPECTION. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATORS #3 AND #4: SCHEDULE FINAL INSPECTION WITH BUILDING DEPARTMENT AND SCHINDLER ELEVATOR TO FINAL INSTALLATION PERMIT # 100648314. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATOR #1: OBTAIN REQUIRED PERMIT FROM A LICENSED ELEVATOR CONTRACTOR TO COMPLETE INSTALLATION OF THIS DEVICE.ELEVATOR IS CURRENTLY OUT OF SERVICE IN A DANGEROUS AND HAZARDOUS CONDITION. ALL WORK TO MEET APPLICABLE CHICAGO BUILDING CODES. (A1 | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING CAR 1: OBTAIN A PERMIT AND PROPERLY DECOMMISSION ELEVATOR. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING CAR 2: MAKE NECESSARY REPAIRS REQUIRED TO COMPLETE WORK DONE UNDER PERMIT #100861542 ISSUED ON 2/5/20 TO ALL TYPES ELEVATOR. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPLACE MISSING CAR IDENTIFICATION TAGS AND 'IN CASE OF FIRE' PICTOGRAPHS. CHECK ALL LANDINGS FOR CARS 3 AND 4. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WORKING TWO WAY COMMUNICATION (PHONE) REQUIRED IN ALL ELEVATOR CABS. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSPECTION PROMPTED BY 311 REQUEST. FOUND ONLY 1 OF 4 ELEVATORS IN SERVICE.NO BUILDING PERSONNEL OR MANAGEMENT AVAILABLE. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COMPLETE WORK REQUIRED TO FINAL PERMIT # 101039328 ISSUED TO SUBURBAN ELEVATOR. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COMPLETE WORK REQUIRED TO FINAL PERMIT # 100861542 ISSUED TO ALL TYPES ELEVATOR. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
OCCUPIED WITHOUT REQ'D C OF O | FAILURE TO OBTAIN CERTIFICATE OF ACCUPANCY BEFORE OCCUPYING BUILDING UNDER PERMIT#100160422, ISSUED:1.31.07 AND REINSTATED AS OF 8.5.13.SECTION 13-36-010 THRU 13-36-070 TO APPLY FOR CERTIFICATE OF ACCUPANCY.UNITS ALL OCCUPIED. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
BLANK-TEXT MUST CITE CODE SECT | CONSTRUCTION WORK FOR COMPLETION/CORRECTION REQUIRES A LICENCE PER SECTION 13-12-050, 4-36-110B.FAILED TO OBTAIN CERTIFICATE OF OCCUPANCY | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LABEL DISCONNECT SWITCHES WITH CAR#, VOLTAGE, SOURCE , AND USE. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
NO PLANS/PERMIT AT JOBSITE | PROVIDE APPROVED PLANS AND PERMIT ON SITE FOR ALL CERTIFICATE OF ACCUPANCY INSPECTIONS. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATOR #1: OBTAIN REQUIRED PERMIT FROM A LICENSED ELEVATOR CONTRACTOR TO COMPLETE INSTALLATION OF THIS DEVICE.ELEVATOR IS CURRENTLY OUT OF SERVICE IN A DANGEROUS AND HAZARDOUS CONDITION. ALL WORK TO MEET APPLICABLE CHICAGO BUILDING CODES. (A17.1-02007).(PREVIOUSLY CITED). | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING ELEVATOR #2: A)REPAIR MALFUNCTIONING FIRE SERVICE. B)REPAIR MALFUNCTIONING TWO WAY COMMUNICATION(PHONE). C)REPAIR OR REPLACE EXPOSED CAB INTERIOR LIGHTING AND BROKEN FIXTURES. D)REPLACE MISSING THIRD FLOOR HALL CALL FIXTURE. E)CLEAN ELEVATOR PIT. F)PROVIDE DOOR UNLOCKING TOOL ON JOBSITE IN FIREMANS SERVICE KEY BOX. G)MACHINE ROOM ACCESS REQUIRED TO COMPLETE THIS INSPECTION.(PREVIOUSLY CITED). | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SCHEDULE FINAL INSPECTION WITH THE ELEVATOR BUREAU TO CLOSE PERMIT #100648314. WORK TO PUNCH LIST PREVIOUSLY PROVIDED. | 6411 N ROCKWELL ST | COMPLAINT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WIRE CONTROLLER IN A PROFESSIONAL, WORKMANLIKE MANNER. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SMOKE DETECTOR REQUIRED IN OVERHEAD MACHINERY SPACE. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SHOW TAG AND DOCUMENT FOR LAST CATEGORY 5 TEST OR PERFORM NEW TEST. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SECURE TOP HOISTWAY ACCESS KEY SWITCH. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SECURE CANOPY ACCESS PANEL. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE A CURRENT FIRE SERVICE MONTHLY TEST LOG AND MAINTENANCE CONTROL PROGRAM ON SITE. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LOCK MANUAL BRAKE RELEASE LEVER LOCATED IN MACHINE ROOM. | 6411 N ROCKWELL ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATORS 3 AND 4: CATEGORY 5 TESTS OVERDUE. TAG AND DOCUMENT AS REQUIRED. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR AND MAINTAIN ELEVATOR 4 - OUT OF SERVICE FOR OVER 2 MONTHS. | 6411 N ROCKWELL ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR HARDWARE | EXTERIOR DOOR AT ROOF - MISSING LOCK; NOT CLOSING OR LATCHING PROPERLY. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
CLASS B DOOR IN STAIRWELL | INTERIOR STAIRWELL DOORS - NOT CLOSING OR LATCHING PROPERLY AT MULTIPLE LOCATIONS ESPECIALLY STAIRWELL DOOR AT 5B. INTERIOR STAIRWELL DOORS AT 2ND THROUGH 4TH FLOORS - OPEN AND UNSECURED ALLOWING ACCESS TO VACANT FLOORS. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | INTERIOR CORRIDORS /WALLS AND CEILINGS - WATER DAMAGED SECTIONS WITH CRACKED PLASTER AT MULTIPLE LOCATIONS; HUMAN FECES SMEARED ON WALL AT MULTIPLE LOCATIONS. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
ILLUMINATE PUBLIC STAIR/HALL | INTERIOR CORRIDORS AND STAIRWELLS /EMERGENCY LIGHTING - NOT WORKING WHEN TESTED AT MULTIPLE LOCATIONS. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINGUISHERS - RECHARGE TAGS EXPIRED AT 5TH FLOOR; EXTINGUISHERS MISSING THROUGHOUT 6TH FLOOR. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
REPAIR LINTELS | WEST ELEVATION /WINDOW LINTELS - RUSTED AT MULTIPLE LOCATIONS. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | INTERIOR STAIRWELLS - HOUSEHOLD ITEMS OBSTRUCTING PATH OF EGRESS AT MULTIPLE LOCATIONS. | 6411 N ROCKWELL ST | COMPLAINT | FAILED | View |