The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SUBMIT 2 COPY MAINTENANCE RPT | FILE REPORTS REQUIRED BY EXTERIOR WALL ORDINANCE.LAST REPORT WAS 2002 CRITICAL EXAM.SHORT FORM DUE NO LATER THAN 11/1/2004 HAS NOT BEEN FILED AS OF 2/23/2006 | 1401 E HYDE PARK BLVD | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL REPAIR-(1) NORTH ELEVATION ALONG FRONT ENTRANCE OPEN STONE POCKETS, WASHED OUT MORTAR, STONE PIECES CRACKED, OLD PREVIOUS CANOPY STEEL CONNECTIONS EMBEDDED RUSTING CAUSING DAMAGE TO SURROUND STONE (2) NORTHWEST CORNER WASHED OUT MORTAR (3) STONE BAND ON WEST ELEVATION 7TH FLOOR WASHED OUT MORTAR SEVERE, MINOR CRACKING (4) GRADE LEVEL ON WEST ELEVATION SEVERE OUT MORTAR, STONE CRACKING (5) STONE ON NORTH ELEVATION NEAR NORTHWEST CORNER SEVERE WASHED OUT MORTAR (6) PERMITS REQUIRED FOR REPAIRS | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
TEST G & S PASS ELE | SOUTH CAR. EV002815. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
OBSTRUCTIONS IN EXIT WAY | SOUTH ELEVATION FIRE ESCAPE EXIT DISCHARGE - COUNTER WEIGHT STAIRS - TRASH CONTAINERS BELOW PROHIBIT THE EMERGENCY LOWERING | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
ARRANGE FOR REINSPECTION REGAR | NO ENTRY INTO STAIRWELLS, APARTMENTS, GROUND FLOOR COMMON SPACES OR BASEMENT TO VERIFY EGRESS, EXIT SIGNS, FIRE EXTINGUISHERS, CARBON MONOXIDE DETECTORS, SMOKE DETECTORS, INTERIOR STRUCTURAL, COSMETIC OR ENVIRONMENTAL CONDITIONS | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL REPAIR-(1) NORTH ELEVATION ALONG FRONT ENTRANCE OPEN STONE POCKETS, WASHED OUT MORTAR, STONE PIECES CRACKED, OLD PREVIOUS CANOPY STEEL CONNECTIONS EMBEDDED RUSTING CAUSING DAMAGE TO SURROUND STONE (2) NORTHWEST CORNER WASHED OUT MORTAR (3) STONE BAND ON WEST ELEVATION 7TH FLOOR WASHED OUT MORTAR SEVERE, MINOR CRACKING (4) GRADE LEVEL ON WEST ELEVATION SEVERE OUT MORTAR, STONE CRACKING (5) STONE ON NORTH ELEVATION NEAR NORTHWEST CORNER SEVERE WASHED OUT MORTAR (6) PERMITS REQUIRED FOR REPAIRS | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | MANAGEMENT NOT ON SITE AT TIME OF INSPECTION; NO ENTRY. UNABLE TO INSPECT INTERIOR, STAIRWELLS, APARTMENTS, BASEMENT, AND REAR STAIR SYSTEM. UNVERIFIED DETECTORS AND OCCUPANCY. | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | NOT REGISTERED 2012 | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | MANAGEMENT NOT ON SITE AT TIME OF INSPECTION; NO ENTRY. UNABLE TO INSPECT INTERIOR, STAIRWELLS, APARTMENTS, BASEMENT, AND REAR STAIR SYSTEM. UNVERIFIED DETECTORS AND OCCUPANCY. | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | BLDG. - NOT REGISTERED FOR 2014. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
I-A I-B I-C AND II FIRE RESIST | FREIGHT ELEVATOR MACHINE ROOM: WALLS COVERED WITH CARDBOARDS; WOOD BOARDS ON FLOOR; ELEVATOR CONTROL CANINET MOUNTED ON WOODEN PLATFORM. REMOVE ALL COMBUSTIBLE MATERIALS AND STRUCTURES IN MECHANICAL ROOM. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
PIPE OPENING W/NONCOMBUST MATL | FREIGHT ELEVATOR MACHINE ROOM - PIPE HOLES AROUND THE RADIATOR. ELEVATOR DOOR - HOLES AROUND THE FRAME, WITH LOOSE AND MISSING MORTAR. PASSENGER ELEVATOR MACHINE ROOM - HOLES ON WALLS. ALL FLOORS: FIRE HORSE, JANITOR / SINK AND ELECTRIC CLOSETS - STAND-PIPES AND CABLE PENETRATIONS FILLED WITH SPRAY FOAMS. ALL FLOORS: TRASH CHUTE SEALED WITH GLUE AROUND THE WALL. 2ND FLOOR / ELECTRIC CLOSET - OPEN 1-INCH DIAMETER PIPE TO BE CAPPED AND SEALED. 1ST FLOOR STAIRWELL - OPEN PIPE PENETRATION. TRASH ROOM, WATER METER ROOM, LAUNDRY ROOM (INSIDE DROP-DOWN CEILING) AND BOILER ROOM - PIPE PENETRATIONS SEALED WITH SPRAY FOAMS. BOILER ROOM, ENTRY DOOR FRAME TO LOBBY - HOLES AROUND THE EDGES. REMOVE ALL EXPANDABLE SPRAY FOAMS, AND SEAL ALL OPENINGS WITH PROPER FIRE-STOPPING MATERIALS SUCH AS FIRE CAULK, WITH MINERAL WOOL BACK-UP. SUBMIT DOCUMENTATION THAT FIRE-STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARD. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
SELF-CLOSE CLASS B FIRE DOOR | PENTHOUSE / EXHAUST FAN ROOM - ENTRY DOOR CLOSER MISSING. PASSENGER ELEVATOR MACHINE ROOM - DOOR NOT LATCHING. FIRE HORSE CLOSETS THROUGHOUT - DOOR CLOSERS MISSING. ELECTRIC METER CLOSETS THROUGHOUT - DOOR LABELS MISSING. 1ST FLOOR - DOOR UNDER STAIRWAY - MISSING LABEL AND CLOSER. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
REPAIR DOOR HARDWARE | 1ST FLOOR - FIRE HORSE ROOM, TIME CLOCK ROOM AND PHONE ROOM - MISSING DOOR CLOSERS. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
NON COMBUSTIBLE STAIRS | ROOF DECK - TWO EXTERIOR STAIRWAYS OVER FIRE-WALL CONSTRUCTED OF WOOD BOARDS. REMOVE AND REBUILD WITH NON COMBUSTIBLE MATERIALS. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
STOP/REMOVE NUISANCE | REMOVE ALL STORAGE: PENTHOUSE / FREIGHT ELEVATOR ROOM - PAINTS AND WOOD BOARD STORAGE. 1ST FLOOR / TRASH ROOM - LAWNMOWER, GASOLINE AND OTHER GARDEN EQUIPMENT STORAGE. WATER METER ROOM - WOOD CABINET SHELVES USED FOR STORAGE. BOILER AND PUMP ROOM - USED AS STORAGE. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
REPAIR EXTERIOR DOOR, RESET | PENTHOUSE - FREIGHT ELEVATOR EMERGENCY EXIT DOOR TO ROOF DRAFTY, BROKEN AND RUSTED. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
REPAIR EXTERIOR DOOR HARDWARE | ALL FLOORS: FIRE ESCAPE DOORS - MISSING CLOSERS. BOILER ROOM REAR EXTERIOR DOOR - MISSING CLOSER. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
PROVIDE | TRASH ROOM: INCOMPLETE 1-HOUR ENCLOSURE - DRYWALL ON ONE SIDE OF OPEN WOOD STUDS (SEC. 15-8-170). | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
1HR PUB.CORRIDOR IN MULT. D.U. | TENANT STORAGE - ENTRANCE DOOR BEING HELD OPEN WITHOUT AUTOMATIC RELEASE OR FAIL-SAFE DEVICE - FIRE HAZARD. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
NO CLOSET/STORAGE UNDER STAIR | 1ST FLOOR - STOVES AND OTHER ITEMS STORED UNDER STAIRWAY. REMOVE ALL STORAGE. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
SUPPORT FIXTURES | 2ND FLOOR / FIRE HORSE - LOOSE AND HANGING JUNCTION BOX. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
COVER OUTLETS AND JBS | 2ND FLOOR / FIRE HORSE ROOM - OPEN JUNCTION BOX, WITH EXPOSED WIRES. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
OBSTRUCTIONS IN EXIT WAY | 4TH FLOOR CORRIDOR - STORED BIKE OBSTRUCTING EGRESS. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
INSTALL SMOKE DETECTORS | BIKE ROOM - SMOKE DETECTOR - MISSING. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
INSTALL EXIT SIGN | TENANT STORAGE - EXIT SIGN - MISSING. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 1 AND CATEGORY 5 SAFETY TESTS ON BOTH ELEVATORS | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
PARAPET | EAST FENCE WALL - WASHED OUT MORTAR AND SPALLING BRICKS. | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
DEFECTIVE FIXTURES | 8TH FLOOR CORRIDOR - EMERGENCY LIGHT FAILED TEST. | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | EAST ELEVATION / EXTERIOR WALL / MULTIPLE LOCATIONS - SPALLING PAINT. | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
ARRANGE FOR REINSPECTION REGAR | INTERIOR OF THE BUILDING - NO RESPONSE, UNVERIFIED DETECTORS AND CONDITIONS. | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
UNINTERRUPTED EXIT AT GRADE | REAR YARD / 8-STORY METAL FIRE ESCAPE / 12 GARBAGE CONTAINERS PLACED UNDER THE FIRE ESCAPE - OBSTRUCTING PATH OF EGRESS. | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RETURN SOUTH ELEVATOR TO SAFE OPERSTION | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CITY OF CHICAGO FIRE SERVICE MANDATE UPGRADE ON SOUTH ELEVATOR. | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RE TEST FIRE SERVICE | 1401 E HYDE PARK BLVD | PERMIT | PASSED | View |
ARRANGE FOR REINSPECTION REGAR | UNABLE TO INSPECT INTERIOR, STAIRWELLS, APARTMENTS, BASEMENT, AND COMMON AREAS. UNVERIFIED DETECTORS AND CONDITIONS. | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | SOUTH/FIRE ESCAPE - EXIT DISCHARGE - COUNTER WEIGHT STAIRS - TRASH CONTAINERS BELOW PROHIBIT THE EMERGENCY LOWERING | 1401 E HYDE PARK BLVD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 1 SAFETY TEST ON BOTH ELEVATORS | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |
1HR ENCL FLR TO FLR SHAFT/DUCT | PENTHOUSE - EXHAUST FAN DUCT - PENETRATION HOLES ON FLOOR AND CEILING. SEAL TOP AND BOTTOM WITH APPROVED FIRE-STOPPING MATERIALS SUCH AS FIRE CAULK, WITH MINERAL WOOL BACK-UP. SUBMIT DOCUMENTATION THAT FIRE-STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARD. | 1401 E HYDE PARK BLVD | PERIODIC | PASSED | View |