Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OWNER OR LICENSED CONTRACTOR | 5757 W 59TH ST | PERIODIC | PASSED | View | |
INTERNAL | BOILER #1 COL FB. | 5757 W 59TH ST | PERIODIC | PASSED | View |
DEFECTIVE SAFETY VALVE-BOILER | BOILER #1 COL FB | 5757 W 59TH ST | PERIODIC | PASSED | View |
PRV RECEIVER | 450 PSIG FOR THE FOLLOWING TWO 5TON, TWO 3.75TON AND ONE 7.5 TON REMOTE REFRIGERATION UNITS THAT SERVES THE W.I.C./W.I.F. THE UNITS ARE LOCATED ON THE ROOF | 5757 W 59TH ST | PERIODIC | FAILED | View |
PRV RECEIVER | 450 PSIG FOR THE FOLLOWING TWO 5TON, TWO 3.75TON AND ONE 7.5 TON REMOTE REFRIGERATION UNITS THAT SERVES THE W.I.C./W.I.F. THE UNITS ARE LOCATED ON THE ROOF | 5757 W 59TH ST | PERIODIC | FAILED | View |
PRV HIGH SIDE | FOR ONE COPELAND / BOHN 10 HP COMPRESSOR SERVING THE PETA FREEZER. FOR ONE COPELAND / KRAMER 7.5 HP. COMPRESSOR SERVING W-IN FREEZER. FOR ONE COPELAND 15 HP. COMPRESSOR WITH THREE 5"X 24" RECEIVERS SERVING DOCK COOLER.FOR ONE COPELAND 10 HP. COMPRESSOR SERVING DOCK COOLER. FOR ONE COPELAND / LARKIN 5 HP. COMPRESSOR SERVING MEAT PACKING ROOM. ALL LOCATED ON ROOF | 5757 W 59TH ST | PERIODIC | FAILED | View |
PRV SEAL DESTROYED | FOR ONE COPELAND / KRACK 7.5 HP. COMPRESSOR SERVING PETA COOLER. FOR ONE COPELAND / SUPERIOR 27 HP. COMPRESSOR SERVING BLAST FREEZER. | 5757 W 59TH ST | PERIODIC | FAILED | View |
OBTAIN REFRIGERATION PERMIT | FOR ONE COPELAND / RUSSELL 10 HP. COMPRESSOR SERVING BLAST FREEZER,R404A,8"X40" RECEIVER LOCATED ON ROOF.FOR ONE COPELAND /LARKIN 5 HP COMPRESSOR SERVING MEAT PACKING ROOM- R-22,5"X30" RECEIVER, LOCATED ON ROOF.FOR TWO COPELAND / RUSSELL 10 HP COMPRESSORS SERVING PRODUCTION AREA COOLER #1A-R404A,10"X24" RECEIVERS,LOCATED ON ROOF. | 5757 W 59TH ST | PERIODIC | FAILED | View |
PRV HIGH SIDE | FOR ONE COPELAND 10 HP. COMPRESSOR SERVING DOCK COOLER.. LOCATED ON ROOF. IF UNIT IS NO LONGER IN SERVICE -DISCONNECT ,RECLAIM REFRIGERANT AND OR REMOVE FROM ROOF. | 5757 W 59TH ST | PERIODIC | CLOSED | View |
PRV SEAL DESTROYED | FOR ONE COPELAND / KRACK 7.5 HP. COMPRESSOR SERVING PETA COOLER. FOR ONE COPELAND / SUPERIOR 27 HP. COMPRESSOR SERVING BLAST FREEZER. | 5757 W 59TH ST | PERIODIC | FAILED | View |
OBTAIN REFRIGERATION PERMIT | FOR ONE COPELAND / RUSSELL WITH TWO 10 HP. COMPRESSORS SERVING BLAST FREEZER,R404A,8"X40" RECEIVER LOCATED ON ROOF.FOR TWO COPELAND / RUSSELL 10 HP COMPRESSORS SERVING PRODUCTION AREA COOLER #1A-R404A,10"X24" RECEIVERS,LOCATED ON ROOF. FOR TWO KRACK / COPELAND 12.5 HP. COMPRESSORS SERVING LOW FREEZER WITH 12" X 30 " RECEIVERS LOCATED ON NORTH EAST END OF ROOF. FOR ONE RUSSELL / COPELAND 15 HP COMPRESSOR SERVING PITA FREEZER WITH 8" X 42 " RECEIVER LOCATED ON ROOF SOUTH ROOF S.W. CORNER. | 5757 W 59TH ST | PERIODIC | CLOSED | View |
PRV GREASE INTCPT OR CTH BASIN | GREASE BASIN NEEDED FOR WASTE FROM DRAINS OF FOOD PRODUCTION PLANT | 5757 W 59TH ST | COMPLAINT | FAILED | View |
LICENSED BONDED PLMBG CONTRCTR | 5757 W 59TH ST | COMPLAINT | FAILED | View | |
NO ENTRY | 5757 W 59TH ST | PERIODIC | PASSED | View | |
OWNER OR LICENSED CONTRACTOR | 5757 W 59TH ST | PERIODIC | PASSED | View | |
ARRANGE PREMISE INSPECTION | INTERIOR OF BLDG: NO RESPONSE - UNVERIFIED DETECTORS, OCCUPANCY AND CONDITIONS. | 5757 W 59TH ST | COMPLAINT | FAILED | View |
INSTALL | DISCHARGE PIPING FROM SAFETY DOWN TO FLOOR BOILER #1 COL FB. | 5757 W 59TH ST | PERIODIC | PASSED | View |
INSTALL | CARBON MONOXIDE DETECTOR. | 5757 W 59TH ST | PERIODIC | PASSED | View |
OBTN PERMIT FOR PLUMBING WORK | 5757 W 59TH ST | COMPLAINT | FAILED | View |