Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ARRANGE COMPLETED PERMIT INSP. | 2959 N PULASKI RD | PERMIT | PASSED | View | |
SEE INSPECTOR COMMENTS | EMERGENCY LIGHT FIXTURES IN BASEMNT HAVE PLASIC HOUSINGS, MUST BE METAL. 18-27-700.366(C)(3) | 2959 N PULASKI RD | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | CIRCUIT BREAKERS FOR 1ST FLOOR COMMERCIAL SPACEBREAKER PANEL ARE NOT LISTED FOR USE WITH THAT PARTICULAR EQUIPMENT. 18-27-110.3(B) | 2959 N PULASKI RD | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | INSTALL EMERGENCY ILLUMINATION FOR BASEMENT STAIRWELL 18-27-700.6(A) | 2959 N PULASKI RD | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | EXPOSED WIRING AT LIGHT FIXTURE AT REAR STORE ROOM 18-27-410.24 | 2959 N PULASKI RD | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | NO SMOKE DETECTORS OR CARBON MONOXIDE DETECTORS PRESENT AT RESIDENTIAL FRONT STAIRWELL 2ND FLOOR LEVEL 18-27-570.10 | 2959 N PULASKI RD | PERMIT | PASSED | View |
OPEN | 2959 N PULASKI RD | PERMIT | PASSED | View | |
SEE INSPECTOR COMMENTS | ELECTRICAL CONTRACTOR MUST BE ON SITE FOR INSPECTION 13-12-170 | 2959 N PULASKI RD | PERMIT | PASSED | View |