Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ADD RECEPTACLES | ADD RECEPTACLES TO EASE EXTENSION CORD USE THRU OUT 5357 1ST FLOOR BAR | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
CONTINUITY OF RACEWAY | PROVIDE GROUND CONTINUITY FOR WIRE MOLD TO EMERGENCY LITES IN ENTRANCE AREA | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
DEFECTIVE FIXTURES | REPLACE ALL DEFECTIVE LITE FIXTURES THRU OUT INTERIOR STAIRWAY AREAS-NO COVERS | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
ADD BRANCH CIRCUITS | ADD CIRCUITS TO EASE OVERLOAD USE FROM APPLIANCES IN KITCHEN AND LIVING ROOM AREAS OF UNITS 5357 3RD FLOOR UNIT AND OTHER TYPICAL UNITS THRU OUT BUILDING | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
SUPPORT FIXTURES | PROPERLY SUPPORT LITE FIXTURE ABOVE POOL TABLE IN 1ST FLOOR BAR 5357 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | PROVIDE GFCI PROTECTION FOR ALL KITCHEN COUNTER TOP AREAS BATHROOM, LAUNDRY AREAS OF UNIT 5357 3RD FLOOR AND OTHER TYPICAL UNIT THRU OUT BUILDING AND 5357 1ST FLOOR COUNTER TOP AREAS 18-27-210.8,18-27-570.8 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
PROVIDE WEATHERPROOF BOXES LITES, FITTINGS AND APPROVED RACEWAY FOR ALL REAR PORCH AREAS 18-27-110.11 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View | |
MAINTAIN REQUIRE CLEARANCES FOR SERVICE DROP CONDUCTORS 18-27-230.24 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View | |
REPAIR**************** | PROVIDE THE REQUIRED DIAGRAM AND LOAD CALCULATION FOR FEEDERS, SERVICES, AND REQUIRED EQUIPMENT 18-27-215.5 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
NO PERMIT WIRING | OBTAIN ELECTRICAL PERMIT AND CONTRACTOR TO CORRECT VIOLATIONS AND FOR INSTALLATION OF SYSTEM 2 EM LITES WITHOUT PLANS OR PERMITS | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
CONTINUITY OF RACEWAY | PROVIDE GROUND CONTINUITY FOR TROUGH RACEWAY AT METER BANK AREAS-DANGEROUS AND HAZARDOUS CONDITION-5357 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
MULTIPLE CONDUCTOR TERM | REMOVE DOUBLE LUGGING AT METER BANK AREA IN BASEMENT-5357 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
LIVE FRONT SWITCHBOARD | REPLACE LIVE FRONT SERVICE WITH DEAD FRONT TYPE IN BASEMENT AREA-5357 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | ALL BOXES SHALL BE ACCESSIBLE, COVERED, AND COMPLY WITH THE DIMENSION REQUIREMENTS OF ARTICLE 370-JUNCTION BOX AT METER BANK AREAS AND TROUGH RACEWAYS 18-27-370-5357 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
TROUGH RACEWAYS NO MORE THAN 30 CURRENT CARRING CONDUCTORS-AT METER BANK AREAS 18-27-362.5-5357 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View | |
NO PERMIT WIRING | OBTAIN ELECTRICAL PERMIT AND CONDUCTOR TO CORRECT BIOLATIONS AND FOR INSTALLATION OF PANELS AT METER BANK WITHOUT PLANS OR PERMITS-5357 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |
1-HR HEATING PLANT ENCLOSURE | BASEMENT BOILER ROOM CEILING BROKEN PLASTER, SEPARATION COMPROMISED, ALSO PENATRATIONS REQUIRE FIRE STOP-5357 | 5359 W BELMONT AVE | COMPLAINT | PASSED | View |