Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ARRANGE COMPLETED PERMIT INSP. | 3445 N KIMBALL AVE | COMPLAINT | PASSED | View | |
PROVIDE SUPPLY | PROVIDE MECHANICAL SUPPLY VENTILATION 13-176-070 SALES 1 CFM/SQ FT OFFICE 0.6 CFM/SQ | 3445 N KIMBALL AVE | COMPLAINT | PASSED | View |
GIVE VENT OPENINGS % FL. AREA | PROVIDE MECHANICAL EXHAUST VENTILATION 13-176-070 SALES 1 CFM/SQ FT OFFICE 0.3 CFM | 3445 N KIMBALL AVE | COMPLAINT | PASSED | View |
PRV RECEIVER | 450# PSIG FOR TWO COPELAND 6 HP REMOTE REFRIGERATION UNITS LOCATED ON ROOF SERVING W.I.C. | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |
PRV RECEIVER | 450# PSIG FOR TWO COPELAND 6 HP REMOTE REFRIGERATION UNITS LOCATED ON ROOF SERVING W.I.C. | 3445 N KIMBALL AVE | PERIODIC | PASSED | View |
PRV RECEIVER | 450#PSIG FOR ONE COPELAND 5HP REMOTE REFRIGERATION UNIT LOCATED ON ROOF SERVING W.I.F. | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |
PRV RECEIVER | 450#PSIG FOR ONE COPELAND 5HP REMOTE REFRIGERATION UNIT LOCATED ON ROOF SERVING W.I.F. | 3445 N KIMBALL AVE | PERIODIC | PASSED | View |
PRV RECEIVER | 450# PSIG FOR ONE SINGER, FOUR COPELAND 5 HP AND ONE COPELAND 2 HP REMOTE REFRIGERATION UNITS LOCATED ON ROOF SERVING W.I. AND R.I. COOLERS | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |
PRV RECEIVER | 450# PSIG FOR ONE SINGER, FOUR COPELAND 5 HP AND ONE COPELAND 2 HP REMOTE REFRIGERATION UNITS LOCATED ON ROOF SERVING W.I. AND R.I. COOLERS | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |
PRV RECEIVER | 450# PSIG FOR ONE COPELAND 7.5 HP REMOTE REFRIGERATION UNIT SERVING WALK IN FREEZERS LOCATED ON ROOF. | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |
ACCESS TO ROOF | ROOF | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |
ARRANGE FOR INSPECTION | CONTACT INSPECTOR PULLEN AT 312 743-3562 ON FRIDAYS FROM 8-9 AM | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |
PRV RECEIVER | 450# PSIG FOR TWO COPELAND 7.5 HP REMOTE REFRIGERATION UNITS SERVING WALK IN FREEZERS LOCATED ON ROOF. | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |
PRV PLUGGED/CAPPED | FOR TWO WITT / COPLEMATIC CONDENSING UNITS 5 HP. EACH LOCATED ON ROOF. 6" X 36" RECEIVERS. PRESSURE RELIEF VALVES ARE CAPPED. | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |
PRV PLUGGED/CAPPED | FOR TWO CENTURY REFRIGERATION UNITS LOCATED ON ROOF. APPROX. 6 HP. EACH WITH 6"X 36" RECEIVERS. PRV'S ARE CAPPED. PLEASE REMOVE CAPS OR REPLACE PRV'S. | 3445 N KIMBALL AVE | PERIODIC | FAILED | View |