PIN: 16111160080000
Property Address: 637 N LAWNDALE AVE
City - Zip: CHICAGO - 60624
2023 Property Class: 211
2023 Township: 77 - West Chicago
2023 Neighborhood: 77101
2023 Tax District: 77052
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 22 Violations
Violation Inspector Comments Address Category Status View
POST OWNER NAME OF VACNT BLDG VIOLATION CLOSED PER PCR 1180 637 N LAWNDALE AVE COMPLAINT CLOSED View
VACANT BUILDING - REGISTER 637 N LAWNDALE AVE COMPLAINT CLOSED View
SUBMIT FOR APPROVAL PLANS 637 N LAWNDALE AVE COMPLAINT CLOSED View
MAINTAN BLDG IN SAFE CONDITION 637 N LAWNDALE AVE COMPLAINT CLOSED View
VACANT BUILDING - REGISTER 637 N LAWNDALE AVE COMPLAINT CLOSED View
POST OWNER INFO ON ABDN BLDG 637 N LAWNDALE AVE COMPLAINT CLOSED View
FAILURE TO PAY DEFECT FEE AND RESPOND TO DEFECT NOTICE SENT 4/08/17 FOR 637 N LAWNDALE AVE. IMMEDIATE SUSPENSION OF PERMITTING PRIVILEGES AS PER 13-12-430 637 N LAWNDALE AVE PERMIT PASSED View
SEAL HOLES UNIT PANEL SHOWS EVIDENCE OF WATER ON CIRCUIT BREAKERS. SEAL HOLES IN PANELS AS PER 18-27-11012(A) & (D) 637 N LAWNDALE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS REMOVE #14 AWG ON 20 AMP CIRCUIT BREAKER AS PER 18-27-210.24 637 N LAWNDALE AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS USE DUCT SEAL TO PROVIDE PROTECTION OF FEEDER (WATER ENTERING DISCONNECET) AS PER 18-27-110.11 637 N LAWNDALE AVE PERMIT PASSED View
MAIN BONDING JUMPER INSTALL MAIN BONDING JUMPER AT SERVICE DISCONNECT AS PER 18-27-250.28 637 N LAWNDALE AVE PERMIT PASSED View
SERVICE BONDING BUSHINGS BOND GROUNDING BUSHING AT SERVICE AS PER 18-27-250.92 637 N LAWNDALE AVE PERMIT PASSED View
MAIN BONDING JUMPER 637 N LAWNDALE AVE PERMIT FAILED View
SERVICE BONDING BUSHINGS BOND GROUND BUSHING AT SERVICE 637 N LAWNDALE AVE PERMIT FAILED View
SEE INSPECTOR COMMENTS BOND GROUND ELECTRODE CONDUCTOR TO NEUTRAL BUS AT SERVICE DISCONNECT AT 18-27-250.24 637 N LAWNDALE AVE PERMIT FAILED View
WORKMANLIKE MANNER SEAL HOLES IN PANEL (UNIT PANEL HAS WATER ON CIRCUIT BREAKERS) AS PER 18-27-110.12(A)(D) 637 N LAWNDALE AVE PERMIT FAILED View
ARC-FAULT FOR BEDROOMS INSTALL ARC FAULT CIRCUIT BREAKER FOR BEDROOMS AS PER 18-27-210.12 637 N LAWNDALE AVE PERMIT FAILED View
SEE INSPECTOR COMMENTS REMOVE #14 AWG ON 20 AMO CIRCUIT BREAKER AS PER 18-27-210.24 637 N LAWNDALE AVE PERMIT FAILED View
SEE INSPECTOR COMMENTS USE DUCT SEAL TO PROVIDE PROTECTION OF FEEDERS (WATER ENTERING SERVICE DISCONNECT) AS PER 18-27-110.11 637 N LAWNDALE AVE PERMIT FAILED View
WATCHMAN 637 N LAWNDALE AVE COMPLAINT CLOSED View
REPAIR/WRECK DANGER RESID PREM 637 N LAWNDALE AVE COMPLAINT CLOSED View
ARC-FAULT FOR BEDROOMS INSTALL ARC FAULT CIRCUIT BREAKER FOR BEDROOMS AS PER 18-27-210.12 637 N LAWNDALE AVE PERMIT PASSED View