Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
FILE BLDG REGISTRATION | BUILDING NOT REGISTERED 1999 TO 2007 | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
INSTALL DOOR VIEWING DEVICE | FRONT DOOR INTERIOR NO PEEPHOLES | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
PROVIDE DEADLOCK FOR ENTRANCE | WEST INTERIOR DOOR NO LOCK | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
DEBRIS, EXCESSIVE | REAR PORCH DEBRIS | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | REAR BASEMENT AND NORTH ELEVATION OPEN MORTAR JOINTS | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
PIGEONS-NESTING | 3RD FLOOR LANDING PIGEON DROPPING | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | ENTRY TO BUILD TO VERIFY SMOKE DETECTOR AND BASEMENT MOLD | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | REAR PORCH LOW FOOTING CRACKED TREADS JOIST SPANNED TO LONG 2X8 AT 1ST FLOOR 2' IN LENGTH NEED PLAN AND PERMITS | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | NOT REGISTERED 1999 TO 2009. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | RAER PORCH TREADS SPLIT. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
INSTALL DOOR VIEWING DEVICE | APARTMENT DOORS NO PEEP HOLES. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
PERMIT REQUIRED - CONTRACTOR | PERMIT TO REDUCE WINDOW SIZE AND BRICK UP WINDOW. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | INTERIOR STAIR RAIL LOOSE , LANDING WEAK AND SAGGING IN. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
DEBRIS, EXCESSIVE | PORCH JUNK AND DEBRIS. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | REAR BASEMENT , NORTH ELEVATION EXTERIOR WALL MORTAR MISSING. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
INSTALL DOOR VIEWING DEVICE | FRONT DOOR INTERIOR NO PEEPHOLES | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
DEBRIS, EXCESSIVE | REAR PORCH DEBRIS | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | REAR BASEMENT AND NORTH ELEVATION OPEN MORTAR JOINTS | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
SERVICE WALK, PASSAGE, AREAWAY | EAST ELEVATION BREEZE WAY BROKEN CONCRETE | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR STAIR | EAST STAIR MISSING HANDRAILS | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | REAR PORCH LOW FOOTING CRACKED TREADS JOIST SPANNED TO LONG 2X8 AT 1ST FLOOR 2' IN LENGTH NEED PLAN AND PERMITS | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | REAR BASEMENT AND NORTH ELEVATION OPEN MORTAR JOINTS | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | RAER PORCH TREADS SPLIT. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
INSTALL DOOR VIEWING DEVICE | APARTMENT DOORS NO PEEP HOLES. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | INTERIOR STAIR RAIL LOOSE , LANDING WEAK AND SAGGING IN. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
PERMIT REQUIRED - CONTRACTOR | PERMIT TO REDUCE WINDOW SIZE AND BRICK UP WINDOW. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR HARDWARE | FRONT ENTRY DOOR LOCK HARDWARE BROKEN. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
INT WALL/CEILING CHIP PLASTER | FRONT HALL WAY WITH CHIPED PAINT AND PLASTER. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
POST OWNER/MANAGERS NAME/# | NO OWNER MANEGMENT SIGN POSTED. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL-(N/W CORNER) AND (5339 S.)-OUTWARD SHIFTING BRICKS. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | REAR PORCH-COLUMNS ARE OVERCUT AT BEAM CONNECTIONS. COLUMNS WITH ONLY 12 INCH SPLICES AND THREE BOLTS. EDGE BEAMS ARE ONLY NAILED AT COLUMN CONNECTIONS. UNDERSIZED 2X8 DECK JOISTS SPANNING 15 FEET. 4X4 POSTS WITH ONLY 6 INCH SPLICES AND ONLY TOE NAILED TOGETHER. 4X4 POSTS ARE ONLY NAILED AT JOIST / EDGE BEAM CONNECTIONS. STRINGERS ARE ONLY NAILED AT COLUMN / POST CONNECTIONS. WORN TREADS. ONLY 36 INCH HEIGHT GUARDRAILS; SHIFT UPON LOAD; MISSING PICKETS; ONLY NAILED AT EXTERIOR WALL CONNECTIONS. MOST MEMBERS ARE ONLY TOE NAILED TOGETHER AT THE CONNECTIONS. PLANS AND PERMIT REQUIRED FOR REPAIRS. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR FRAME | EXTERIOR DOOR FRAME-SPLINTERED; BROKEN; DOES NOT LOCK. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR HARDWARE | FRONT ENTRY DOOR LOCK HARDWARE BROKEN. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | FRONT INTERIOR STAIRWAY-MISSING PICKETS. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
DEFECTIVE OUTLETS | OUTLET-LOOSE; EXPOSED CONDUIT. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
EMERGENCY ILLUMINATION | EMERGENCY LIGHTING-DIM; LOW ILLUMINATION WHEN TESTED. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL-(N/W CORNER) AND (5339 S.)-OUTWARD SHIFTING BRICKS. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR FRAME | EXTERIOR DOOR FRAME-SPLINTERED; BROKEN; DOES NOT LOCK. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | NOT REGISTERED 1999 TO 2006 | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR PORCH SYSTEM | RAER PORCH TREADS SPLIT. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
INSTALL DOOR VIEWING DEVICE | APARTMENT DOORS NO PEEP HOLES. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
PERMIT REQUIRED - CONTRACTOR | PERMIT TO REDUCE WINDOW SIZE AND BRICK UP WINDOW. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | INTERIOR STAIR RAIL LOOSE , LANDING WEAK AND SAGGING IN. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
PROVIDE DEADLOCK FOR ENTRANCE | WEST INTERIOR DOOR NO LOCK. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
DEBRIS, EXCESSIVE | PORCH JUNK AND DEBRIS. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | REAR BASEMENT , NORTH ELEVATION EXTERIOR WALL MORTAR MISSING. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | PROVIDE EVIDENCE OF BUILDING REGISTRATION FOR YEARS 2009-2012. | 5337 S CALUMET AVE | COMPLAINT | FAILED | View |
MAINTAIN PROJECTIONS | FRONT STONE ORNAMINAL PROJECTIONS AT BALCONY WASHED OUT MORTAR JOINTS. | 5337 S CALUMET AVE | COMPLAINT | FAILED | View |
REPAIR CORNICE | EXTERIOR WEST CORNICE CORNICE WASHED OUT MORTAR JOINTS. | 5337 S CALUMET AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO RESPONSE TO INTERIOR TO VERIFY OCCUPANCY, DETECTORS, PORCHES, AND COMPLAINT OF LEAKS AND MILDEW. | 5337 S CALUMET AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL NORTH WEST CORNER STRESS AND STEP FRACTURES. | 5337 S CALUMET AVE | COMPLAINT | FAILED | View |
REPAIR PORCH SYSTEM | REAR 3 STORY WOOD PORCH WITH ROOF;COLUMNS /6X6 LOOKOUT STACKED ON TOP OF 6X6 COLUMNS, WITH NAILS /SCREWS, GUSSET ONLY;STRINGERS /LOWER ENDS OF STRINGERS INADEQUATE SUPPORTED AT HEADER JOISTS AND COLUMNS, FASTENED WITH NAILS /SCREWS ONLY;RAILINGS /GUARD RAILING SECTIONS [AT EXTERIOR WALL] ¿ LOOSE AND PULLING; DEFLECTING UNDER LOAD; WITH TOP RAILS PULLING; STAIR RAILING SECTIONS ¿ LOOSE AND PULLING; DEFLECTING UNDER LOAD; WITH TOP AND BOTTOM RAILS PULLING; | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR STAIR | EAST STAIR MISSING HANDRAILS | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
SERVICE WALK, PASSAGE, AREAWAY | EAST ELEVATION BREEZE WAY BROKEN CONCRETE | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
INSTALL DOOR VIEWING DEVICE | APARTMENT DOORS NO PEEP HOLES. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | INTERIOR STAIR RAIL LOOSE , LANDING WEAK AND SAGGING IN. | 5337 S CALUMET AVE | PERIODIC | FAILED | View |