Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
VACANT BUILDING - REGISTER | 6214 S EVANS AVE | COMPLAINT | CLOSED | View | |
ARRANGE PERMIT INSP. | 6214 S EVANS AVE | PERMIT | PASSED | View | |
ARRANGE COMPLETED PERMIT INSP. | 18-28-106.1 INSPECTION REQUIRED 13-32-270 WARM AIR FURNACES | 6214 S EVANS AVE | COMPLAINT | PASSED | View |
OPEN TYPE VIOLATION | (VT 7019) 18-28-603.3 METALLIC DUCTS ALL DUCTS SHALL BE CONSTRUCTED OF IRON, STEEL,ALUMINUM OR OTHER APPROVED MATERIAL APPROVED MATERIAL | 6214 S EVANS AVE | COMPLAINT | PASSED | View |
OPEN TYPE VIOLATION | (VT 7022) 18-28-603.8 JOINTS AND CONNECTIONS, ALL JOINTS, LONGITUDINAL AND TRANSVERSE SEAMS AND CONNECTIONS SHALL BE SECURELY FASTENED AND SEALED WITH WELDS, GASKET,MASTICS (ADHESIVES) | 6214 S EVANS AVE | COMPLAINT | PASSED | View |
PROVIDE | PROVIDE 18-28-918.2 MINIMUM DUCT SIZES THE MINIMUM UNOBSTRUCTED TOTAL AREA OF OUTSIDE AND RETURN AIR DUCTS OR OPENINGS TO A FORCED AIR WARM AIR FURNACE SHALL BE NOT LESS THAN 2 SQUARE INCHES PER 1,000 BTU OUTPUT RATING CAPACITY OF THE FURNACE AND NOT LESS THAN THAT SPECIFIED IN THE FURNACE MANUFACTURER'S INSTALLATION INSTRUCTIONS | 6214 S EVANS AVE | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | SEE NOTICE # 11995 | 6214 S EVANS AVE | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | SEE COMMENTS IN BUILDING INSPECTIONS | 6214 S EVANS AVE | PERMIT | PASSED | View |
ARRANGE PERMIT INSP. | 6214 S EVANS AVE | PERMIT | FAILED | View | |
ARRANGE PERMIT INSP. | 6214 S EVANS AVE | PERMIT | PASSED | View | |
ARRANGE PERMIT INSP. | 6214 S EVANS AVE | PERMIT | FAILED | View |