Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
VACANT BUILDING - REGISTER | 4325 W 21ST PL | COMPLAINT | CLOSED | View | |
VACANT BUILDING - REGISTER | INSPECTED BY BL01036 ON 02-AUG-10 AND RE-INSPECTED BY BL00272 ON 02-DEC-10. DEPT. OF BUILDINGS DATABASE REVIEWED ON 10-FEB-11 BY BL00393. NO PROOF OF REGISTRATION AS OF 02-AUG-10 AND 02-DEC-10 :: | 4325 W 21ST PL | COMPLAINT | CLOSED | View |
VACANT BUILDING - REGISTER | 4325 W 21ST PL | COMPLAINT | CLOSED | View | |
SUBMIT FOR APPROVAL PLANS | 4325 W 21ST PL | COMPLAINT | CLOSED | View | |
MAINTAN BLDG IN SAFE CONDITION | 4325 W 21ST PL | COMPLAINT | CLOSED | View | |
WATCHMAN | 4325 W 21ST PL | COMPLAINT | CLOSED | View | |
VACANT BUILDING - REGISTER | 4325 W 21ST PL | COMPLAINT | CLOSED | View | |
POST OWNER INFO ON ABDN BLDG | 4325 W 21ST PL | COMPLAINT | CLOSED | View | |
REMOVE ABANDONED EQUIP. | REMOVE ABANDONED ELECTRICAL AT BASEMENT AS PER 18-27-110.12(E) | 4325 W 21ST PL | PERMIT | PASSED | View |
MATCH AVAILABLE FAULT CURRENT | MATCH AVAILABLE FAULT CURRENT AT 1ST AND 2ND FLOOR PANELS AS PER 18-27-110.11 | 4325 W 21ST PL | PERMIT | PASSED | View |
2 SMALL APPL BRANCH CIRCUITS | INSTALL REQUIRED 2 SMALL APPLINCE BRANCH CIRCUITS AT KITCHENS AS PER 18-210.11(C) AND 18-27-210.52(B) | 4325 W 21ST PL | PERMIT | PASSED | View |
ARC-FAULT FOR BEDROOMS | INSTALL REQUIRED ARC FAULT BREAKERS AS PER 18-210.12 | 4325 W 21ST PL | PERMIT | PASSED | View |
PROPER SIZE OCP | INSTALL PROPER SIZED BREAKERS AT ALL PANELS. #14 AWG ON 20AMP BREAKERS | 4325 W 21ST PL | PERMIT | PASSED | View |
PROTECT SERVICE CONDUCTORS | ALL SERVICE CONDUCTORS MAY NOT BE INSTALLED IN EMT AS PER 18-230.49 - 50 | 4325 W 21ST PL | PERMIT | PASSED | View |
CONTINUITY OF COND AND EQUIP | PROPERLY TIGHTEN ALL LOOSE LOCKNUTS THROUGHOUT AS PER 18-27-300.12 AND .13 | 4325 W 21ST PL | PERMIT | PASSED | View |
REPAIR/WRECK DANGER RESID PREM | 4325 W 21ST PL | COMPLAINT | CLOSED | View | |
POST OWNER NAME OF VACNT BLDG | VIOLATION CLOSED PER PCR 1180 | 4325 W 21ST PL | COMPLAINT | CLOSED | View |
INSULATING BUSHINGS | INSTALL REQUIRED BUSHINGS AT ALL PANELS AS PER 18-27-300.4(F) | 4325 W 21ST PL | PERMIT | PASSED | View |
REQUIRED OUTLETS AND SPACING | FOLLOW PROPER WALL OUTLET SPACING THROUGHOUT AS PER 18-210.52 | 4325 W 21ST PL | PERMIT | PASSED | View |
SERVICE DISCONNECT LOCATION | 1ST, 2ND, AND PUBLIC PANELS OR DISCONNECTS TO BE GROUPED AS PER 18-27-230.70 | 4325 W 21ST PL | PERMIT | PASSED | View |
WORKMANLIKE MANNER | INSTALL SERVICE CONDUCTORS IN NEAT AND WORKMANLIKE MANNER AS PER 18-27-110.12 | 4325 W 21ST PL | PERMIT | PASSED | View |
STORAGE FIXTURE | PROVIDE REQUIRED LIGHTING AT BASEMENT AS PER 18-27-210.70(A)2(2)(D) AND 18-27-410.8 | 4325 W 21ST PL | PERMIT | PASSED | View |
SERVICE BONDING BUSHINGS | PROVIDE GROUNDING BUSHINGS AS PER 18-27-250.92 AND 94 | 4325 W 21ST PL | PERMIT | PASSED | View |
GES / WATER PIPE 5 FT. | PROVIDE COLDWATER GROUND AND OR BONDING AS PER 18-27-250.30 AND .50 | 4325 W 21ST PL | PERMIT | PASSED | View |
SMOKE AND CO DETECTORS | PROVIDE SMOKE AND CARBON MONOXIDE DETECTORS WITHIN 15' OF BEDROOMS AS PER 18-27-560.3(B) | 4325 W 21ST PL | PERMIT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 4325 W 21ST PL | PERMIT | PASSED | View | |
OPEN | 4325 W 21ST PL | PERMIT | PASSED | View |