Chicago Building Violations Data: 27 Violations
Violation Inspector Comments Address Category Status View
VACANT BUILDING - REGISTER 4325 W 21ST PL COMPLAINT CLOSED View
VACANT BUILDING - REGISTER INSPECTED BY BL01036 ON 02-AUG-10 AND RE-INSPECTED BY BL00272 ON 02-DEC-10. DEPT. OF BUILDINGS DATABASE REVIEWED ON 10-FEB-11 BY BL00393. NO PROOF OF REGISTRATION AS OF 02-AUG-10 AND 02-DEC-10 :: 4325 W 21ST PL COMPLAINT CLOSED View
VACANT BUILDING - REGISTER 4325 W 21ST PL COMPLAINT CLOSED View
SUBMIT FOR APPROVAL PLANS 4325 W 21ST PL COMPLAINT CLOSED View
MAINTAN BLDG IN SAFE CONDITION 4325 W 21ST PL COMPLAINT CLOSED View
WATCHMAN 4325 W 21ST PL COMPLAINT CLOSED View
VACANT BUILDING - REGISTER 4325 W 21ST PL COMPLAINT CLOSED View
POST OWNER INFO ON ABDN BLDG 4325 W 21ST PL COMPLAINT CLOSED View
REMOVE ABANDONED EQUIP. REMOVE ABANDONED ELECTRICAL AT BASEMENT AS PER 18-27-110.12(E) 4325 W 21ST PL PERMIT PASSED View
MATCH AVAILABLE FAULT CURRENT MATCH AVAILABLE FAULT CURRENT AT 1ST AND 2ND FLOOR PANELS AS PER 18-27-110.11 4325 W 21ST PL PERMIT PASSED View
2 SMALL APPL BRANCH CIRCUITS INSTALL REQUIRED 2 SMALL APPLINCE BRANCH CIRCUITS AT KITCHENS AS PER 18-210.11(C) AND 18-27-210.52(B) 4325 W 21ST PL PERMIT PASSED View
ARC-FAULT FOR BEDROOMS INSTALL REQUIRED ARC FAULT BREAKERS AS PER 18-210.12 4325 W 21ST PL PERMIT PASSED View
PROPER SIZE OCP INSTALL PROPER SIZED BREAKERS AT ALL PANELS. #14 AWG ON 20AMP BREAKERS 4325 W 21ST PL PERMIT PASSED View
PROTECT SERVICE CONDUCTORS ALL SERVICE CONDUCTORS MAY NOT BE INSTALLED IN EMT AS PER 18-230.49 - 50 4325 W 21ST PL PERMIT PASSED View
CONTINUITY OF COND AND EQUIP PROPERLY TIGHTEN ALL LOOSE LOCKNUTS THROUGHOUT AS PER 18-27-300.12 AND .13 4325 W 21ST PL PERMIT PASSED View
REPAIR/WRECK DANGER RESID PREM 4325 W 21ST PL COMPLAINT CLOSED View
POST OWNER NAME OF VACNT BLDG VIOLATION CLOSED PER PCR 1180 4325 W 21ST PL COMPLAINT CLOSED View
INSULATING BUSHINGS INSTALL REQUIRED BUSHINGS AT ALL PANELS AS PER 18-27-300.4(F) 4325 W 21ST PL PERMIT PASSED View
REQUIRED OUTLETS AND SPACING FOLLOW PROPER WALL OUTLET SPACING THROUGHOUT AS PER 18-210.52 4325 W 21ST PL PERMIT PASSED View
SERVICE DISCONNECT LOCATION 1ST, 2ND, AND PUBLIC PANELS OR DISCONNECTS TO BE GROUPED AS PER 18-27-230.70 4325 W 21ST PL PERMIT PASSED View
WORKMANLIKE MANNER INSTALL SERVICE CONDUCTORS IN NEAT AND WORKMANLIKE MANNER AS PER 18-27-110.12 4325 W 21ST PL PERMIT PASSED View
STORAGE FIXTURE PROVIDE REQUIRED LIGHTING AT BASEMENT AS PER 18-27-210.70(A)2(2)(D) AND 18-27-410.8 4325 W 21ST PL PERMIT PASSED View
SERVICE BONDING BUSHINGS PROVIDE GROUNDING BUSHINGS AS PER 18-27-250.92 AND 94 4325 W 21ST PL PERMIT PASSED View
GES / WATER PIPE 5 FT. PROVIDE COLDWATER GROUND AND OR BONDING AS PER 18-27-250.30 AND .50 4325 W 21ST PL PERMIT PASSED View
SMOKE AND CO DETECTORS PROVIDE SMOKE AND CARBON MONOXIDE DETECTORS WITHIN 15' OF BEDROOMS AS PER 18-27-560.3(B) 4325 W 21ST PL PERMIT PASSED View
ARRANGE COMPLETED PERMIT INSP. 4325 W 21ST PL PERMIT PASSED View
OPEN 4325 W 21ST PL PERMIT PASSED View