Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
DEBRIS, EXCESSIVE | ALL BASEMENTS STOCKPILED WITH JUNK AND DEBRIS . FIRE / SAFETY HAZARD . RAT HARBORAGE. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
RAT PROOF EXTERIOR DOOR | ALL BASEMENT DOORS - OPEN GAPS AND CRACKS . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
STOP/REMOVE NUISANCE | REAR BY SOUTHEAST PORCH - METAL GRATE CABINATE WITH PLASTIC GASOLINE CANS STORED AT BASE OF PORCH . REMOVE CABINATE AND ALL GASOLINE STORAGE FROM PROPERTY. FIRE / SAFETY HAZARD. CENTER SOUTH BASEMENT - GASOLINE SNOWTHROWER STORED . REMOVE GASOLINE LAWN AND SNOW EQUIPMENT FROM PROPERTY . FIRE / SAFETY HAZARD. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | SOUTH BASEMENT - CARBON MONOXIDE DETECTOR MISSING . WATER HEATER ROOM. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CHIMNEY | SOUTH BASEMENT - OPEN SEAL WITH LOOSE BRICKS AT BASE OF CHIMNEY WITH OPEN MORTAR JOINTS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
DWELLING CLEAN AND SANITARY | SOUTH BASEMENT - SEWAGE AND STAGNANT WATER . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
1HR FLR OVER BSMT, 1 OR 2 DU | ALL BASEMENTS - CEILINGS FALLING AND BROKEN PLASTER WITH EXPOSED LATH . FIRE / SAFETY HAZARD. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
DOOR PROJECT INTO PUBLIC WAY | WEST ELEVATION COMMERCIAL SPACES . DOORS SWING ONTO PUBLICWAY AND CITY OF CHICAGO SIDEWALK. SAFETY HAZARD TO OCCUPANTS AND PASSERBYS . PERMIT REQUIRED FOR REPAIRS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPAIR ROOF | ALL THIRD FLOOR APARTMENTS AND HALLS - CEILINGS WATER DAMAGED , ROOF LEAKING . PERMITS REQUIRED FOR ALL FLAT ROOF REPAIRS AND REPLACEMENTS . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 6353 COMMERCIAL SPACE - REAR CEILING WATER DAMAGED TILES.2725 EAST 3RD FLOOR APARTMENT - BEDROOM WATER DAMAGED CEILING .2727 EAST 2ND FLOOR APARTMENT - LIVING ROOM WALLS DETERIORATED BEHIND WALL COVERINGS. 6355 SOUTH 2ND FLOOR APARTMENT - BATHROOM CEILING WATER DAMAGED. 2727 COMMERCIAL SPACE - CEILING ABOVE DROP TILES DETERIORATED AND WATER DAMAGED WITH LOOSE AND FALLING PLASTER.6351 3RD FLOOR APARTMENT - KITCHEN CEILING WATER DAMAGED PLASTER. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF COMMERCIAL SPACE AND BASEMENT OF 2729 W. DEVON , NO ENTRY . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR STAIR | SOUTHEAST EXTERIOR BASEMENT CONCRETE STAIRS BROKEN AND FRACTURED. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
FILE BLDG REGISTRATION | BUILDING - NOT REGISTERED 1990 THROUGH 2012 YEARS . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPAIR PORCH SYSTEM | REAR PORCHES - FOUNDATIONS STATUS UNKNOWN ; 2 X 8 JOIST SPAN 11'8" . STRINGERS INADEQUATELY SUPPORTED AT COLUMNS ; OPEN RISER DESIGN - 4 1/2" - 6 1/2 " GAPS BETWEEN TREADS ; ROTTING WOOD AT 3RD FLOOR CEILING . RECENTLY BUILT REAR PORCHES ; PLANS AND PERMITS REQUIRED TO REPAIR/REPLACE REAR PORCHES. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
RAT STOP AROUND EXTERIOR | SOUTH , WEST ELEVATIONS - HOLES , GAPS AT FOUNDATION ALLOWING RATS TO ENTER BUILDING . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPAIR DEFECTIVE FOUNDATION | SOUTH AND WEST ELEVATIONS - GAPS ,HOLES , WASHED OUT MORTAR. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
INSECTS | #2727 - 3W APARTMENT - INSECTS THRU-OUT . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | #6353 STOREFRONT - FIRE EXTINGUISHER - NOT TAGGED. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
MAINTAIN WINDOW SASH | ALL ELEVATIONS - WINDOW SASHES - ROTTING ; PAINT PEELING . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
MAINTAIN WINDOW | ALL ELEVATIONS - WINDOW FRAMES - ROTTING ; PAINT PEELING. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
PROVIDE DEADLOCK FOR ENTRANCE | NORTH , WEST ELEVATIONS - DEADBOLT LOCKS MISSING AT ALL FRONT ENTRY DOORS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPAIR DOOR HARDWARE | NORTH AND WEST ELEVATIONS - BUZZER SYSTEM FOR FRONT ENTRY DOORS NOT WORKING AT TIME OF INSPECTION. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | GUARDRAILS MISSING AT GRADE FOR BASEMENT AREAWAY. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | PROVIDE PROPER MATERIAL FOR SOIL / WASTE / VENT PIPE 18-29--702-4 REMOVE ALL P.V.C PIPING INTHE BASEMENTS ALL BASEMENTS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
SEAL DRAIN OPENING UNUSD FIXTR | SEAL DRAIN OPENINGS & UNUSED FIXTURES 18-29-102-3 VENT BAR IN THE STORE AT 6349 FAIRFIELD | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
PRV CAST IRON COVER FOR BASIN | PROVIDE CAST IRON COVER FOR SUMP BASIN 18-29-1003-4-1 SOUTH BASEMENT. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE TRAP | REPLACE DEFECTIVE TRAP- TRAP FOR BATHTUB AT 2727 W.DEVON 2ND FLOOR WEST NEEDS TO BE REPLACED. IT IS NOW CURRENTLY IN THE BASEMENT OF THE STORE AT 2727 W.DEVON. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | PROVIDE PROPER MATERIAL FOR SOIL / WASTE / VENT PIPE 18-29-702-4 DRAIN LINE FROM BATHTUB 2ND FLOOR | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
NO PERMIT WIRING | 2727 COMMERCIAL UNIT ALL WIRING & PANEL MAINTERANCE OF BUILDING WIRING BY NON QUIALIFIED JANITOR DANGEROUS & HAZARDOUS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
DEFECTIVE POWER SERVICE | EMERGENCY SERVICE TAMPERED WITH AND LOCKED OFF BY EDISON RESTORE OR REMOVE. PLAN REQUIRES DANGEROUS & HAZARDOUS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
WORKING SPACE | PROVIDE CLEAR SPACE & ACCESS TO ALL DISTRIBUTION & SERVICE EQUIPMENT. REMOVE DEBRIS, WATER & PROVIDE CLEAR PATH & LIGHTING. 18-22-110-26,230-70 & 72 DANGEROUS & HAZARDOUS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
FIRE & WATER DAMAGE | REPAIR OR REPLACE TO ACCEPTABLE SPECIFICATIONS METERS, PIPES, BOXES & WIRING NORTH BASEMENT. SERVICE DISCONNECTS SOUTHWEST BASEMENT. SEVERE DAMAGE TO FLEX,CONDUIT,BOXES,WIRING & FIXTURES AT CEILING IN NORTHEAST BASEMENT.2727 COMMERCIAL UNIT CEILING WIRING,PANEL & FLEX DAMAGED FROM LEAKS ABOVE. DANGEROUS & HAZARDOUS | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
SEPARATE CIRCUIT FOR APPLIANCE | ALL CENTRAL HEATING UNITS REQUIRE DEDICATED CIRCUITS. ALL COMMERCIAL & DWELLING UNITS | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | ALL BASEMENTS COMMERCIAL AND DWELLINGS DANGEROUS & HAZAROUS | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
EXPOSED WIRING | SOUTH CENTER, SOUTHWEST AND NORTHEAST BASEMENTS INCLUDING SUMP PUMPS.2725 3RD FLOOR CEILING,2727 2 WEST CEILING,2727 3 EAST CEILING 6355 3 NORTH & SOUTH BATHROOMS DANGEROUS & HAZARDOUS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
UNAPPROVED CORDS | 2727 COMMERCIAL UNIT CEILING 6357 COMMERCIAL UNIT CEILING.2727 2ND EAST LIVING ROOM,6351 2ND FLOOR BEDROOM & 6355 3 NORTH LIVING ROOM.DANGEROUS & HAZARDOUS | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | 2725 3RD FLOOR, 2727 2 WEST & 2 EAST, 6355 3 NORTH AND 6351 2ND FLOOR. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
ADD RECEPTACLES | 6349 COMMERCIAL UNIT TO REMOVE CORDS, 6355 3 NORTH KITCHEN,6351 2ND KITCHEN,2725 2ND FLOOR KITCHEN. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
DEFECTIVE OUTLETS | ALL DWELLING RECEPTACLES AND SWITCHES COMMERCIAL SPACES AS NEEDED. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
SUPPORT OUTLET AND JBOX | 2727 WEST LIVING & BATH ROOMS ALSO WHERE NEEDED. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
SUPPORT FIXTURES | PROPERLY SUPPORT ALL FIXTURES IN ALL DWELLING UNITS | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CONTINUITY OF RACEWAY | ALL BASEMENTS | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPLACE DAMAGED CLOTH WIRE AT CEILING BOXES 18-27-110.2& 3. | 2727 W DEVON AVE | COMPLAINT | FAILED | View | |
REPAIR OR REPLACE | REPLACE BROKEN,RUSTED,IMPROPERLY FASTENED AND INSTALLED HOT WATER FLUE IN SOUTHEAST SECTION OF BASEMENT AND PROPERLY SIZE TO ROOF WITH TIGHT CEMENT SEAL WHERE PASSING INTO OLD CHIMNEY.18-28-802-3 18-28-802.7 18-28-803.9 18-28-803.10.1 18-28-803-10.3 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
PROVIDE COMBUSTION AIR FOR ALL FUNACE CLOSETS 18-28-703.1, 18-28-703.1, 18-28-703.3 | 2727 W DEVON AVE | COMPLAINT | FAILED | View | |
REMOVE | DO NOT VENT INTO OLD MASONARY CHIMNEY. MUST HAVE CORRECT SIZE LINER TO ROOF 19-28-801.18.2,18-28-801-18.4, 18-28-920.3, 18-28-801-18.2, 18-28-801.16 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CARBON MONOXIDE DETECTORS MUST BE IN ALL RESIDENTIAL AND COMMERCIAL SPACES AND IN BASEMENT WHERE HOT WATER TANK IS LOCATED 18-28-711, 18-28-1013.1 | 2727 W DEVON AVE | COMPLAINT | FAILED | View | |
PROVIDE MINIMUM VENT QUANTITY | ALL COMMERCIAL SPACES ARE MISSING VENTILATION AND MUST BE PROVIDED WITH ORDINANCE REQUIRED SUPPLY AND EXHAUST VENTILATION 18-28-403, 18-28-103.3 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
PROVIDE SUPPLY | PROVIDE OUTSIDE AIR SUPPLY TO ALL COMMERCIAL SPACES 18-28-403.3 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
GIVE VENT OPENINGS % FL. AREA | PROVIDE EXHAUST TO ALL COMMERCIAL SPACES 18-28-403-3 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REMOVE | P.V.C FLUES SERVING COMMERCIAL SPACES MUST TERMINATE AT LEAST 4 FEET FROM WINDOWS & DOORS ON 1ST FLOOR 18-28-804.3.4 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CITY PROGRAM TO RID VERMIN | ALL BROKEN DUCTWORK CONNECTIONS AND HOLES IN PLENUM MUST BE PROPERTLY REPAIRED 18-28-603.3 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
ALL DUCTWORK CONNECTIONS MUST BE SEALED WITH TYPE 181JEACENT OR TAPE | 2727 W DEVON AVE | COMPLAINT | FAILED | View | |
PROVIDE | PROVIDE FILTER RACKS AND FILTERS FOR ALL FURNACES IN BUILDING PER MANUFACTURERS SPECS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CITY PROGRAM TO RID VERMIN | FURNACES CAN NOT BE COMMON VENTED TOGETHER MUST INSTALL INDIVIDUAL FLUE FOR EACH FURNACE 18-28-801.19 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
(1) FURNACES THAT WERE INSTALLED IN BEDROOMS ARE NOT APPROVED TO BE IN SLEEPING ROOMS AS PER CODE.REMOVE FURNACES IN BEDROOMS OR INSTALL PER CODE 18-28-918-9.2 (2)PROVIDE FRONT CLEARANCE TO FURNACE IN APARTMENT 6355#3S THAT HAS WALL CONSTRUCTED IN FRONT OF 18-28-9.3.3 | 2727 W DEVON AVE | COMPLAINT | FAILED | View | |
GIVE VENT OPENINGS % FL. AREA | MAKE ALL WINDOWS OPERABLE IN APARTMENTS THAT HAVE BEEN SEALED WITH PAINT COVERS WITH PLYWOOD OR TILED OVER AS IN 2725 #2 (NOTE) ANY WINDOWS NOT PROVIDED TO BATHROOMS MUST HAVE MECHANICAL EXHAUST FANS. 18-28-403.3 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REMOVE | REMOVE UNAPPROVED KITCHEN HOOD EXHAUST DUCT ON EXTERIOR OF BUILDING THAT IS NOT CORRECT GAUGE,IMPROPER CONNECTIONS,NOT WELDED,IMPROPERLY FASTENED,RUSTED,ECT.DUCT CAN NOT BE USED FOR ANY FUTURE RESTAURANT.18-28-506.1 THRU 18-28-507.17 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
SUBMIT PLANS/GET VENT PERMIT | OBTAIN PERMIT AND ONLY USE LICENSED H.V.A.C.CONTRACTOR TO INSTALL,REPAIR AND CORRECT ALL VIOLATIONS 13-32-020, 13-32-130, 13-40-010, 18-28-403-14 | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
SEAL DRAIN OPENING UNUSD FIXTR | SEAL DRAIN OPENINGS & UNUSED FIXTURES 18-29-102-3 VENT BAR IN THE STORE AT 6349 FAIRFIELD | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
WORKING SPACE | PROVIDE CLEAR SPACE & ACCESS TO ALL DISTRIBUTION & SERVICE EQUIPMENT. REMOVE DEBRIS, WATER & PROVIDE CLEAR PATH & LIGHTING. 18-22-110-26,230-70 & 72 DANGEROUS & HAZARDOUS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CONTINUITY OF RACEWAY | ALL BASEMENTS | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
DEBRIS, EXCESSIVE | ALL BASEMENTS STOCKPILED WITH JUNK AND DEBRIS . FIRE / SAFETY HAZARD . RAT HARBORAGE. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
STOP/REMOVE NUISANCE | REAR BY SOUTHEAST PORCH - METAL GRATE CABINATE WITH PLASTIC GASOLINE CANS STORED AT BASE OF PORCH . REMOVE CABINATE AND ALL GASOLINE STORAGE FROM PROPERTY. FIRE / SAFETY HAZARD. CENTER SOUTH BASEMENT - GASOLINE SNOWTHROWER STORED . REMOVE GASOLINE LAWN AND SNOW EQUIPMENT FROM PROPERTY . FIRE / SAFETY HAZARD. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | SOUTH BASEMENT - CARBON MONOXIDE DETECTOR MISSING . WATER HEATER ROOM. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CONNECT GAS APPLIANCE TO VENT | SOUTH BASEMENT - LARGE WATER HEATER FLUE PIPE SAGGING AND DISCONNECTED AT JOINTS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CHIMNEY | SOUTH BASEMENT - OPEN SEAL WITH LOOSE BRICKS AT BASE OF CHIMNEY WITH OPEN MORTAR JOINTS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR STAIR | SOUTHEAST EXTERIOR BASEMENT CONCRETE STAIRS BROKEN AND FRACTURED. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | #6353 STOREFRONT - FIRE EXTINGUISHER - NOT TAGGED. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
RATS | ALL BASEMENTS - SEVERE INFESTATION OF RATS . RAT DROPPINGS COVERING ALL FLOORS . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
PROPER SIZE OCP | PROVIDE PROPER OVER CURRENT TO PROTECT WIRING FOR ALL FEEDERS AND BRANCIT CIRCUIT WIRING THRU-OUT | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
RATS | 2727W /APT.3W - RAT INFESTED. | 2727 W DEVON AVE | COMPLAINT | CLOSED | View |
ROACHES | 2727W /APT.3W - ROACH INFESTED. | 2727 W DEVON AVE | COMPLAINT | CLOSED | View |
REPAIR INTERIOR WALLS/CEILING | 2727W /APT.3W - CEILINGS HAVE WATER DAMAGED HOLES; BATHROOM HAS BLACK MILDEW LIKE SUBSTANCE OVER WALLS AND CEILING. | 2727 W DEVON AVE | COMPLAINT | CLOSED | View |
CARPETING | 2727W /APT.3W - FILTHY, DIRTY, STAINED CARPETING. | 2727 W DEVON AVE | COMPLAINT | CLOSED | View |
INT WALL/CEILING CHIP PLASTER | 2727W /FRONT INTERIOR STAIRWELL - CHIPPED, CRACKED PAINT MULTIPLE LOCATIONS. | 2727 W DEVON AVE | COMPLAINT | CLOSED | View |
INSTALL SMOKE DETECTORS | 2727W /APT.3W - NO SMOKE DETECTOR. | 2727 W DEVON AVE | COMPLAINT | CLOSED | View |
REPAIR/REPLACE SMOKE DETECTORS | 2727W /FRONT INTERIOR STAIRWELL - SMOKE DETECTOR OUT OF SERVICE. | 2727 W DEVON AVE | COMPLAINT | CLOSED | View |
DWELLING CLEAN AND SANITARY | 2727W /APT.3W - UNSANITARY CONDITIONS. DIRTY WALLS, FLOORS, STOVE, AND FURNITURE. | 2727 W DEVON AVE | COMPLAINT | CLOSED | View |
INSECTS | 2727W /APT.3W - BED BUG INFESTATION THROUGHOUT. PROPERTY MUST EFFECTIVELY TREAT TO EXTERMINATE BED BUGS THROUGHOUT BY EMPLOYING AND EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION. | 2727 W DEVON AVE | COMPLAINT | CLOSED | View |
SECURE RACEWAY | ALL BASEMENTS SERVICE EQUIPMENT IN SOUTHWEST BASEMENT DANGEROUS & HAZARDOUS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPAIR WINDOW SILLS | #2727- 3W APARTMENT , BATHROOM ROTTING WOOD , DARK SUBSTANCE COVERING SILL. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
CONNECT GAS APPLIANCE TO VENT | SOUTH BASEMENT - LARGE WATER HEATER FLUE PIPE SAGGING AND DISCONNECTED AT JOINTS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
STOP SMOKE, NOXIOUS ODORS | SOUTH BASEMENT , SEWAGE ODORS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
INSPECT CONSTRUCTION WORK | RECENTLY BUILT REAR PORCHES . PERMIT #100126863 ISSUED 1-25-2007 VOIDED . " GC LISTED NOT DOING WORK " . PLANS AND PERMIT NOT AVAILABLE FOR REVIEW AT TIME OF INSPECTION . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
VERIFY PROPER NEUTRALS WITH BRANCH CIRCUITS FOR ALL DWELLING & COMMERCIAL BRANCH CIRCUITS 18-27-210.4 | 2727 W DEVON AVE | COMPLAINT | FAILED | View | |
PRV FLOOR DRAIN WITH METAL STR | ALL BASEMENTS MISSING FLOOR DRAIN COVERS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REPUTTY WINDOW PANES | ALL ELEVATIONS - WINDOW TRIM - ROTTING PAINT PEELING. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
ROACHES | #2727 -3W APARTMENT - ROACHES THRU-OUT . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
REMOVE STAGNANT WATER BSMT | SOUTH BASEMENT , STANDING WATER AND SEWAGE . | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
SYSTEM II | ENTIRE BUILDING PLANS REQUIRED. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |
PROVIDE SUPPLY BRANCHS WITH DAMPERS ON ALL DUCTWORK IN RESIDENTIAL & COMMERCIAL SPACES 18-28-603.15 | 2727 W DEVON AVE | COMPLAINT | FAILED | View | |
CLEAN ALL FURANCES OF DIRT AND DEBRIS,DO TO NOT HAVING FILTERS AND CRUMBLING CEILINGS FALLING IN CLOSETS. | 2727 W DEVON AVE | COMPLAINT | FAILED | View |