Viewing Parcel Address (PIN)

More Information

The Open Source Data Files that are here are from Cook County.

This Page is a combination of all Files.

The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.

This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.

The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.

Viewing Parcel Address (PIN)


Last Modification Date: 2024-10-22 @ 4:33 PM
PIN: 13012010010000
Property Address: 2727 W DEVON AVE
City - Zip: CHICAGO - 60659
2023 Property Class: 318
2023 Township: 71 - Jefferson
2023 Neighborhood: 71041
2023 Tax District: 71102
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 93 Violations
Violation Inspector Comments Address Category Status View
DEBRIS, EXCESSIVE ALL BASEMENTS STOCKPILED WITH JUNK AND DEBRIS . FIRE / SAFETY HAZARD . RAT HARBORAGE. 2727 W DEVON AVE COMPLAINT FAILED View
RAT PROOF EXTERIOR DOOR ALL BASEMENT DOORS - OPEN GAPS AND CRACKS . 2727 W DEVON AVE COMPLAINT FAILED View
STOP/REMOVE NUISANCE REAR BY SOUTHEAST PORCH - METAL GRATE CABINATE WITH PLASTIC GASOLINE CANS STORED AT BASE OF PORCH . REMOVE CABINATE AND ALL GASOLINE STORAGE FROM PROPERTY. FIRE / SAFETY HAZARD. CENTER SOUTH BASEMENT - GASOLINE SNOWTHROWER STORED . REMOVE GASOLINE LAWN AND SNOW EQUIPMENT FROM PROPERTY . FIRE / SAFETY HAZARD. 2727 W DEVON AVE COMPLAINT FAILED View
CARB MONOX DETECT IN RESID SOUTH BASEMENT - CARBON MONOXIDE DETECTOR MISSING . WATER HEATER ROOM. 2727 W DEVON AVE COMPLAINT FAILED View
CHIMNEY SOUTH BASEMENT - OPEN SEAL WITH LOOSE BRICKS AT BASE OF CHIMNEY WITH OPEN MORTAR JOINTS. 2727 W DEVON AVE COMPLAINT FAILED View
DWELLING CLEAN AND SANITARY SOUTH BASEMENT - SEWAGE AND STAGNANT WATER . 2727 W DEVON AVE COMPLAINT FAILED View
1HR FLR OVER BSMT, 1 OR 2 DU ALL BASEMENTS - CEILINGS FALLING AND BROKEN PLASTER WITH EXPOSED LATH . FIRE / SAFETY HAZARD. 2727 W DEVON AVE COMPLAINT FAILED View
DOOR PROJECT INTO PUBLIC WAY WEST ELEVATION COMMERCIAL SPACES . DOORS SWING ONTO PUBLICWAY AND CITY OF CHICAGO SIDEWALK. SAFETY HAZARD TO OCCUPANTS AND PASSERBYS . PERMIT REQUIRED FOR REPAIRS. 2727 W DEVON AVE COMPLAINT FAILED View
REPAIR ROOF ALL THIRD FLOOR APARTMENTS AND HALLS - CEILINGS WATER DAMAGED , ROOF LEAKING . PERMITS REQUIRED FOR ALL FLAT ROOF REPAIRS AND REPLACEMENTS . 2727 W DEVON AVE COMPLAINT FAILED View
REPAIR INTERIOR WALLS/CEILING 6353 COMMERCIAL SPACE - REAR CEILING WATER DAMAGED TILES.2725 EAST 3RD FLOOR APARTMENT - BEDROOM WATER DAMAGED CEILING .2727 EAST 2ND FLOOR APARTMENT - LIVING ROOM WALLS DETERIORATED BEHIND WALL COVERINGS. 6355 SOUTH 2ND FLOOR APARTMENT - BATHROOM CEILING WATER DAMAGED. 2727 COMMERCIAL SPACE - CEILING ABOVE DROP TILES DETERIORATED AND WATER DAMAGED WITH LOOSE AND FALLING PLASTER.6351 3RD FLOOR APARTMENT - KITCHEN CEILING WATER DAMAGED PLASTER. 2727 W DEVON AVE COMPLAINT FAILED View
ARRANGE PREMISE INSPECTION INTERIOR OF COMMERCIAL SPACE AND BASEMENT OF 2729 W. DEVON , NO ENTRY . 2727 W DEVON AVE COMPLAINT FAILED View
REPAIR EXTERIOR STAIR SOUTHEAST EXTERIOR BASEMENT CONCRETE STAIRS BROKEN AND FRACTURED. 2727 W DEVON AVE COMPLAINT FAILED View
FILE BLDG REGISTRATION BUILDING - NOT REGISTERED 1990 THROUGH 2012 YEARS . 2727 W DEVON AVE COMPLAINT FAILED View
REPAIR PORCH SYSTEM REAR PORCHES - FOUNDATIONS STATUS UNKNOWN ; 2 X 8 JOIST SPAN 11'8" . STRINGERS INADEQUATELY SUPPORTED AT COLUMNS ; OPEN RISER DESIGN - 4 1/2" - 6 1/2 " GAPS BETWEEN TREADS ; ROTTING WOOD AT 3RD FLOOR CEILING . RECENTLY BUILT REAR PORCHES ; PLANS AND PERMITS REQUIRED TO REPAIR/REPLACE REAR PORCHES. 2727 W DEVON AVE COMPLAINT FAILED View
RAT STOP AROUND EXTERIOR SOUTH , WEST ELEVATIONS - HOLES , GAPS AT FOUNDATION ALLOWING RATS TO ENTER BUILDING . 2727 W DEVON AVE COMPLAINT FAILED View
REPAIR DEFECTIVE FOUNDATION SOUTH AND WEST ELEVATIONS - GAPS ,HOLES , WASHED OUT MORTAR. 2727 W DEVON AVE COMPLAINT FAILED View
INSECTS #2727 - 3W APARTMENT - INSECTS THRU-OUT . 2727 W DEVON AVE COMPLAINT FAILED View
FIRE EXTNGSHR RECHARGE & TAG #6353 STOREFRONT - FIRE EXTINGUISHER - NOT TAGGED. 2727 W DEVON AVE COMPLAINT FAILED View
MAINTAIN WINDOW SASH ALL ELEVATIONS - WINDOW SASHES - ROTTING ; PAINT PEELING . 2727 W DEVON AVE COMPLAINT FAILED View
MAINTAIN WINDOW ALL ELEVATIONS - WINDOW FRAMES - ROTTING ; PAINT PEELING. 2727 W DEVON AVE COMPLAINT FAILED View
PROVIDE DEADLOCK FOR ENTRANCE NORTH , WEST ELEVATIONS - DEADBOLT LOCKS MISSING AT ALL FRONT ENTRY DOORS. 2727 W DEVON AVE COMPLAINT FAILED View
REPAIR DOOR HARDWARE NORTH AND WEST ELEVATIONS - BUZZER SYSTEM FOR FRONT ENTRY DOORS NOT WORKING AT TIME OF INSPECTION. 2727 W DEVON AVE COMPLAINT FAILED View
PROVIDE GUARD RAIL 42 IN HIGH GUARDRAILS MISSING AT GRADE FOR BASEMENT AREAWAY. 2727 W DEVON AVE COMPLAINT FAILED View
SOIL/WASTE,VENT PIPE MATRL PROVIDE PROPER MATERIAL FOR SOIL / WASTE / VENT PIPE 18-29--702-4 REMOVE ALL P.V.C PIPING INTHE BASEMENTS ALL BASEMENTS. 2727 W DEVON AVE COMPLAINT FAILED View
SEAL DRAIN OPENING UNUSD FIXTR SEAL DRAIN OPENINGS & UNUSED FIXTURES 18-29-102-3 VENT BAR IN THE STORE AT 6349 FAIRFIELD 2727 W DEVON AVE COMPLAINT FAILED View
PRV CAST IRON COVER FOR BASIN PROVIDE CAST IRON COVER FOR SUMP BASIN 18-29-1003-4-1 SOUTH BASEMENT. 2727 W DEVON AVE COMPLAINT FAILED View
REPLACE DEFECTIVE TRAP REPLACE DEFECTIVE TRAP- TRAP FOR BATHTUB AT 2727 W.DEVON 2ND FLOOR WEST NEEDS TO BE REPLACED. IT IS NOW CURRENTLY IN THE BASEMENT OF THE STORE AT 2727 W.DEVON. 2727 W DEVON AVE COMPLAINT FAILED View
SOIL/WASTE,VENT PIPE MATRL PROVIDE PROPER MATERIAL FOR SOIL / WASTE / VENT PIPE 18-29-702-4 DRAIN LINE FROM BATHTUB 2ND FLOOR 2727 W DEVON AVE COMPLAINT FAILED View
NO PERMIT WIRING 2727 COMMERCIAL UNIT ALL WIRING & PANEL MAINTERANCE OF BUILDING WIRING BY NON QUIALIFIED JANITOR DANGEROUS & HAZARDOUS. 2727 W DEVON AVE COMPLAINT FAILED View
DEFECTIVE POWER SERVICE EMERGENCY SERVICE TAMPERED WITH AND LOCKED OFF BY EDISON RESTORE OR REMOVE. PLAN REQUIRES DANGEROUS & HAZARDOUS. 2727 W DEVON AVE COMPLAINT FAILED View
WORKING SPACE PROVIDE CLEAR SPACE & ACCESS TO ALL DISTRIBUTION & SERVICE EQUIPMENT. REMOVE DEBRIS, WATER & PROVIDE CLEAR PATH & LIGHTING. 18-22-110-26,230-70 & 72 DANGEROUS & HAZARDOUS. 2727 W DEVON AVE COMPLAINT FAILED View
FIRE & WATER DAMAGE REPAIR OR REPLACE TO ACCEPTABLE SPECIFICATIONS METERS, PIPES, BOXES & WIRING NORTH BASEMENT. SERVICE DISCONNECTS SOUTHWEST BASEMENT. SEVERE DAMAGE TO FLEX,CONDUIT,BOXES,WIRING & FIXTURES AT CEILING IN NORTHEAST BASEMENT.2727 COMMERCIAL UNIT CEILING WIRING,PANEL & FLEX DAMAGED FROM LEAKS ABOVE. DANGEROUS & HAZARDOUS 2727 W DEVON AVE COMPLAINT FAILED View
SEPARATE CIRCUIT FOR APPLIANCE ALL CENTRAL HEATING UNITS REQUIRE DEDICATED CIRCUITS. ALL COMMERCIAL & DWELLING UNITS 2727 W DEVON AVE COMPLAINT FAILED View
INSTALL COVERS ALL BASEMENTS COMMERCIAL AND DWELLINGS DANGEROUS & HAZAROUS 2727 W DEVON AVE COMPLAINT FAILED View
EXPOSED WIRING SOUTH CENTER, SOUTHWEST AND NORTHEAST BASEMENTS INCLUDING SUMP PUMPS.2725 3RD FLOOR CEILING,2727 2 WEST CEILING,2727 3 EAST CEILING 6355 3 NORTH & SOUTH BATHROOMS DANGEROUS & HAZARDOUS. 2727 W DEVON AVE COMPLAINT FAILED View
UNAPPROVED CORDS 2727 COMMERCIAL UNIT CEILING 6357 COMMERCIAL UNIT CEILING.2727 2ND EAST LIVING ROOM,6351 2ND FLOOR BEDROOM & 6355 3 NORTH LIVING ROOM.DANGEROUS & HAZARDOUS 2727 W DEVON AVE COMPLAINT FAILED View
DEFECTIVE FIXTURES 2725 3RD FLOOR, 2727 2 WEST & 2 EAST, 6355 3 NORTH AND 6351 2ND FLOOR. 2727 W DEVON AVE COMPLAINT FAILED View
ADD RECEPTACLES 6349 COMMERCIAL UNIT TO REMOVE CORDS, 6355 3 NORTH KITCHEN,6351 2ND KITCHEN,2725 2ND FLOOR KITCHEN. 2727 W DEVON AVE COMPLAINT FAILED View
DEFECTIVE OUTLETS ALL DWELLING RECEPTACLES AND SWITCHES COMMERCIAL SPACES AS NEEDED. 2727 W DEVON AVE COMPLAINT FAILED View
SUPPORT OUTLET AND JBOX 2727 WEST LIVING & BATH ROOMS ALSO WHERE NEEDED. 2727 W DEVON AVE COMPLAINT FAILED View
SUPPORT FIXTURES PROPERLY SUPPORT ALL FIXTURES IN ALL DWELLING UNITS 2727 W DEVON AVE COMPLAINT FAILED View
CONTINUITY OF RACEWAY ALL BASEMENTS 2727 W DEVON AVE COMPLAINT FAILED View
REPLACE DAMAGED CLOTH WIRE AT CEILING BOXES 18-27-110.2& 3. 2727 W DEVON AVE COMPLAINT FAILED View
REPAIR OR REPLACE REPLACE BROKEN,RUSTED,IMPROPERLY FASTENED AND INSTALLED HOT WATER FLUE IN SOUTHEAST SECTION OF BASEMENT AND PROPERLY SIZE TO ROOF WITH TIGHT CEMENT SEAL WHERE PASSING INTO OLD CHIMNEY.18-28-802-3 18-28-802.7 18-28-803.9 18-28-803.10.1 18-28-803-10.3 2727 W DEVON AVE COMPLAINT FAILED View
PROVIDE COMBUSTION AIR FOR ALL FUNACE CLOSETS 18-28-703.1, 18-28-703.1, 18-28-703.3 2727 W DEVON AVE COMPLAINT FAILED View
REMOVE DO NOT VENT INTO OLD MASONARY CHIMNEY. MUST HAVE CORRECT SIZE LINER TO ROOF 19-28-801.18.2,18-28-801-18.4, 18-28-920.3, 18-28-801-18.2, 18-28-801.16 2727 W DEVON AVE COMPLAINT FAILED View
CARBON MONOXIDE DETECTORS MUST BE IN ALL RESIDENTIAL AND COMMERCIAL SPACES AND IN BASEMENT WHERE HOT WATER TANK IS LOCATED 18-28-711, 18-28-1013.1 2727 W DEVON AVE COMPLAINT FAILED View
PROVIDE MINIMUM VENT QUANTITY ALL COMMERCIAL SPACES ARE MISSING VENTILATION AND MUST BE PROVIDED WITH ORDINANCE REQUIRED SUPPLY AND EXHAUST VENTILATION 18-28-403, 18-28-103.3 2727 W DEVON AVE COMPLAINT FAILED View
PROVIDE SUPPLY PROVIDE OUTSIDE AIR SUPPLY TO ALL COMMERCIAL SPACES 18-28-403.3 2727 W DEVON AVE COMPLAINT FAILED View
GIVE VENT OPENINGS % FL. AREA PROVIDE EXHAUST TO ALL COMMERCIAL SPACES 18-28-403-3 2727 W DEVON AVE COMPLAINT FAILED View
REMOVE P.V.C FLUES SERVING COMMERCIAL SPACES MUST TERMINATE AT LEAST 4 FEET FROM WINDOWS & DOORS ON 1ST FLOOR 18-28-804.3.4 2727 W DEVON AVE COMPLAINT FAILED View
CITY PROGRAM TO RID VERMIN ALL BROKEN DUCTWORK CONNECTIONS AND HOLES IN PLENUM MUST BE PROPERTLY REPAIRED 18-28-603.3 2727 W DEVON AVE COMPLAINT FAILED View
ALL DUCTWORK CONNECTIONS MUST BE SEALED WITH TYPE 181JEACENT OR TAPE 2727 W DEVON AVE COMPLAINT FAILED View
PROVIDE PROVIDE FILTER RACKS AND FILTERS FOR ALL FURNACES IN BUILDING PER MANUFACTURERS SPECS. 2727 W DEVON AVE COMPLAINT FAILED View
CITY PROGRAM TO RID VERMIN FURNACES CAN NOT BE COMMON VENTED TOGETHER MUST INSTALL INDIVIDUAL FLUE FOR EACH FURNACE 18-28-801.19 2727 W DEVON AVE COMPLAINT FAILED View
(1) FURNACES THAT WERE INSTALLED IN BEDROOMS ARE NOT APPROVED TO BE IN SLEEPING ROOMS AS PER CODE.REMOVE FURNACES IN BEDROOMS OR INSTALL PER CODE 18-28-918-9.2 (2)PROVIDE FRONT CLEARANCE TO FURNACE IN APARTMENT 6355#3S THAT HAS WALL CONSTRUCTED IN FRONT OF 18-28-9.3.3 2727 W DEVON AVE COMPLAINT FAILED View
GIVE VENT OPENINGS % FL. AREA MAKE ALL WINDOWS OPERABLE IN APARTMENTS THAT HAVE BEEN SEALED WITH PAINT COVERS WITH PLYWOOD OR TILED OVER AS IN 2725 #2 (NOTE) ANY WINDOWS NOT PROVIDED TO BATHROOMS MUST HAVE MECHANICAL EXHAUST FANS. 18-28-403.3 2727 W DEVON AVE COMPLAINT FAILED View
REMOVE REMOVE UNAPPROVED KITCHEN HOOD EXHAUST DUCT ON EXTERIOR OF BUILDING THAT IS NOT CORRECT GAUGE,IMPROPER CONNECTIONS,NOT WELDED,IMPROPERLY FASTENED,RUSTED,ECT.DUCT CAN NOT BE USED FOR ANY FUTURE RESTAURANT.18-28-506.1 THRU 18-28-507.17 2727 W DEVON AVE COMPLAINT FAILED View
SUBMIT PLANS/GET VENT PERMIT OBTAIN PERMIT AND ONLY USE LICENSED H.V.A.C.CONTRACTOR TO INSTALL,REPAIR AND CORRECT ALL VIOLATIONS 13-32-020, 13-32-130, 13-40-010, 18-28-403-14 2727 W DEVON AVE COMPLAINT FAILED View
SEAL DRAIN OPENING UNUSD FIXTR SEAL DRAIN OPENINGS & UNUSED FIXTURES 18-29-102-3 VENT BAR IN THE STORE AT 6349 FAIRFIELD 2727 W DEVON AVE COMPLAINT FAILED View
WORKING SPACE PROVIDE CLEAR SPACE & ACCESS TO ALL DISTRIBUTION & SERVICE EQUIPMENT. REMOVE DEBRIS, WATER & PROVIDE CLEAR PATH & LIGHTING. 18-22-110-26,230-70 & 72 DANGEROUS & HAZARDOUS. 2727 W DEVON AVE COMPLAINT FAILED View
CONTINUITY OF RACEWAY ALL BASEMENTS 2727 W DEVON AVE COMPLAINT FAILED View
DEBRIS, EXCESSIVE ALL BASEMENTS STOCKPILED WITH JUNK AND DEBRIS . FIRE / SAFETY HAZARD . RAT HARBORAGE. 2727 W DEVON AVE COMPLAINT FAILED View
STOP/REMOVE NUISANCE REAR BY SOUTHEAST PORCH - METAL GRATE CABINATE WITH PLASTIC GASOLINE CANS STORED AT BASE OF PORCH . REMOVE CABINATE AND ALL GASOLINE STORAGE FROM PROPERTY. FIRE / SAFETY HAZARD. CENTER SOUTH BASEMENT - GASOLINE SNOWTHROWER STORED . REMOVE GASOLINE LAWN AND SNOW EQUIPMENT FROM PROPERTY . FIRE / SAFETY HAZARD. 2727 W DEVON AVE COMPLAINT FAILED View
CARB MONOX DETECT IN RESID SOUTH BASEMENT - CARBON MONOXIDE DETECTOR MISSING . WATER HEATER ROOM. 2727 W DEVON AVE COMPLAINT FAILED View
CONNECT GAS APPLIANCE TO VENT SOUTH BASEMENT - LARGE WATER HEATER FLUE PIPE SAGGING AND DISCONNECTED AT JOINTS. 2727 W DEVON AVE COMPLAINT FAILED View
CHIMNEY SOUTH BASEMENT - OPEN SEAL WITH LOOSE BRICKS AT BASE OF CHIMNEY WITH OPEN MORTAR JOINTS. 2727 W DEVON AVE COMPLAINT FAILED View
REPAIR EXTERIOR STAIR SOUTHEAST EXTERIOR BASEMENT CONCRETE STAIRS BROKEN AND FRACTURED. 2727 W DEVON AVE COMPLAINT FAILED View
FIRE EXTNGSHR RECHARGE & TAG #6353 STOREFRONT - FIRE EXTINGUISHER - NOT TAGGED. 2727 W DEVON AVE COMPLAINT FAILED View
RATS ALL BASEMENTS - SEVERE INFESTATION OF RATS . RAT DROPPINGS COVERING ALL FLOORS . 2727 W DEVON AVE COMPLAINT FAILED View
PROPER SIZE OCP PROVIDE PROPER OVER CURRENT TO PROTECT WIRING FOR ALL FEEDERS AND BRANCIT CIRCUIT WIRING THRU-OUT 2727 W DEVON AVE COMPLAINT FAILED View
RATS 2727W /APT.3W - RAT INFESTED. 2727 W DEVON AVE COMPLAINT CLOSED View
ROACHES 2727W /APT.3W - ROACH INFESTED. 2727 W DEVON AVE COMPLAINT CLOSED View
REPAIR INTERIOR WALLS/CEILING 2727W /APT.3W - CEILINGS HAVE WATER DAMAGED HOLES; BATHROOM HAS BLACK MILDEW LIKE SUBSTANCE OVER WALLS AND CEILING. 2727 W DEVON AVE COMPLAINT CLOSED View
CARPETING 2727W /APT.3W - FILTHY, DIRTY, STAINED CARPETING. 2727 W DEVON AVE COMPLAINT CLOSED View
INT WALL/CEILING CHIP PLASTER 2727W /FRONT INTERIOR STAIRWELL - CHIPPED, CRACKED PAINT MULTIPLE LOCATIONS. 2727 W DEVON AVE COMPLAINT CLOSED View
INSTALL SMOKE DETECTORS 2727W /APT.3W - NO SMOKE DETECTOR. 2727 W DEVON AVE COMPLAINT CLOSED View
REPAIR/REPLACE SMOKE DETECTORS 2727W /FRONT INTERIOR STAIRWELL - SMOKE DETECTOR OUT OF SERVICE. 2727 W DEVON AVE COMPLAINT CLOSED View
DWELLING CLEAN AND SANITARY 2727W /APT.3W - UNSANITARY CONDITIONS. DIRTY WALLS, FLOORS, STOVE, AND FURNITURE. 2727 W DEVON AVE COMPLAINT CLOSED View
INSECTS 2727W /APT.3W - BED BUG INFESTATION THROUGHOUT. PROPERTY MUST EFFECTIVELY TREAT TO EXTERMINATE BED BUGS THROUGHOUT BY EMPLOYING AND EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION. 2727 W DEVON AVE COMPLAINT CLOSED View
SECURE RACEWAY ALL BASEMENTS SERVICE EQUIPMENT IN SOUTHWEST BASEMENT DANGEROUS & HAZARDOUS. 2727 W DEVON AVE COMPLAINT FAILED View
REPAIR WINDOW SILLS #2727- 3W APARTMENT , BATHROOM ROTTING WOOD , DARK SUBSTANCE COVERING SILL. 2727 W DEVON AVE COMPLAINT FAILED View
CONNECT GAS APPLIANCE TO VENT SOUTH BASEMENT - LARGE WATER HEATER FLUE PIPE SAGGING AND DISCONNECTED AT JOINTS. 2727 W DEVON AVE COMPLAINT FAILED View
STOP SMOKE, NOXIOUS ODORS SOUTH BASEMENT , SEWAGE ODORS. 2727 W DEVON AVE COMPLAINT FAILED View
INSPECT CONSTRUCTION WORK RECENTLY BUILT REAR PORCHES . PERMIT #100126863 ISSUED 1-25-2007 VOIDED . " GC LISTED NOT DOING WORK " . PLANS AND PERMIT NOT AVAILABLE FOR REVIEW AT TIME OF INSPECTION . 2727 W DEVON AVE COMPLAINT FAILED View
VERIFY PROPER NEUTRALS WITH BRANCH CIRCUITS FOR ALL DWELLING & COMMERCIAL BRANCH CIRCUITS 18-27-210.4 2727 W DEVON AVE COMPLAINT FAILED View
PRV FLOOR DRAIN WITH METAL STR ALL BASEMENTS MISSING FLOOR DRAIN COVERS. 2727 W DEVON AVE COMPLAINT FAILED View
REPUTTY WINDOW PANES ALL ELEVATIONS - WINDOW TRIM - ROTTING PAINT PEELING. 2727 W DEVON AVE COMPLAINT FAILED View
ROACHES #2727 -3W APARTMENT - ROACHES THRU-OUT . 2727 W DEVON AVE COMPLAINT FAILED View
REMOVE STAGNANT WATER BSMT SOUTH BASEMENT , STANDING WATER AND SEWAGE . 2727 W DEVON AVE COMPLAINT FAILED View
SYSTEM II ENTIRE BUILDING PLANS REQUIRED. 2727 W DEVON AVE COMPLAINT FAILED View
PROVIDE SUPPLY BRANCHS WITH DAMPERS ON ALL DUCTWORK IN RESIDENTIAL & COMMERCIAL SPACES 18-28-603.15 2727 W DEVON AVE COMPLAINT FAILED View
CLEAN ALL FURANCES OF DIRT AND DEBRIS,DO TO NOT HAVING FILTERS AND CRUMBLING CEILINGS FALLING IN CLOSETS. 2727 W DEVON AVE COMPLAINT FAILED View